background image

12

7.2.3. Using SW4 in outdoor unit

Refer to the outdoor unit installation manual.

7.3. Self-check

7.3.1. Wired remote controller (Fig. 7-3)

1

Turn on the power.

2

Press the [CHECK] button twice.

3

Set refrigerant address with [TEMP] button if system control is used.

4

Press the [ON/OFF] button to stop the self-check.

A

CHECK button

B

Refrigerant address

C

TEMP. button

D

IC:

Indoor unit

OC: Outdoor unit

E

Check code

F

Unit address

7.3.2. Wireless remote controller (Fig. 7-4)

1

Turn on the power.

2

Press the 

CHECK

 button twice.

(Start this operation from the status of remote controller display turned off.)

A

CHECK

 begins to light.

B

“00” begins to blink.

3

While pointing the remote controller toward the unit’s receiver, press the 

h

button. The check code will be indicated by the number of times that the buzzer
sounds from the receiver section and the number of blinks of the operation lamp.

4

Press the ON/OFF button to stop the self-check.

7. Test run

ON/OFF

  TEMP

FAN

VANE

TEST RUN

AUTO STOP

AUTO START

h

min

LOUVER

MODE

CHECK

RESET

SET

CLOCK

CHECK

2

4

A

3

B

Fig. 7-4

Fig. 7-3

PAR-21MAA

ON/OFF 

FILTER

CHECK

OPERATION

CLEAR

TEST

TEMP.

MENU

BACK

DAY

MONITOR/SET

CLOCK

ON/OFF

ERROR CODE

ERROR CODE

ERROR CODE

C

B

A

B

F

E

E D

[Output pattern A]

Errors detected by indoor unit

Beeper sounds/OPERATION

Symptom

Remark

INDICATOR lamp flashes

Check code

(Number of times)

1

P1

Intake sensor error

2

P2, P9

Pipe (Liquid or 2-phase pipe) sensor error

3

E6, E7

Indoor/outdoor unit communication error

4

P4

Drain sensor error

5

P5

Drain pump error

6

P6

Freezing/Overheating safeguard operation

7

EE

Communication error between indoor and outdoor units

8

P8

Pipe temperature error

9

E4

Remote controller signal receiving error

10

11

12

Fb

Indoor unit control system error (memory error, etc.)

No sound

– –

No corresponding

OPERATION
INDICATOR
lamp flash
pattern

Beep

Beep

Beep

Beep

Beep

Beep

Beep

Off

Approx. 2.5 sec.

On

Approx. 3 sec.

On

0.5 sec.

On

0.5 sec.

On

0.5 sec.

On

0.5 sec.

Off

Approx. 2.5 sec.

On

Approx. 3 sec.

On

0.5 sec.

On

0.5 sec.

· · · Repeated

Number of flashes/beeps in pattern indicates the check
code in the following table (i.e., n=5 for “P5”)

Number of flashes/beeps in pattern indicates
the check code in the following table

n

th

1

st

2

nd

3

rd

1

st

2

nd

Self-check
starts
(Start signal
received)

Beeper sounds

[Output pattern B]

OPERATION
INDICATOR
lamp flash
pattern

Beep

Beep

Beep

Beep

Beep

Beep

Beep

Off

Approx. 2.5 sec.

On

0.5 sec.

On

0.5 sec.

On

0.5 sec.

On

0.5 sec.

Off

Approx. 2.5 sec.

On

0.5 sec.

On

0.5 sec.

· · · Repeated

Number of flashes/beeps in pattern indicates the check
code in the following table (i.e., n=5 for “P5”)

Number of flashes/beeps in pattern indicates
the check code in the following table

n

th

1

st

2

nd

3

rd

1

st

2

nd

Self-check
starts
(Start signal
received)

Beeper sounds

• Refer to the following tables for details on the check codes. (Wireless remote controller)
[Output pattern A]

Wireless remote controller

Wired remote

controller

Содержание Mr.SLIM PKA-RP GAL

Страница 1: ...stallare il condizionatore d aria leggere attentamente il presente manuale ed il manuale d installazione dell unità esterna MANUAL DE INSTALACIÓN Para un uso seguro y correcto lea detalladamente este manual de instalación antes de montar la unidad de aire acondicionado E XEIPI IO O H IøN E KATA TA H È ÛˆÛÙ Î È ÛÊ Ï Ú ÛË È ÛÙ ÚÔÛÂÎÙÈÎ Ùfi ÙÔ ÂÁ ÂÈÚ ÈÔ Î ıÒ Î È ÙÔ ÂÁ ÂÈÚ ÈÔ ÂÁÎ Ù ÛÙ ÛË ÙË Â͈ÙÂÚÈÎ Ì...

Страница 2: ...nit as these items can be damaged by temperature changes or dripping water When the room humidity exceeds 80 or when the drainpipe is clogged wa ter may drip from the indoor unit Do not install the indoor unit where such dripping can cause damage When installing the unit in a hospital or communications office be prepared for noise and electronic interference Inverters home appliances high fre quen...

Страница 3: ...wall mounting fixture determine the unit s installation position and the locations of the piping holes to be drilled Warning Before drilling a hole in the wall you must consult the building contractor A Supporting piece J Bottom right pipe slot ø90 B Mount board K Bottom right pipe slot knockout hole C Main body L Liquid pipe flare connection position D Slot 6 11 20 M Gas pipe flare connection pos...

Страница 4: ...ling pipe and drain pipe together Bind the pipes together with vinyl tape at three or more points This will facilitate passing the pipes through the wall 2 Remove the corner box and knock out the knockout holes as necessary Remove the corner box by pushing in a downward direction b while at the same time pressing in the upper side part of the corner box a A Corner box B Under cover Left and left r...

Страница 5: ...RP60 140 Liquid pipe ø6 35 thickness 0 8 mm ø9 52 thickness 0 8 mm Gas pipe ø12 7 thickness 0 8 mm ø15 88 thickness 1 0 mm Do not use pipes thinner than those specified above 4 2 Connecting pipes Fig 4 1 When commercially available copper pipes are used wrap liquid and gas pipes with commercially available insulation materials heat resistant to 100 C or more thickness of 12 mm or more The indoor p...

Страница 6: ...n outlet B Hooks Remove the side panel of the indoor unit on the drain side Pour water in the drain pan and check that it comes out the drain pipe end After confirmation reinstall the side panel A a b A A B 1 3 2 4 Fig 5 2 4 Installing the refrigerant piping A B C D E F G Fig 4 5 4 3 Positioning refrigerant and drain piping 1 Position of refrigerant and drain piping Fig 4 3 The drain pipe can be c...

Страница 7: ...sed and S3 separated Max 50 m If 6 mm2 used and S3 separated Max 80 m 3 The 10 m wire is attached in the remote controller accessory Max 500 m 4 The figures are NOT always against the ground S3 terminal has DC 24 V against S2 terminal However between S3 and S1 these terminals are not electrically insulataed by the transformer or other device Notes 1 Wiring size must comply with the applicable loca...

Страница 8: ... C Wiring circuit breaker or isolating switch D Outdoor unit E Indoor unit outdoor unit connecting cords F Remote controller G Indoor unit H Option J Indoor unit power supply For models without heater The optional wiring replacement kits are required Simultaneous twin triple four system If the indoor and outdoor units have separate power supplies refer to the table at the below If the optional wir...

Страница 9: ...controllers are connected set one to Main and the other to Sub For setting procedures refer to Function selection of remote controller in the operation manual for the indoor unit 6 2 2 For wireless remote controller 1 Installation area Area in which the remote controller is not exposed to direct sunshine Area in which there is no nearby heating source Area in which the remote controller is not exp...

Страница 10: ... to 04 7 Press the G button and the current set setting number 2 will flash Use the F button to switch the setting number in response to the power supply voltage to be used Power supply voltage 240 V setting number 1 220 V 230 V setting number 2 8 Press the MODE button E and mode and the setting number 1 and 2 will change to being on constantly and the contents of the setting can be confirmed 9 Pr...

Страница 11: ... the test run 2 Press the TEST button twice TEST RUN liquid crystal display 3 Press the Mode selection button Make sure that wind is blown out 4 Press the Mode selection button and switch to the cooling or heating mode Make sure that cold or warm wind is blown out 5 Press the Fan speed button Make sure that the wind speed is switched 6 Check operation of the outdoor unit fan 7 Release test run by ...

Страница 12: ... 1 P1 Intake sensor error 2 P2 P9 Pipe Liquid or 2 phase pipe sensor error 3 E6 E7 Indoor outdoor unit communication error 4 P4 Drain sensor error 5 P5 Drain pump error 6 P6 Freezing Overheating safeguard operation 7 EE Communication error between indoor and outdoor units 8 P8 Pipe temperature error 9 E4 Remote controller signal receiving error 10 11 12 Fb Indoor unit control system error memory e...

Страница 13: ...nnected to the outdoor unit refrigerant address 0 LED 3 communication between indoor and outdoor units Indicates state of communication between the indoor and outdoor units Make sure that this LED is always blinking 7 Test run On wireless remote controller The continuous buzzer sounds from receiving section of indoor unit Blink of operation lamp On wired remote controller Check code displayed in t...

Страница 14: ...ess the ON OFF button to deactivate the maintenance mode Stable operation Using the maintenance mode the operation frequency can be fixed and the op eration can be stabilized If the air conditioner is stopped use the following proce dure to start this operation COOL STABLE MODE HEAT STABLE MODE STABLE MODE CANCEL Stable cooling operation Stable heating operation Stable operation cancellation Displ...

Страница 15: ... EEC Electromagnetic Compatibility Directive 89 336 EEC This product is designed and intended for use in the residential commercial and light industrial environment HEAD OFFICE MITSUBISHI DENKI BLDG 2 2 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN Printed in Japan BG79U615H01 The product at hand is based on the following EU regulations ...

Отзывы: