3 EMC COUNTERMEASURES
3.4 Cable layout
13
3
Servo motor power cable (1)
If stripping the cable outer sheath will affect the safety of the machine such as electric shock or injury, it is recommended to
install additional protective covers or enclosures.
Shielded cable
Metal conduit
1.
Use four shielded cables (3-phase + ground cable) to prevent disconnection outside the cabinet. Connect the grounding
terminals of the servo amplifier and servo motor with the grounding cable.
2.
Ground the shield on both the cabinet side and servo motor chassis side. For the reason why the shield should be
grounded on both the cabinet side and servo motor chassis side, refer to the following.
Page 28 Reason for grounding the shield on both the cabinet side and servo motor chassis side
The grounding position of the shield on the servo amplifier side should be within 10 cm from the cabinet. For the reason why
the grounding position of the shield on the servo amplifier side should be within 10 cm from the cabinet, refer to the following.
Cabinet
To servo
amplifier
Shield cable
Servo motor
Connector
Keep as
close as
possible
10 cm or less
Grounding with the P or U clip
Cabinet
To servo
amplifier
Servo motor
Connector
Conduit connector
Multiple core cable
Earth with surface paint removed
Metal
conduit