6. Electrical work

6.2. Remote controller

6.2.1. For wired remote controller

1) Installing procedures

(1) Select an installing position for the remote controller. (Fig. 6-2)
The temperature sensors are located on both remote controller and indoor unit.

s

Procure the following parts locally:

Two piece switch box
Thin copper conduit tube
Lock nuts and bushings

A

Remote controller profile

B

Required clearances surrounding the remote controller

C

Installation pitch

(2) Seal the service entrance for the remote controller cord with putty to prevent pos-

sible invasion of dew drops, water, cockroaches or worms. (Fig. 6-3)

A

For installation in the switch box:

B

For direct installation on the wall select one of the following:

• Prepare a hole through the wall to pass the remote controller cord (in order to run

the remote controller cord from the back), then seal the hole with putty.

• Run the remote controller cord through the cut-out upper case, then seal the cut-

out notch with putty similarly as above.

B-1. To lead the remote controller cord from the back of the controller:
B-2. To run the remote controller cord through the upper portion:

(3) For direct installation on the wall

C

Wall

D

Conduit

E

Lock nut

F

Bushing

G

Switch box

H

Remote controller cord

I

Seal with putty

J

Wood screw

2) Connecting procedures (Fig. 6-4)

1

Connect the remote controller cord to the terminal block.

A

To TB5 on the indoor unit

B

TB6 (No polarity)

3) Two remote controllers setting

If two remote controllers are connected, set one to “Main” and the other to “Sub”. For
setting procedures, refer to “Function selection of remote controller” in the operation
manual for the indoor unit.

6.2.2. For wireless remote controller

1) Installation area

• Area in which the remote controller is not exposed to direct sunshine.
• Area in which there is no nearby heating source.
• Area in which the remote controller is not exposed to cold (or hot) winds.
• Area in which the remote controller can be operated easily.
• Area in which the remote controller is beyond the reach of children.

2) Installation method (Fig. 6-5)

1

Attach the remote controller holder to the desired location using two tapping screws.

2

Place the lower end of the controller into the holder.

A

Remote controller

B

Wall

C

Display panel

D

Receiver

• The signal can travel up to approximately 7 meters (in a straight line) within 45

degrees to both right and left of the center line of the receiver.

3) Setting (Fig. 6-6)

1

Insert batteries.

2

Press the SET button with something sharp at the end.

MODEL SELECT

 blinks and Model No. is lighted.

3

Press the temp 

 

 button to set the Model No.

4

Press the SET button with something sharp at the end.

MODEL SELECT

 and Model No. are lighted for three seconds, then turned off.

Indoor

Outdoor

A

 Model No.

PLH, PCH, PKH (35, 50)

PUH

001

PLA, PCA, PKA (35, 50)

PUH, PUHZ, SUZ

001

PU

033

PKH (60, 71, 100)

PUH

003

PKA (60, 71, 100)

PUH, PUHZ, SUZ

003

PU

035

30

46

30

30

120

83.5

A

B

C

F

A

H

C

D

E

G

I

I

I

H

B

B-1.

B-2.

Fig. 6-3

A

AB

TB6

B

ON/OFF

  TEMP

FAN

VANE

TEST RUN

AUTO STOP

AUTO START

h

min

LOUVER

MODE

CHECK

RESET

SET

CLOCK

MODEL SELECT

2

,

4

3

A

Fig. 6-5

Fig. 6-6

Fig. 6-2

J

H

Fig. 6-4

B

1

C

A

2

ON

OFF

STAND

BY

COOL

HEAT

D

Содержание Mr.SLIM PKA-RP GAL

Страница 1: ...stallare il condizionatore d aria leggere attentamente il presente manuale ed il manuale d installazione dell unità esterna MANUAL DE INSTALACIÓN Para un uso seguro y correcto lea detalladamente este manual de instalación antes de montar la unidad de aire acondicionado E XEIPI IO O H IøN E KATA TA H È ÛˆÛÙ Î È ÛÊ Ï Ú ÛË È ÛÙ ÚÔÛÂÎÙÈÎ Ùfi ÙÔ ÂÁ ÂÈÚ ÈÔ Î ıÒ Î È ÙÔ ÂÁ ÂÈÚ ÈÔ ÂÁÎ Ù ÛÙ ÛË ÙË Â͈ÙÂÚÈÎ Ì...

Страница 2: ...nit as these items can be damaged by temperature changes or dripping water When the room humidity exceeds 80 or when the drainpipe is clogged wa ter may drip from the indoor unit Do not install the indoor unit where such dripping can cause damage When installing the unit in a hospital or communications office be prepared for noise and electronic interference Inverters home appliances high fre quen...

Страница 3: ...wall mounting fixture determine the unit s installation position and the locations of the piping holes to be drilled Warning Before drilling a hole in the wall you must consult the building contractor A Supporting piece J Bottom right pipe slot ø90 B Mount board K Bottom right pipe slot knockout hole C Main body L Liquid pipe flare connection position D Slot 6 11 20 M Gas pipe flare connection pos...

Страница 4: ...ling pipe and drain pipe together Bind the pipes together with vinyl tape at three or more points This will facilitate passing the pipes through the wall 2 Remove the corner box and knock out the knockout holes as necessary Remove the corner box by pushing in a downward direction b while at the same time pressing in the upper side part of the corner box a A Corner box B Under cover Left and left r...

Страница 5: ...RP60 140 Liquid pipe ø6 35 thickness 0 8 mm ø9 52 thickness 0 8 mm Gas pipe ø12 7 thickness 0 8 mm ø15 88 thickness 1 0 mm Do not use pipes thinner than those specified above 4 2 Connecting pipes Fig 4 1 When commercially available copper pipes are used wrap liquid and gas pipes with commercially available insulation materials heat resistant to 100 C or more thickness of 12 mm or more The indoor p...

Страница 6: ...n outlet B Hooks Remove the side panel of the indoor unit on the drain side Pour water in the drain pan and check that it comes out the drain pipe end After confirmation reinstall the side panel A a b A A B 1 3 2 4 Fig 5 2 4 Installing the refrigerant piping A B C D E F G Fig 4 5 4 3 Positioning refrigerant and drain piping 1 Position of refrigerant and drain piping Fig 4 3 The drain pipe can be c...

Страница 7: ...sed and S3 separated Max 50 m If 6 mm2 used and S3 separated Max 80 m 3 The 10 m wire is attached in the remote controller accessory Max 500 m 4 The figures are NOT always against the ground S3 terminal has DC 24 V against S2 terminal However between S3 and S1 these terminals are not electrically insulataed by the transformer or other device Notes 1 Wiring size must comply with the applicable loca...

Страница 8: ... C Wiring circuit breaker or isolating switch D Outdoor unit E Indoor unit outdoor unit connecting cords F Remote controller G Indoor unit H Option J Indoor unit power supply For models without heater The optional wiring replacement kits are required Simultaneous twin triple four system If the indoor and outdoor units have separate power supplies refer to the table at the below If the optional wir...

Страница 9: ...controllers are connected set one to Main and the other to Sub For setting procedures refer to Function selection of remote controller in the operation manual for the indoor unit 6 2 2 For wireless remote controller 1 Installation area Area in which the remote controller is not exposed to direct sunshine Area in which there is no nearby heating source Area in which the remote controller is not exp...

Страница 10: ... to 04 7 Press the G button and the current set setting number 2 will flash Use the F button to switch the setting number in response to the power supply voltage to be used Power supply voltage 240 V setting number 1 220 V 230 V setting number 2 8 Press the MODE button E and mode and the setting number 1 and 2 will change to being on constantly and the contents of the setting can be confirmed 9 Pr...

Страница 11: ... the test run 2 Press the TEST button twice TEST RUN liquid crystal display 3 Press the Mode selection button Make sure that wind is blown out 4 Press the Mode selection button and switch to the cooling or heating mode Make sure that cold or warm wind is blown out 5 Press the Fan speed button Make sure that the wind speed is switched 6 Check operation of the outdoor unit fan 7 Release test run by ...

Страница 12: ... 1 P1 Intake sensor error 2 P2 P9 Pipe Liquid or 2 phase pipe sensor error 3 E6 E7 Indoor outdoor unit communication error 4 P4 Drain sensor error 5 P5 Drain pump error 6 P6 Freezing Overheating safeguard operation 7 EE Communication error between indoor and outdoor units 8 P8 Pipe temperature error 9 E4 Remote controller signal receiving error 10 11 12 Fb Indoor unit control system error memory e...

Страница 13: ...nnected to the outdoor unit refrigerant address 0 LED 3 communication between indoor and outdoor units Indicates state of communication between the indoor and outdoor units Make sure that this LED is always blinking 7 Test run On wireless remote controller The continuous buzzer sounds from receiving section of indoor unit Blink of operation lamp On wired remote controller Check code displayed in t...

Страница 14: ...ess the ON OFF button to deactivate the maintenance mode Stable operation Using the maintenance mode the operation frequency can be fixed and the op eration can be stabilized If the air conditioner is stopped use the following proce dure to start this operation COOL STABLE MODE HEAT STABLE MODE STABLE MODE CANCEL Stable cooling operation Stable heating operation Stable operation cancellation Displ...

Страница 15: ... EEC Electromagnetic Compatibility Directive 89 336 EEC This product is designed and intended for use in the residential commercial and light industrial environment HEAD OFFICE MITSUBISHI DENKI BLDG 2 2 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN Printed in Japan BG79U615H01 The product at hand is based on the following EU regulations ...