5-3. PUMPING DOWN

When relocating or disposing of the air conditioner, pump down the system following
the procedure below so that refrigerant is not released into the atmosphere.
1) Connect the gauge manifold valve to the service port of the stop valve on the gas

pipe side of the outdoor unit.

2) Fully close the stop valve on the liquid pipe side of the outdoor unit.
3) Close the stop valve on the gas pipe side of the outdoor unit almost completely

so that it can be easily closed fully when the pressure gauge shows 0 MPa [Gauge]
(0 lbf/in.

2

[0 kgf/cm

2

]).

4) Start the emergency COOL operation.
 To start the emergency operation in COOL mode, disconnect the power supply

plug and/or turn off the breaker. After 15 seconds, connect the power supply plug
and/or turn on the breaker, and then press the E.O. SW once. (The emergency
COOL operation can be performed continuously for up to 30 minutes.)

5) Fully close the stop valve on the gas pipe side of the outdoor unit when the pressure

gauge shows 0.05 to 0 MPa [Gauge] (approx. 7.25 to 0 lbf/in

2

[0.5 to 0 kgf/cm

2

]).

6) Stop the emergency COOL operation.
 Press the E.O. SW twice to stop the operation.

5. RELOCATION AND MAINTENANCE

HEAD OFFICE: TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO
100-8310, JAPAN

5-1. REMOVING AND INSTALLING THE PANEL  

 

ASSEMBLY

Removal procedure

1) Remove the two screws that attach the panel assembly.

5HPRYHWKHSDQHODVVHPEO\%HVXUHWRUHPRYHLWVERWWRPHQG¿UVW

5-2. REMOVING THE INDOOR UNIT

Remove the bottom of the indoor unit from the installation plate.
When releasing the corner part, release both left and right bottom corner part of

LQGRRUXQLWDQGSXOOLWGRZQZDUGDQGIRUZDUGDVVKRZQLQWKH¿JXUHRQWKHULJKW

Push

Lower

Square hole

Installation procedure

1) Install the panel assembly following the removal procedure in reverse.
2) Be sure to press the positions as indicated by the arrows in order to attach the

assembly completely to the unit.

If the above method cannot be used

Remove the front panel. Then, insert hexagonal wrenches into the square holes on

WKHOHIWDQGULJKWVLGHVRIWKHXQLWDQGSXVKWKHPXSDVVKRZQLQWKHIROORZLQJ¿JXUH

The bottom of the indoor unit lowers and releases the hooks.

Содержание Mr. Slim MSZ-FD09NA

Страница 1: ... parts both in the outlet and on the plug Verify that the power supply plug is completely in the outlet If there is dust blockage or loose parts on the power supply plug or the outlet it could FDXVH HOHFWULF VKRFN RU UH I ORRVH SDUWV DUH IRXQG RQ WKH SRZHU VXSSO SOXJ UHSODFH LW N Securely attach the electrical cover to the indoor unit and the service panel to the outdoor unit If the electrical cov...

Страница 2: ...sibility of vibration Where it is not exposed to direct sunlight Where it can be easily drained At a distance 3 ft 1 m or more away from a TV and radio Operation of the air conditioner may interfere with radio or TV reception An amplifier may be re quired for the affected device In a place as far away as possible from fluorescent and incandescent lights so the infrared remote control can operate t...

Страница 3: ...ver D Seal the wall hole gap with putty H Attach the pipe to wall with pipe at tachment strap E Attachment screw F After the leak test apply insulating mate rial tightly so that there is no gap When the piping is to be attached to a wall comprised of tin plate or metal netting use chemically treated wooden piece 25 32 in 20 mm or thicker between the wall and the piping or wrap insulation vinyl tap...

Страница 4: ... A Fig 3 Attach it to the terminal block Be careful not to make mis wiring Attach the wire to the terminal block securely so that its core cannot be seen and no external force affects the connecting section of the terminal block 7 Firmly tighten the terminal screws After tightening verify that the wires are tightly fas tened 8 Secure indoor outdoor unit connecting wire A and the ground wire with c...

Страница 5: ...the section to which the drain hose is to be attached at the rear of the indoor unit Fig 3 Insert a screwdriver into the hole on the cap and insert the cap fully into the drain pan 5 Insert the drain hose fully into the drain pan at the back right of the indoor unit Fig 4 Check if the hose is hooked securely to the projection of its inserting part at the drain pan 6 Insert the drain hose into wall...

Страница 6: ... pipe in the dimension shown in the table Select A mm from the table according to the tool you use 5 Check RPSDUH WKH ÀDUHG ZRUN ZLWK LJ I ÀDUH LV GHIHFWLYH FXW RII WKH VHFWLRQ DQG UHSHDW SURFHGXUH Terminal block Conduit cover Lead wire 3 OUTDOOR UNIT INSTALLATION Power supply cord K Indoor outdoor unit connecting wire A Make earth wire a little longer than others More than 2 3 8 in 60 mm For futu...

Страница 7: ... 7 After refrigerant pipes are connected and evacuated fully open all stop valves on both sides of gas pipe and liquid pipe Operating the unit without fully opening the valves lowers the performance and causes problems 8 Refer to 1 3 SPECIFICATIONS and charge the prescribed amount of refrigerant if needed Be sure to charge slowly with liquid refrigerant Otherwise composition of the refrigerant in ...

Страница 8: ...ws 0 05 to 0 MPa Gauge approx 7 25 to 0 lbf in2 0 5 to 0 kgf cm2 6 Stop the emergency COOL operation Press the E O SW twice to stop the operation 5 RELOCATION AND MAINTENANCE HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN 5 1 REMOVING AND INSTALLING THE PANEL ASSEMBLY Removal procedure 1 Remove the two screws that attach the panel assembly 5HPRYH WKH SDQHO DVVHPEO H VXUH W...