background image

3

3. Installing the indoor unit

Fig. 3-2

A

Independent piece (Removable)

B

Drain tubing

C

Gas tubing

D

Liquid tubing

E

T.B.box

1)

(mm)

2)

A

B

Fig. 3-3

A

Pattern paper

B

Suspension bolt hole

C

Indoor unit width

A

Use inserts of 100 kg to
150 kg each.

B

Use suspension bolts of
W3/8 or M10 in size

Fig. 3-4

(mm)

2. Installation location

2.1. Outline dimensions (Indoor unit) (Fig. 2-1)

Select a proper position allowing the following clearances for installation and mainte-
nance.

(mm)

Models

W

D

H

A

C

E

RP71

1136

650

296

Min. 100

Min. 100

Min. 500

Max. 250

RP125

1520

650

296

Min. 100

Min. 100

Min. 500

Max. 250

 Warning:

Mount the indoor unit on a ceiling strong enough to withstand the weight of the
unit.

More than 300 mm recommended for easy maintenance.

F

Obstacle

Fig. 2-1

Secure the suspension bolts or use angle stock braces or square timbers for bolt
installation. (Fig. 3-4)

3) Selection of suspension bolts and tubing positions (Fig. 3-3)

Using the pattern paper provided for installation, select proper positions for suspen-
sion bolts and tubing and prepare relative holes.

3.2. Preparation for installation (Fig. 3-2)

1) Suspension bolt installing spacing

(mm)

Models

A

B

RP71

1180

1136

RP125

1564

1520

2) Refrigerant and drain tubing location

(mm)

Models

C

RP71

542

RP125

422

3.1. Check the indoor unit accessories (Fig. 3-1)

The indoor unit should be supplied with the following spare parts and accessories
(contained in the inside of the intake grille).

Accessory name

Q’ty

1

Washer

4 pcs + 4 pcs (with insulation)

2

Pipe cover

1 pc

Large size (For gas tubing)

3

Pipe cover

1 pc

Small size (For liquid tubing)

4

Band

4 pcs

5

Drain hose

1 pc

6

Band

2 pcs

7

Drain tubing cover

1 pc

8

Filter element

12 pcs

9

Flare nut

RP125

1 (ø19.05)

RP71

0

Fig. 3-1

1

;

@

€

À

(PAC-SG38KF-E)

2

3

4

5

6

7

8

9

Содержание Mr. Slim PCA-RP-HAQ

Страница 1: ...are il condizionatore d aria leggere attentamente il presente manuale ed il manuale d installazione dell unità esterna MANUAL DE INSTALACIÓN Para un uso seguro y correcto lea detalladamente este manual de instalación antes de montar la unidad de aire acondicionado E XEIPI IO O H IøN E KATA TA H È ÛˆÛÙ Î È ÛÊ Ï Ú ÛË È ÛÙ ÚÔÛÂÎÙÈÎ Ùfi ÙÔ ÂÁ ÂÈÚ ÈÔ Î ıÒ Î È ÙÔ ÂÁ ÂÈÚ ÈÔ ÂÁÎ Ù ÛÙ ÛË ÙË Â͈ÙÂÚÈÎ ÌÔÓ ÚÈ...

Страница 2: ...ons office be prepared for noise and electronic interference Inverters home appliances high fre quency medical equipment and radio communications equipment can cause the air conditioner to malfunction or breakdown The air conditioner may also affect medical equipment disturbing medical care and communications equip ment harming the screen display quality Thermal insulation of the refrigerant pipe ...

Страница 3: ...sion bolts or use angle stock braces or square timbers for bolt installation Fig 3 4 3 Selection of suspension bolts and tubing positions Fig 3 3 Using the pattern paper provided for installation select proper positions for suspen sion bolts and tubing and prepare relative holes 3 2 Preparation for installation Fig 3 2 1 Suspension bolt installing spacing mm Models A B RP71 1180 1136 RP125 1564 15...

Страница 4: ...he below Make sure the insides of the pipes are clean and do not contain any harmful contaminants such as sulfuric com pounds oxidants debris or dust Warning When installing or moving the air conditioner use only the specified refriger ant R410A to charge the refrigerant lines Do not mix it with any other refriger ant and do not allow air to remain in the lines Air enclosed in the lines can cause ...

Страница 5: ...copper pipes are used wrap liquid and gas pipes with commercially available insulation materials heat resistant to 100 C or more thickness of 12 mm or more The indoor parts of the drain pipe should be wrapped with polyethylene foam insu lation materials specific gravity of 0 03 thickness of 9 mm or more Apply thin layer of refrigerant oil to pipe and joint seating surface before tightening flare n...

Страница 6: ...upplied with the unit to the drain hose 5 3 Connect the drain hose 5 to the drain hole of the unit 4 Connect the field drain tubing VP 25 O D ø32 PVC TUBE to the drain hose 5 5 Tighten the band 6 in 2 places 6 Wrap the drain tubing cover 7 supplied with the unit 7 Install the independent piece 8 Check for correct drainage Fill the drain pan with water of about 1 L from the tubing sensor access por...

Страница 7: ...prene sheathed flexible cord Design 245 IEC 57 3 Install an earth longer than other cables Indoor unit model Indoor unit power supply Heater Indoor unit input capacity Heater 1 Main switch Breaker Indoor unit power supply Heater Indoor unit power supply Heater earth Indoor unit Outdoor unit 2 Indoor unit Outdoor unit earth 2 Remote controller Indoor unit 3 Indoor unit Heater L N 4 Indoor unit Outd...

Страница 8: ...code 2 Power supply cords and indoor unit outdoor unit connecting cords shall not be lighter than polychloroprene sheathed flexible cord Design 245 IEC 57 3 Install an earth longer than other cables Indoor unit model Indoor unit power supply Indoor unit input capacity 1 Main switch Breaker Indoor unit power supply Indoor unit power supply earth Indoor unit Outdoor unit 2 Indoor unit Outdoor unit e...

Страница 9: ...ts of the setting can be confirmed 9 Press the FILTER A and TEST RUN B buttons simultaneously for at least two seconds The function selection screen will disappear momentarily and the air conditioner OFF display will appear A To TB5 on the indoor unit B TB6 No polarity 2 Connecting procedures Fig 6 5 Connect the remote controller cord to the terminal block 3 Two remote controller setting If two re...

Страница 10: ...em control is used 4 Press the ON OFF button to stop the self check C C SIMPLE PAR 21MAA ON OFF FILTER CHECK OPERATION CLEAR TEST TEMP MENU BACK DAY MONITOR SET CLOCK ON OFF TEST RUN COOL HEAT A F C E D B M I H G A ON OFF button B Test run display C Indoor temperature liquid line tem perature display D ON OFF lamp E Power display F Error code display Test run remaining time display G Set temperatu...

Страница 11: ...ates whether control power is supplied Make sure that this LED is always lit LED 2 power for remote controller Indicates whether power is supplied to the remote controller This LED lights only in the case of the indoor unit which is connected to the outdoor unit refrigerant address 0 LED 3 communication between indoor and outdoor units Indicates state of communication between the indoor and outdoo...

Страница 12: ... press the ON OFF button to deactivate the maintenance mode Stable operation Using the maintenance mode the operation frequency can be fixed and the op eration can be stabilized If the air conditioner is stopped use the following proce dure to start this operation COOL STABLE MODE HEAT STABLE MODE STABLE MODE CANCEL Stable cooling operation Stable heating operation Stable operation cancellation Di...

Страница 13: ...C This product is designed and intended for use in the residential commercial and light industrial environment HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN Authorized representative in EU MITSUBISHI ELECTRIC EUROPE B V HARMAN HOUSE 1 GEORGE STREET UXBRIDGE MIDDLESEX UB8 1QQ U K Printed in Japan RG79D721H01 The product at hand is based on the following EU regulations ...

Отзывы: