7.2. Test run

The following 2 methods are available.

7.2.1. Using wired remote controller (Fig. 7-1)

1

Turn on the power at least 12 hours before the test run.

2

Press the [TEST] button twice. 

 “TEST RUN” liquid crystal display

3

Press the [Mode selection] button. 

 Make sure that wind is blown out.

4

Press the [Mode selection] button and switch to the cooling (or heating) mode.

 Make sure that cold (or warm) wind is blown out.

5

Press the [Fan speed] button. 

 Make sure that the wind speed is switched.

6

Check operation of the outdoor unit fan.

7

Release test run by pressing the [ON/OFF] button. 

 Stop

8

Register a telephone number.
The telephone number of the repair shop, sales office, etc., to contact if an error
occurs can be registered in the remote controller. The telephone number will be
displayed when an error occurs. For registration procedures, refer to the operation
manual for the indoor unit.

7.2.2. Using SW4 in outdoor unit

Refer to the outdoor unit installation manual.

7.3. Self-check (Fig. 7-2)

1

Turn on the power.

2

Press the [CHECK] button twice.

3

Set refrigerant address with [TEMP.] button if system control is used.

4

Press the [ON/OFF] button to stop the self-check.

˚C

˚C

SIMPLE

PAR-21MAA

ON/OFF 

FILTER

CHECK

OPERATION

CLEAR

TEST

TEMP.

MENU

BACK

DAY

MONITOR/SET

CLOCK

ON/OFF

TEST RUN
COOL, HEAT

A

F

C

E

D B

M

I

H G

A

ON/OFF button

B

Test run display

C

Indoor temperature liquid line tem-
perature display

D

ON/OFF lamp

E

Power display

F

Error code display

Test run remaining time display

G

Set temperature button

H

Mode selection button

I

Fan speed button

M

TEST button

Fig. 7-1

7. Test run

[Output pattern A]

Errors detected by indoor unit

Check code

Symptom

Remark

P1

Intake sensor error

P2, P9

Pipe (Liquid or 2-phase pipe) sensor error

E6, E7

Indoor/outdoor unit communication error

P4

Drain sensor error

P5

Drain pump error

P6

Freezing/Overheating safeguard operation

EE

Communication error between indoor and outdoor units

P8

Pipe temperature error

E4

Remote controller signal receiving error

Fb

Indoor unit control system error (memory error, etc.)

– –

No corresponding

7.1. Before test run

s

After completing installation and the wiring and piping of the indoor and
outdoor units, check for refrigerant leakage, looseness in the power supply
or control wiring, wrong polarity, and no disconnection of one phase in the
supply.

s

Use a 500-volt megohmmeter to check that the resistance between the power
supply terminals and ground is at least 1.0 M

.

s

Do not carry out this test on the control wiring (low voltage circuit) termi-
nals.
 Warning:

Do not use the air conditioner if the insulation resistance is less than 1.0 M

.

Insulation resistance

Содержание Mr. Slim PCA-RP-HAQ

Страница 1: ...are il condizionatore d aria leggere attentamente il presente manuale ed il manuale d installazione dell unità esterna MANUAL DE INSTALACIÓN Para un uso seguro y correcto lea detalladamente este manual de instalación antes de montar la unidad de aire acondicionado E XEIPI IO O H IøN E KATA TA H È ÛˆÛÙ Î È ÛÊ Ï Ú ÛË È ÛÙ ÚÔÛÂÎÙÈÎ Ùfi ÙÔ ÂÁ ÂÈÚ ÈÔ Î ıÒ Î È ÙÔ ÂÁ ÂÈÚ ÈÔ ÂÁÎ Ù ÛÙ ÛË ÙË Â͈ÙÂÚÈÎ ÌÔÓ ÚÈ...

Страница 2: ...ons office be prepared for noise and electronic interference Inverters home appliances high fre quency medical equipment and radio communications equipment can cause the air conditioner to malfunction or breakdown The air conditioner may also affect medical equipment disturbing medical care and communications equip ment harming the screen display quality Thermal insulation of the refrigerant pipe ...

Страница 3: ...sion bolts or use angle stock braces or square timbers for bolt installation Fig 3 4 3 Selection of suspension bolts and tubing positions Fig 3 3 Using the pattern paper provided for installation select proper positions for suspen sion bolts and tubing and prepare relative holes 3 2 Preparation for installation Fig 3 2 1 Suspension bolt installing spacing mm Models A B RP71 1180 1136 RP125 1564 15...

Страница 4: ...he below Make sure the insides of the pipes are clean and do not contain any harmful contaminants such as sulfuric com pounds oxidants debris or dust Warning When installing or moving the air conditioner use only the specified refriger ant R410A to charge the refrigerant lines Do not mix it with any other refriger ant and do not allow air to remain in the lines Air enclosed in the lines can cause ...

Страница 5: ...copper pipes are used wrap liquid and gas pipes with commercially available insulation materials heat resistant to 100 C or more thickness of 12 mm or more The indoor parts of the drain pipe should be wrapped with polyethylene foam insu lation materials specific gravity of 0 03 thickness of 9 mm or more Apply thin layer of refrigerant oil to pipe and joint seating surface before tightening flare n...

Страница 6: ...upplied with the unit to the drain hose 5 3 Connect the drain hose 5 to the drain hole of the unit 4 Connect the field drain tubing VP 25 O D ø32 PVC TUBE to the drain hose 5 5 Tighten the band 6 in 2 places 6 Wrap the drain tubing cover 7 supplied with the unit 7 Install the independent piece 8 Check for correct drainage Fill the drain pan with water of about 1 L from the tubing sensor access por...

Страница 7: ...prene sheathed flexible cord Design 245 IEC 57 3 Install an earth longer than other cables Indoor unit model Indoor unit power supply Heater Indoor unit input capacity Heater 1 Main switch Breaker Indoor unit power supply Heater Indoor unit power supply Heater earth Indoor unit Outdoor unit 2 Indoor unit Outdoor unit earth 2 Remote controller Indoor unit 3 Indoor unit Heater L N 4 Indoor unit Outd...

Страница 8: ...code 2 Power supply cords and indoor unit outdoor unit connecting cords shall not be lighter than polychloroprene sheathed flexible cord Design 245 IEC 57 3 Install an earth longer than other cables Indoor unit model Indoor unit power supply Indoor unit input capacity 1 Main switch Breaker Indoor unit power supply Indoor unit power supply earth Indoor unit Outdoor unit 2 Indoor unit Outdoor unit e...

Страница 9: ...ts of the setting can be confirmed 9 Press the FILTER A and TEST RUN B buttons simultaneously for at least two seconds The function selection screen will disappear momentarily and the air conditioner OFF display will appear A To TB5 on the indoor unit B TB6 No polarity 2 Connecting procedures Fig 6 5 Connect the remote controller cord to the terminal block 3 Two remote controller setting If two re...

Страница 10: ...em control is used 4 Press the ON OFF button to stop the self check C C SIMPLE PAR 21MAA ON OFF FILTER CHECK OPERATION CLEAR TEST TEMP MENU BACK DAY MONITOR SET CLOCK ON OFF TEST RUN COOL HEAT A F C E D B M I H G A ON OFF button B Test run display C Indoor temperature liquid line tem perature display D ON OFF lamp E Power display F Error code display Test run remaining time display G Set temperatu...

Страница 11: ...ates whether control power is supplied Make sure that this LED is always lit LED 2 power for remote controller Indicates whether power is supplied to the remote controller This LED lights only in the case of the indoor unit which is connected to the outdoor unit refrigerant address 0 LED 3 communication between indoor and outdoor units Indicates state of communication between the indoor and outdoo...

Страница 12: ... press the ON OFF button to deactivate the maintenance mode Stable operation Using the maintenance mode the operation frequency can be fixed and the op eration can be stabilized If the air conditioner is stopped use the following proce dure to start this operation COOL STABLE MODE HEAT STABLE MODE STABLE MODE CANCEL Stable cooling operation Stable heating operation Stable operation cancellation Di...

Страница 13: ...C This product is designed and intended for use in the residential commercial and light industrial environment HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN Authorized representative in EU MITSUBISHI ELECTRIC EUROPE B V HARMAN HOUSE 1 GEORGE STREET UXBRIDGE MIDDLESEX UB8 1QQ U K Printed in Japan RG79D721H01 The product at hand is based on the following EU regulations ...

Отзывы: