4 APPLICABLE FUNCTIONS
4.1 Tough drive function
Timing chart
■
Instantaneous power failure time > [Pr. PF25 Instantaneous power failure tough drive -
Detection time]
The alarm occurs when the instantaneous power failure time exceeds [Pr. PF25 Instantaneous power failure tough drive -
Detection time]. MTTR (During tough drive) turns on after the instantaneous power failure is detected.
MBR (Electromagnetic brake interlock) turns off when the alarm occurs.
ALM
[Pr. PF25]
MTTR
MBR
ON
OFF
ON
OFF
ON
OFF
WNG
ON
OFF
ON
OFF
ON
OFF
(DC 158 V)
Power supply
Bus voltage
Undervoltage level
Time for instantaneous power failure
Base circuit
(Warning)
(Tough drive in progress)
(Electromagnetic brake
interlock)
(Malfunction)