background image

10

PAR-21MAA

ON/OFF 

FILTER

CHECK

OPERATION

CLEAR

TEST

TEMP.

MENU

BACK

DAY

MONITOR/SET

CLOCK

ON/OFF

A

B

D

C

G

E

F

4

1

2

1

3 4

1

2

A

 Pair No. of wireless remote controller

Indoor PC board

0

Factory setting

1

Cut J41

2

Cut J42

3–9

Cut J41, J42

4) Assigning a remote controller to each unit (Fig. 6-7)

Each unit can be operated only by the assigned remote controller.
Make sure each pair of an indoor unit PC board and a remote controller is assigned
to the same pair No.

5) Wireless remote controller pair number setting operation

1

Press the SET button with something sharp at the end.
Start this operation from the status of remote controller display turned off.

MODEL SELECT

 blinks and Model No. is lighted.

2

Press the 

min

 button twice continuously.

Pair No. “0” blinks.

3

Press the temp 

 

 button to set the pair number you want to set.

4

Press the SET button with something sharp at the end.
Set pair number is lighted for three seconds then turned off.

Fig. 6-7

Fig. 6-8

3

CHECK

4

CHECK

ON/OFF

  TEMP

FAN

VANE

TEST RUN

AUTO STOP

AUTO START

h

min

LOUVER

MODE

CHECK

RESET

SET

CLOCK

CHECK

E

C

,

D

F

A

B

Fig. 6-9

2

CHECK

CHECK

1

6. Electrical work

Mode number

Setting number

Refrigerant address

Unit number

1

2

3

4

ON/OFF

  TEMP

FAN

VANE

TEST RUN

AUTO STOP

AUTO START

h

min

LOUVER

MODE

CHECK

RESET

SET

CLOCK

MODEL SELECT

1

,

4

3

A

2

6.3. Function settings

6.3.1 Function setting on the unit (Selecting the unit functions)

1) For wired remote controller (Fig. 6-8)

Changing the power voltage setting
• Be sure to change the power voltage setting depending on the voltage used.

1

Go to the function setting mode.

Switch OFF the remote controller.
Press the 

A

 and 

B

 buttons simultaneously and hold them for at least 2

seconds. FUNCTION will start to flash.

2

Use the 

C

 button to set the refrigerant address (

3

) to 00.

3

Press 

D

 and [--] will start to flash in the unit number (

4

) display.

4

Use the 

C

 button to set the unit number (

4

) to 00.

5

Press the 

E

 MODE button to designate the refrigerant address/unit number. [--]

will flash in the mode number (

1

) display momentarily.

6

Press the 

F

 buttons to set the mode number (

1

) to 04.

7

Press the 

G

 button and the current set setting number (

2

) will flash.

Use the 

F

 button to switch the setting number in response to the power supply

voltage to be used.
Power supply voltage

240 V

: setting number = 1

220 V, 230 V : setting number = 2

8

Press the MODE button 

E

 and mode and the setting number (

1

) and (

2

) will

change to being on constantly and the contents of the setting can be confirmed.

9

Press the FILTER 

A

 and TEST RUN 

B

 buttons simultaneously for at least two

seconds. The function selection screen will disappear momentarily and the air
conditioner OFF display will appear.

2) For wireless remote controller (Fig. 6-9)

Changing the power voltage setting
• Be sure to change the power voltage setting depending on the voltage used.

1

Go to the function select mode

Press the 

CHECK

 button 

F

 twice continuously.

(Start this operation from the status of remote controller display turned off.)

CHECK

 is lighted and “00” blinks.

Press the temp 

 button 

C

 once to set “50”. Direct the wireless remote controller

toward the receiver of the indoor unit and press the 

h

 button 

A

.

2

Setting the unit number

Press the temp 

 

 button 

C

 and 

D

 to set the unit number “00”. Direct the wireless

remote controller toward the receiver of the indoor unit and press the 

min

 button 

B

.

3

Selecting a mode

Enter 04 to change the power voltage setting using the 

 

C

 and 

 

D

 buttons.

Direct the wireless remote controller toward the receiver of the indoor unit and press

the 

h

 button 

A

.

Current setting number:

1 = 1 beep (one second)
2 = 2 beeps (one second each)
3 = 3 beeps (one second each)

4

Selecting the setting number

Use the 

 

C

 and 

 

D

 buttons to change the power voltage setting to 01 (240 V).

Direct the wireless remote controller toward the sensor of the indoor unit and press

the 

h

 button 

A

.

5

To select multiple functions continuously

Repeat steps 

3

 and 

4

 to change multiple function settings continuously.

6

Complete function selection

Direct the wireless remote controller toward the sensor of the indoor unit and press

the 

 button 

E

.

Note:
Whenever changes are made to the function settings after installation or main-
tenance, be sure to record the changes with a mark in the “Setting” column of
the Function table.

6.3.2 Function setting on the remote controller

Refer to the indoor unit operation manual.

Содержание Mr.SLIM PKA-RP GAL

Страница 1: ...stallare il condizionatore d aria leggere attentamente il presente manuale ed il manuale d installazione dell unità esterna MANUAL DE INSTALACIÓN Para un uso seguro y correcto lea detalladamente este manual de instalación antes de montar la unidad de aire acondicionado E XEIPI IO O H IøN E KATA TA H È ÛˆÛÙ Î È ÛÊ Ï Ú ÛË È ÛÙ ÚÔÛÂÎÙÈÎ Ùfi ÙÔ ÂÁ ÂÈÚ ÈÔ Î ıÒ Î È ÙÔ ÂÁ ÂÈÚ ÈÔ ÂÁÎ Ù ÛÙ ÛË ÙË Â͈ÙÂÚÈÎ Ì...

Страница 2: ...nit as these items can be damaged by temperature changes or dripping water When the room humidity exceeds 80 or when the drainpipe is clogged wa ter may drip from the indoor unit Do not install the indoor unit where such dripping can cause damage When installing the unit in a hospital or communications office be prepared for noise and electronic interference Inverters home appliances high fre quen...

Страница 3: ...wall mounting fixture determine the unit s installation position and the locations of the piping holes to be drilled Warning Before drilling a hole in the wall you must consult the building contractor A Supporting piece J Bottom right pipe slot ø90 B Mount board K Bottom right pipe slot knockout hole C Main body L Liquid pipe flare connection position D Slot 6 11 20 M Gas pipe flare connection pos...

Страница 4: ...ling pipe and drain pipe together Bind the pipes together with vinyl tape at three or more points This will facilitate passing the pipes through the wall 2 Remove the corner box and knock out the knockout holes as necessary Remove the corner box by pushing in a downward direction b while at the same time pressing in the upper side part of the corner box a A Corner box B Under cover Left and left r...

Страница 5: ...RP60 140 Liquid pipe ø6 35 thickness 0 8 mm ø9 52 thickness 0 8 mm Gas pipe ø12 7 thickness 0 8 mm ø15 88 thickness 1 0 mm Do not use pipes thinner than those specified above 4 2 Connecting pipes Fig 4 1 When commercially available copper pipes are used wrap liquid and gas pipes with commercially available insulation materials heat resistant to 100 C or more thickness of 12 mm or more The indoor p...

Страница 6: ...n outlet B Hooks Remove the side panel of the indoor unit on the drain side Pour water in the drain pan and check that it comes out the drain pipe end After confirmation reinstall the side panel A a b A A B 1 3 2 4 Fig 5 2 4 Installing the refrigerant piping A B C D E F G Fig 4 5 4 3 Positioning refrigerant and drain piping 1 Position of refrigerant and drain piping Fig 4 3 The drain pipe can be c...

Страница 7: ...sed and S3 separated Max 50 m If 6 mm2 used and S3 separated Max 80 m 3 The 10 m wire is attached in the remote controller accessory Max 500 m 4 The figures are NOT always against the ground S3 terminal has DC 24 V against S2 terminal However between S3 and S1 these terminals are not electrically insulataed by the transformer or other device Notes 1 Wiring size must comply with the applicable loca...

Страница 8: ... C Wiring circuit breaker or isolating switch D Outdoor unit E Indoor unit outdoor unit connecting cords F Remote controller G Indoor unit H Option J Indoor unit power supply For models without heater The optional wiring replacement kits are required Simultaneous twin triple four system If the indoor and outdoor units have separate power supplies refer to the table at the below If the optional wir...

Страница 9: ...controllers are connected set one to Main and the other to Sub For setting procedures refer to Function selection of remote controller in the operation manual for the indoor unit 6 2 2 For wireless remote controller 1 Installation area Area in which the remote controller is not exposed to direct sunshine Area in which there is no nearby heating source Area in which the remote controller is not exp...

Страница 10: ... to 04 7 Press the G button and the current set setting number 2 will flash Use the F button to switch the setting number in response to the power supply voltage to be used Power supply voltage 240 V setting number 1 220 V 230 V setting number 2 8 Press the MODE button E and mode and the setting number 1 and 2 will change to being on constantly and the contents of the setting can be confirmed 9 Pr...

Страница 11: ... the test run 2 Press the TEST button twice TEST RUN liquid crystal display 3 Press the Mode selection button Make sure that wind is blown out 4 Press the Mode selection button and switch to the cooling or heating mode Make sure that cold or warm wind is blown out 5 Press the Fan speed button Make sure that the wind speed is switched 6 Check operation of the outdoor unit fan 7 Release test run by ...

Страница 12: ... 1 P1 Intake sensor error 2 P2 P9 Pipe Liquid or 2 phase pipe sensor error 3 E6 E7 Indoor outdoor unit communication error 4 P4 Drain sensor error 5 P5 Drain pump error 6 P6 Freezing Overheating safeguard operation 7 EE Communication error between indoor and outdoor units 8 P8 Pipe temperature error 9 E4 Remote controller signal receiving error 10 11 12 Fb Indoor unit control system error memory e...

Страница 13: ...nnected to the outdoor unit refrigerant address 0 LED 3 communication between indoor and outdoor units Indicates state of communication between the indoor and outdoor units Make sure that this LED is always blinking 7 Test run On wireless remote controller The continuous buzzer sounds from receiving section of indoor unit Blink of operation lamp On wired remote controller Check code displayed in t...

Страница 14: ...ess the ON OFF button to deactivate the maintenance mode Stable operation Using the maintenance mode the operation frequency can be fixed and the op eration can be stabilized If the air conditioner is stopped use the following proce dure to start this operation COOL STABLE MODE HEAT STABLE MODE STABLE MODE CANCEL Stable cooling operation Stable heating operation Stable operation cancellation Displ...

Страница 15: ... EEC Electromagnetic Compatibility Directive 89 336 EEC This product is designed and intended for use in the residential commercial and light industrial environment HEAD OFFICE MITSUBISHI DENKI BLDG 2 2 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN Printed in Japan BG79U615H01 The product at hand is based on the following EU regulations ...

Отзывы: