50
(2) SW2 (Address selector)
(3) SW3 (Emergency operation switch)
(4) SW5 (Model selector)
(5) SW6 (Model selector)
(6) SW7 (Model selector)
Switch to set the output of phase-controlled indoor fan motor.
Address setting is available at any time.
The initial factory setting by is based on each capacity.
SW5-1) Power supply
SW5-2) OFF:For models with heat pump.
ON:For models without heat pump.
SW5-3) Not for use
SW5-4) This switch is unavailable for PKH-FK(S)A-E. Keep this switch at OFF.
Single control
Twin control
Triple control
SW6-1
OFF
ON(Twin NO.1) ON(Triple NO.1)
SW6-2
OFF
ON(Twin NO.2) ON(Triple NO.2)
SW6-3
OFF
OFF
ON(Triple NO.3)
SW6-4
OFF
OFF
ON
Service Ref.
SW7
PKH-1.6FKA-E
PKH-2FKA-E
[3] On indoor controller board
For PKH-2.5FKA-E / PKH-3FKA-E / PKH-4FKSA-E
(1) J1 (Mode selector)
J1-1)
Switch that changes between FAN mode and AUTO mode.
Provided: Fan mode for models with heat pump.
Not provided: AUTO mode for models with heat pump.
J1-4)
Switch for drain pump (For optional parts)
Provided: The drain pump works in only COOL operation.
Not provided: The drain pump works in both COOL and HEAT operation.
J1-5)
Switch to change the temperature to start coil frost prevention.
Provided : 1°C (For all current models)
Not provided: -3°C (For previous special models)
ON :230V/240V
OFF:220V
)
(
Used in setting the unit-address for group control.
For further information, refer to page 68.