3 - 2 3 - 2
MELSEC-Q
3 SPECIFICATIONS
3.2 Network Configuration
3.2.1 Basic configuration
1) Equipment types
Class 1 master
GX Configurator-DP
Slave
Repeater
2) Number of units that can be connected to the entire network (when repeaters are
used)
slave
≤
126 units
3) Number that can be connected for 1 segment
slave+repeaters
≤
32 units
4) Communications can be conducted via a maximum of 3 repeaters from an arbitrary
master or arbitrary slave to an arbitrary master or arbitrary slave (Not 3 units in the
entire network).
5) The maximum number of slaves that can be connected to 1 QJ71PB92D is 60
stations.
CPU module
Master (class 1)
QJ71PB92D
GX Configurator-DP
Slave
Slave
Slave
The PROFIBUS-DP cable is provided by the user.
3