2 - 3 2 - 3
MELSEC-Q
2 SYSTEM CONFIGURATION
2.3 Precautions for Configuring a System
(1) The following configuration software programs cannot be used on QJ71PB92D.
SW05F-PROFIMAP
MELSEC-PROFIMAP 1.0
MELSEC-PROFIMAP 2.0
MELSEC-PROFIMAP 3.0
(2) The separation prevention function can be used only on those products having
QCPU (Q mode) with serial No. 02092
and subsequent.
If this function is used on products that do not support it, incorrect I/O data will
result.
(3) When performing the following operations, ensure that the module READY signal
X1D of QJ71PB92D is turned ON beforehand.
To switch over the operation mode with Y11/X11, using the sequence program.
To set parameters.
If the status of X1D is ignored and data is read from or written in the buffer
memory, the CPU module may detect an error to stop the sequence calculation.
(4) Do not write parameters in QJ71PB92D simultaneously from a plurality of GX
Configurator-DPs.
The parameter values of QJ71PB92D will become incorrect ones.
(5) If remote parameter setting is performed from GX Configrator-DP to the
QJ71PB92D which is making data exchange, note that PROFIBUS data
exchange will stop during parameter setting.
(6) When setting parameters in GX Configurator-DPs, do not perform the mode
selection using a program.
The parameter setting or mode selection may not be performed correctly.
(7) Combination with MELSECNET/H
QJ71PB92D can be mounted on the MELSECNET/H administrative station and
general stations, but cannot be mounted on MELSECNET/H remote stations.