3-1. CONNECTING WIRES FOR OUTDOOR UNIT

1) Remove the service panel.
2) Remove the conduit cover.
3) Attach the conduit connector to conduit plate with lock nut then secure it against unit with

screws.

4) Connect ground wires of indoor/outdoor unit connecting wire (A) and power supply cord (K)  

to the TB support.

5) Loosen the terminal screw, and attach indoor/outdoor unit connecting wire (A) from the indoor

unit correctly on the terminal block. Attach the wire to the terminal block securely so that its
core cannot be seen, and no external force affects the connecting section of the terminal
block.

6) Firmly tighten the terminal screws. After tightening, verify that the wires are tightly fastened.
7) Connect power supply cord (K).
8) Install the conduit cover.
9) Install the service panel securely.

3-2. FLARE CONNECTION

1) Cut the copper pipe as straight as possible with a pipe cutter. (Fig. 1, 2)
2) Remove all burrs from the cut section of the pipe, ensuring that precautions are taken to

avoid getting metal shavings into the piping. (Fig. 3)

5HPRYHÀDUHQXWVDWWDFKHGWRLQGRRUDQGRXWGRRUXQLWVWKHQSXWWKHPRQSLSH

4) Flaring work (Fig. 4, 5). Firmly hold copper pipe in the dimension shown in the table. Select A

mm from the table according to the tool you use.

5) Check

‡ &RPSDUHWKHÀDUHGZRUNZLWK)LJ
‡ ,IÀDUHLVGHIHFWLYHFXWRIIWKHVHFWLRQDQGUHSHDWSURFHGXUH

Terminal block

Conduit cover

Lead wire

3. OUTDOOR UNIT INSTALLATION

Power supply cord (K)

Indoor/outdoor unit
connecting wire (A)

• Make earth wire a little longer than others.

(More than 2-3/8 in. [60 mm])

• For future servicing, leave some slack in

the connecting wires.

Pipe diameter

inch (mm)

Nut

inch

(mm)

A inch (mm)

Tightening torque

Clutch

type tool

for R410A

Clutch

type tool

for R22

Wing nut

type tool

for R22

N•m

ft•lb

(kgf•cm)

ø 1/4 (6.35)

1/4

(17)

0 to 0.02

(0 to 0.5)

0.04 to

0.06

(1.0 to

1.5)

0.06 to

0.08

(1.5 to

2.0)

13.7 to 17.7

10 to 13

(140 to 180)

ø 3/8 (9.52)

3/8

(22)

34.3 to 41.2

25 to 30

(350 to 420)

ø 1/2 (12.7)

1/2

(26)

0.08 to

0.10

(2.0 to

2.5)

49.0 to 56.4

36 to 42

(500 to 575)

ø 5/8 (15.88)

5/8

(29)

73.5 to 78.4

54 to 58

(750 to 800)

Power supply cord (K)

L1 L2

1-3/8 in.
(35 mm)

19/32 in.
(15 mm)

Service panel

Lock nut

Conduit cover

Conduit plate

Connector

Grounding
terminal

Copper
pipe

Good

90°

Tilted

No good

Fig. 1

Fig. 2

Burr

Copper pipe

Spare reamer

Pipe cutter

Fig. 4

Fig. 3

Smooth all around

Even length
all around

Inside is shin-
ing without any
scratches.

Fig. 5

Fig. 6

A

Flare nut

Die

Copper pipe

Clutch type

Flaring tool

Wing nut type

Uneven Burred

TB support

Содержание Mr. Slim MSZ-FD09NA

Страница 1: ... parts both in the outlet and on the plug Verify that the power supply plug is completely in the outlet If there is dust blockage or loose parts on the power supply plug or the outlet it could FDXVH HOHFWULF VKRFN RU UH I ORRVH SDUWV DUH IRXQG RQ WKH SRZHU VXSSO SOXJ UHSODFH LW N Securely attach the electrical cover to the indoor unit and the service panel to the outdoor unit If the electrical cov...

Страница 2: ...sibility of vibration Where it is not exposed to direct sunlight Where it can be easily drained At a distance 3 ft 1 m or more away from a TV and radio Operation of the air conditioner may interfere with radio or TV reception An amplifier may be re quired for the affected device In a place as far away as possible from fluorescent and incandescent lights so the infrared remote control can operate t...

Страница 3: ...ver D Seal the wall hole gap with putty H Attach the pipe to wall with pipe at tachment strap E Attachment screw F After the leak test apply insulating mate rial tightly so that there is no gap When the piping is to be attached to a wall comprised of tin plate or metal netting use chemically treated wooden piece 25 32 in 20 mm or thicker between the wall and the piping or wrap insulation vinyl tap...

Страница 4: ... A Fig 3 Attach it to the terminal block Be careful not to make mis wiring Attach the wire to the terminal block securely so that its core cannot be seen and no external force affects the connecting section of the terminal block 7 Firmly tighten the terminal screws After tightening verify that the wires are tightly fas tened 8 Secure indoor outdoor unit connecting wire A and the ground wire with c...

Страница 5: ...the section to which the drain hose is to be attached at the rear of the indoor unit Fig 3 Insert a screwdriver into the hole on the cap and insert the cap fully into the drain pan 5 Insert the drain hose fully into the drain pan at the back right of the indoor unit Fig 4 Check if the hose is hooked securely to the projection of its inserting part at the drain pan 6 Insert the drain hose into wall...

Страница 6: ... pipe in the dimension shown in the table Select A mm from the table according to the tool you use 5 Check RPSDUH WKH ÀDUHG ZRUN ZLWK LJ I ÀDUH LV GHIHFWLYH FXW RII WKH VHFWLRQ DQG UHSHDW SURFHGXUH Terminal block Conduit cover Lead wire 3 OUTDOOR UNIT INSTALLATION Power supply cord K Indoor outdoor unit connecting wire A Make earth wire a little longer than others More than 2 3 8 in 60 mm For futu...

Страница 7: ... 7 After refrigerant pipes are connected and evacuated fully open all stop valves on both sides of gas pipe and liquid pipe Operating the unit without fully opening the valves lowers the performance and causes problems 8 Refer to 1 3 SPECIFICATIONS and charge the prescribed amount of refrigerant if needed Be sure to charge slowly with liquid refrigerant Otherwise composition of the refrigerant in ...

Страница 8: ...ws 0 05 to 0 MPa Gauge approx 7 25 to 0 lbf in2 0 5 to 0 kgf cm2 6 Stop the emergency COOL operation Press the E O SW twice to stop the operation 5 RELOCATION AND MAINTENANCE HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN 5 1 REMOVING AND INSTALLING THE PANEL ASSEMBLY Removal procedure 1 Remove the two screws that attach the panel assembly 5HPRYH WKH SDQHO DVVHPEO H VXUH W...

Отзывы: