(10) Trouble no information time setting area (Buffer memory address:
2084 (824
H
))
Set the time at seconds unit, which does not inform the communication trouble
after the exchange start. Default value is 20 seconds so the communication
trouble is not informed for 20 seconds after the exchange start. By this setting, in
case the master power supply ON is faster than the slave power supply ON etc.,
it makes possible to prohibit an error that occurs temporary when system starts
up.
(11) Slave status area (Buffer memory address: 2112 (840
H
) to 2116
(844
H
))
This is the area that stores the status of each slave station.
The following figure shows the configuration:
b0
b0
b0
b15
b15
b15
b0
b15
b0
b15
1st station to 16th station
2112(840
H
)
2115(843
H
)
2114(842
H
)
2113(841
H
)
2116(844
H
)
17th station to 32th station
33th station to 48th station
49th station to 60th station
Communication
status area
for all stations
Communication
status area for
individual stations
Communication status (all stations)
Communication status
(station 1 to station 60)
Indicates the communication status for all
stations by a bit.
0: Normal in all stations
1: Faulty station exists
(Fixed at 0)
(Fixed at 0)
Communication status
for all stations
Indicates the communication status of each of the individual
stations by a bit. (Reserve station and not set station are treated
as normal station)
0: Normal
1. Data link error occurred
Buffer memory
address demical
(Hexadecimal)
The communication status of each slave
station under communication is set up.
This area is operated when either the normal
service mode (Mode 0) or extended service
mode (Mode E) is set up.