62
3 BASIC FUNCTION
3.9 Alarm function
Alarm history
The No. of the alarm that has occurred and the time at which it occurred can be recorded in the history. In the alarm history,
the latest 16 alarms are recorded so that the types of alarms that have occurred in the past can be checked.
The alarm history can be cleared with [Pr. PC21.0 Alarm clear history selection] or on the alarm display of MR Configurator2.
Method for checking with MR Configurator2
1.
Connect the servo amplifier and a personal computer and select "Alarm Display" from "Diagnosis" in MR Configurator2.
2.
The alarm display shows the alarm No., detail number, accumulated time after power-on, and actual time.
Related objects
By using the objects, the alarm occurrence status and alarm history can be checked.
Index
Sub
Object
Name
Data
Type
Access Default
Description
2A00h
0
ARRAY
Alarm history newest
U8
ro
5
The number of the sub object (5) is returned.
1
ARRAY
Alarm No.
U32
ro
0
The Alarm No. and detail number of the alarm that has
occurred are returned. (32 bit)
2
ARRAY
Alarm time (Hour)
U32
ro
0
Alarm occurrence time is returned.
4
ARRAY
Alarm time (second)
U32
ro
0
The alarm occurrence time is returned as a 32-bit integer
(time passed from January 1, 1970, 0:00:00).
5
ARRAY
Alarm time
(nanosecond)
U32
ro
0
In the alarm occurrence time, the digits below the
"second" unit are returned as a 32-bit integer.
2A01h
0
ARRAY
Alarm history 1
U8
ro
2
The number of the sub object (5) is returned.
1
ARRAY
Alarm No.
U32
ro
0
The Alarm No. and detail number of the second alarm are
returned. (32 bit)
2
ARRAY
Alarm time (Hour)
U32
ro
0
The occurrence time of the second alarm is returned.
4
ARRAY
Alarm time (second)
U32
ro
0
The occurrence time of the second alarm is returned as a
32-bit integer (time passed from January 1, 1970,
0:00:00).
5
ARRAY
Alarm time
(nanosecond)
U32
ro
0
In the second alarm occurrence time, the digits below the
"second" unit are returned as a 32-bit integer.
:
:
:
:
:
:
:
:
2A0Fh
0
ARRAY
Alarm history 15
U8
ro
2
The number of the sub object (5) is returned.
1
ARRAY
Alarm No.
U32
ro
0
The Alarm No. and detail number of the 16th alarm are
returned. (32 bit)
2
ARRAY
Alarm time (Hour)
U32
ro
0
The occurrence time of the 16th alarm is returned.
4
ARRAY
Alarm time (second)
U32
ro
0
The occurrence time of the 16th alarm is returned as a 32-
bit integer (time passed from January 1, 1970, 0:00:00).
5
ARRAY
Alarm time
(nanosecond)
U32
ro
0
In the 16th alarm occurrence time, the digits below the
"second" unit are returned as a 32-bit integer.
2A40h
VAR
Clear alarm history
U16
wo
Writing "1EA5h" enables the alarm history to be cleared.
2A41h
VAR
Current alarm
U32
ro
The number of the current alarm is returned. (4 Bytes)
2A44h
VAR
Parameter error number
U16
ro
0
The number of the servo parameter errors are returned.
2A45h
0
ARRAY
Parameter error number
U8
ro
When [AL. 037 Parameter error] occurs, the number of the
servo parameter which causes the error is returned.
1
ARRAY
Parameter error list 1
U16
ro
When [AL. 037 Parameter error] occurs, the first servo
parameter number that caused the alarm is returned.
:
:
:
:
:
:
:
254
ARRAY
Parameter error list 254
U16
ro
When [AL. 037 Parameter error] has occurred, the 254th
servo parameter number that caused the alarm is
returned.
2A46h
VAR
Reset alarm
U16
wo
Writing the value "1EA5h" resets the alarm.