4 FUNCTIONS
4.2.2 Extended service mode (MODE E)
This is the mode for communicating with the slave station by allocating any I/O area of
the QJ71PB92D buffer memory to each slave station.
Because the I/O area size can be set for each slave station, an empty space is not
produced in the buffer memory of QJ71PB92D. Therefore, the data can be read
from/write to the continuous area of the PLC CPU.
The area of allocation for each slave station is set using the GX Configurator-DP.
The area of allocation in the input and output areas for each station is 0 to 244 bytes (0
to 122 words).
The set number of slave stations 1 to 60.
When an area of 244 bytes (max) is allocated for each station, up to seven stations
can be set up.
After the communication start is completed (X00=ON), the allocated area data
equivalent to an amount of specified number of bytes is transmitted to each slave
station.
Before the communication is started or when it is interrupted, the I/O data is not
updated.