(mm)

A

Suspending bracket

B

Unit

C

Double nuts (purchased locally)

D

Nut (purchased locally)

E

Washer 

1

 (with insulation)

F

Washer 

1

 (without insulation)

Fig. 3-6

Fig. 3-5

A

Ceiling surface

B

Suspending bolt

C

Suspending bracket

D

Nut (purchased locally)

E

Washer 

1

 (with insula-

tion)

F

Washer 

1

 (without insu-

lation)

3. Installing the indoor unit

4. Installing the refrigerant piping

4.1. Precautions

4.1.1. For devices that use R407C refrigerant

• Do not use the existing refrigerant piping.
• Do not use crushed, misshapen, or discolored tubing. The inside of the tub-

ing should be clean and free from harmful sulfuric compounds, oxidants,
dirt, debris, oils and moisture.

• Store the piping to be used during installation indoors and keep both ends of

the piping sealed until just before brazing.

• Use ester oil, ether oil or alkylbenzene (small amount) as the refrigerator oil

to coat flares and flange connections.

• Use liquid refrigerant to fill the system.
• Do not use a refrigerant other than R407C.
• Use a vacuum pump with a reverse flow check valve.
• Do not use the tools that are used with conventional refrigerants.
• Do not use a charging cylinder.
• Be especially careful when managing the tools.
• Do not use commercially available dryers.

4.1.2. For devices that use R410A refrigerant

• Use ester oil, ether oil, alkylbenzene oil (small amount) as the refrigeration oil

applied to the flared sections.

• Use C1220 copper phosphorus, for copper and copper alloy seamless pipes,

to connect the refrigerant pipes. Use refrigerant pipes with the thicknesses
specified in the table to the below. Make sure the insides of the pipes are
clean and do not contain any harmful contaminants such as sulfuric com-
pounds, oxidants, debris, or dust.

 Warning:

When installing or moving the air conditioner, use only the specified refriger-
ant (R410A) to charge the refrigerant lines. Do not mix it with any other refriger-
ant and do not allow air to remain in the lines. Air enclosed in the lines can
cause pressure peaks resulting in a rupture and other hazards.

RP35, 50

RP60-140

Liquid pipe

ø6.35 thickness 0.8 mm

ø9.52 thickness 0.8 mm

Gas pipe

ø12.7 thickness 0.8 mm

ø15.88 thickness 1.0 mm

• Do not use pipes thinner than those specified above.

3.3. Installing the indoor unit (Fig. 3-6)

Use a proper suspending method depending on the presence or absence of ceiling
materials as side.
In the absence of ceiling materials

1) Directly suspending the unit

Installing procedures
1. Install the washer 

1

 (with insulation) and the nut (to be locally procured).

2. Install the washer 

1

 (without insulation) and the nut (to be locally procured).

3. Set (hook) the unit through the suspending bolts.
4. Tighten the nuts.
Check the unit installing condition.
• Check that the unit is horizontal between the right and left sides.
• Check that the unit slopes continuously downward from the front to the rear.
• Check that the unit is not contacting the ceiling.

4) Indoor unit preparation (Fig. 3-5)

1. Install the suspending bolts. (Procure the W3/8 or M10 bolts locally.)
Predetermine the length from the ceiling (

1

 within 70-90 mm).

2. Remove the intake grille.
Slide the intake grille holding knobs (at two locations) backward to open the intake
grille.
3. Remove the side panel.
Remove the side panel holding screws (one in each side, right and left) then slide the
side panel forward for removal.

Содержание Mr. Slim PCA-RP-HAQ

Страница 1: ...are il condizionatore d aria leggere attentamente il presente manuale ed il manuale d installazione dell unità esterna MANUAL DE INSTALACIÓN Para un uso seguro y correcto lea detalladamente este manual de instalación antes de montar la unidad de aire acondicionado E XEIPI IO O H IøN E KATA TA H È ÛˆÛÙ Î È ÛÊ Ï Ú ÛË È ÛÙ ÚÔÛÂÎÙÈÎ Ùfi ÙÔ ÂÁ ÂÈÚ ÈÔ Î ıÒ Î È ÙÔ ÂÁ ÂÈÚ ÈÔ ÂÁÎ Ù ÛÙ ÛË ÙË Â͈ÙÂÚÈÎ ÌÔÓ ÚÈ...

Страница 2: ...ons office be prepared for noise and electronic interference Inverters home appliances high fre quency medical equipment and radio communications equipment can cause the air conditioner to malfunction or breakdown The air conditioner may also affect medical equipment disturbing medical care and communications equip ment harming the screen display quality Thermal insulation of the refrigerant pipe ...

Страница 3: ...sion bolts or use angle stock braces or square timbers for bolt installation Fig 3 4 3 Selection of suspension bolts and tubing positions Fig 3 3 Using the pattern paper provided for installation select proper positions for suspen sion bolts and tubing and prepare relative holes 3 2 Preparation for installation Fig 3 2 1 Suspension bolt installing spacing mm Models A B RP71 1180 1136 RP125 1564 15...

Страница 4: ...he below Make sure the insides of the pipes are clean and do not contain any harmful contaminants such as sulfuric com pounds oxidants debris or dust Warning When installing or moving the air conditioner use only the specified refriger ant R410A to charge the refrigerant lines Do not mix it with any other refriger ant and do not allow air to remain in the lines Air enclosed in the lines can cause ...

Страница 5: ...copper pipes are used wrap liquid and gas pipes with commercially available insulation materials heat resistant to 100 C or more thickness of 12 mm or more The indoor parts of the drain pipe should be wrapped with polyethylene foam insu lation materials specific gravity of 0 03 thickness of 9 mm or more Apply thin layer of refrigerant oil to pipe and joint seating surface before tightening flare n...

Страница 6: ...upplied with the unit to the drain hose 5 3 Connect the drain hose 5 to the drain hole of the unit 4 Connect the field drain tubing VP 25 O D ø32 PVC TUBE to the drain hose 5 5 Tighten the band 6 in 2 places 6 Wrap the drain tubing cover 7 supplied with the unit 7 Install the independent piece 8 Check for correct drainage Fill the drain pan with water of about 1 L from the tubing sensor access por...

Страница 7: ...prene sheathed flexible cord Design 245 IEC 57 3 Install an earth longer than other cables Indoor unit model Indoor unit power supply Heater Indoor unit input capacity Heater 1 Main switch Breaker Indoor unit power supply Heater Indoor unit power supply Heater earth Indoor unit Outdoor unit 2 Indoor unit Outdoor unit earth 2 Remote controller Indoor unit 3 Indoor unit Heater L N 4 Indoor unit Outd...

Страница 8: ...code 2 Power supply cords and indoor unit outdoor unit connecting cords shall not be lighter than polychloroprene sheathed flexible cord Design 245 IEC 57 3 Install an earth longer than other cables Indoor unit model Indoor unit power supply Indoor unit input capacity 1 Main switch Breaker Indoor unit power supply Indoor unit power supply earth Indoor unit Outdoor unit 2 Indoor unit Outdoor unit e...

Страница 9: ...ts of the setting can be confirmed 9 Press the FILTER A and TEST RUN B buttons simultaneously for at least two seconds The function selection screen will disappear momentarily and the air conditioner OFF display will appear A To TB5 on the indoor unit B TB6 No polarity 2 Connecting procedures Fig 6 5 Connect the remote controller cord to the terminal block 3 Two remote controller setting If two re...

Страница 10: ...em control is used 4 Press the ON OFF button to stop the self check C C SIMPLE PAR 21MAA ON OFF FILTER CHECK OPERATION CLEAR TEST TEMP MENU BACK DAY MONITOR SET CLOCK ON OFF TEST RUN COOL HEAT A F C E D B M I H G A ON OFF button B Test run display C Indoor temperature liquid line tem perature display D ON OFF lamp E Power display F Error code display Test run remaining time display G Set temperatu...

Страница 11: ...ates whether control power is supplied Make sure that this LED is always lit LED 2 power for remote controller Indicates whether power is supplied to the remote controller This LED lights only in the case of the indoor unit which is connected to the outdoor unit refrigerant address 0 LED 3 communication between indoor and outdoor units Indicates state of communication between the indoor and outdoo...

Страница 12: ... press the ON OFF button to deactivate the maintenance mode Stable operation Using the maintenance mode the operation frequency can be fixed and the op eration can be stabilized If the air conditioner is stopped use the following proce dure to start this operation COOL STABLE MODE HEAT STABLE MODE STABLE MODE CANCEL Stable cooling operation Stable heating operation Stable operation cancellation Di...

Страница 13: ...C This product is designed and intended for use in the residential commercial and light industrial environment HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN Authorized representative in EU MITSUBISHI ELECTRIC EUROPE B V HARMAN HOUSE 1 GEORGE STREET UXBRIDGE MIDDLESEX UB8 1QQ U K Printed in Japan RG79D721H01 The product at hand is based on the following EU regulations ...

Отзывы: