3 EMC COUNTERMEASURES
3.3 Filter wiring and installation
11
3
Installation
Install the servo amplifier and EMC filter to the same cabinet. Install the filter on the right or left side of the servo amplifier as
shown in the figure below.
For details of the EMC filter, refer to the following.
Page 18 EMC filter (for servo amplifier power supply)
To ensure that the cabinet, filter, and servo amplifier have the same potential, remove or plate paint on the filter surface and
securely ground it to the cabinet.
The same applies to the servo amplifier installation.
Separate the filter input cable (a) from the output cables (b), (c) and (d) as far as possible.
Shorten the wiring ((a), (b), and (c)) between the filter and servo amplifier as short as possible.
(The total of (b) and (c) is 1.5 m or less.)
(a)
(b)
(c)
(d)
Main circuit
power supply
Cabinet
Servo amplifier
EMC Filter
Bare metal or
metal plated
surface
(no paint, etc)
Control circuit
power supply
Power
supply
input
Magnetic
contactor