41
Minimum 3 minutes
w
2
ON
Thermostat
Indoor fan
Auto vane
Compressor
Power ON lamp
STAND BY lamp
ON
ON
(PKH-2 . 5 / 3 / 4 for
J 1 - 7 , J 1 - 8 )
LOW or HIGH
LOW or HIGH
OFF
OFF
OFF
ON
OFF
ON
OFF
ON
OFF
Extra LOW
w
1
Extra LOW
w
1
Close
10
°
Close
From POWER ON until
warm begins to blow
Depends on remote
controller setting
Depends on remote
controller setting
w
1 Changeable by indoor
dipswitch SW1- 7
and SW1- 8.
LOW
Operation starts by
P O W E R b u t t o n
ON.
Operation stops by
P O W E R b u t t o n
OFF.
Room temperature
becomes equal to
set temperature.
Room temperature
falls below set tem-
perature.
w
2 Even if the room temperature rise above the set temperature during this period, the compressor will not start until this period has ended.
<HEAT operation time chart>
2-3 HEAT operation
<How to operate>
1
Press POWER ON/OFF button.
2
Press the
a
button to display “
g
”.
3
Press the
i
TEMP. button to set the desired temperature.
NOTE: The set temperature changes 1°C when the
or
button is press one time Heating 17 to 28°C.
<Display in HEAT operation>
[ DEFROST ]
The [ DEFROST ] symbol is only displayed during the defrost operation.
[ STANDBY ]
The [ STANDBY ] symbol is displayed from the time the heating opera-
tion starts until the heated air begins to blow.
FILTER
CHECK MODE
TEST RUN
241
(1) Compressor control
1
3-minute time delay
To prevent overload, the compressor will not start within 3, minutes after stop.
2
The compressor runs when the room temperature is lower than the set temperature.
The compressor stops when the room temperature is equal to or higher than the set temperature.
3
The compressor stops in check mode or during protective functions.
4
Overheat protection
<Start condition>
When the indoor coil thermistor reads 70°C or above, the overheat protection will start.
<Overheat protection>
The compressor stops for 6 minutes, and then restarts.
If the start condition is satisfied again within 10 minutes of compressor operation, both the indoor and outdoor units stop,
displaying a check code of “P6” on the remote controller.
<Termination conditions>
Overheat protection is terminated when the start condition is not satisfied again during the allowance (10-minute compres-
sor operation), when operation mode changes to other mode, or when thermostat turns OFF.