![Mitsubishi Electric melsec q00ucpu Скачать руководство пользователя страница 554](http://html.mh-extra.com/html/mitsubishi-electric/melsec-q00ucpu/melsec-q00ucpu_user-manual_239147554.webp)
1
2
3
APPEN-
DIX
6
7
8
Appendix 3 Me
thod of R
epla
cing Basic Mod
el QCPU
or H
igh
Perfor
mance
Model QCPU with U
niversal
Model QCPU
Appendix 3.1 Precautions for Re
placement
APPENDICES
App
-
10
(3)
Drive and file
(4)
External communication (Service processing)
(5) Battery installation position
TableApp.4 Precautions for replacement and replacement methods (Program) (Continued)
Item
Precautions
Replacement method
Reference
File register
To use the file register, capacity setting is
required.
Set the capacity of the file register used in
the PLC file tab of the PLC parameter.
SFC program
The following settings are required for
using SFC programs.
• Program setting (when both sequence
programs and SFC programs exist.)
• Common pointer No. setting (to exe-
cute the CALL instruction from SFC
programs)
• Set program details in the Program tab
of the PLC parameter dialog box.
• Enter a common pointer number in the
PLC system of the PLC parameter dia-
log box.
TableApp.5 Precautions for replacement and replacement methods (Drive and file)
Item
Precautions
Replacement method
Reference
Boot file setting
The boot file setting is not supported.
Since the Universal model QCPU holds
the data in the program memory even
when the battery voltage drops, the boot
file setting is not necessary.
Move files with the boot setting (from the
standard ROM to the program memory) to
the program memory.
TableApp.6 Precautions for replacement and replacement methods (External communication (Service processing))
Item
Precautions
Replacement method
Reference
Time reserved for
communication pro-
cessing
The time reserved for communication pro-
cessing (SM315/SD315) is not supported.
Set service processing time in the PLC
system tab of the PLC parameter dialog
box.
TableApp.7 Precautions for replacement and replacement methods (Battery installation position)
Item
Precautions
Replacement method
Reference
Battery installation
position
The battery replacement method is different.
The battery installation position varies
depending on the model.
• Q00JCPU, Q00CPU, Q01CPU
...On the front of the module.
• Q00UJCPU, Q00UCPU, Q01UCPU
...At the bottom of the module.
For the battery replacement method,
refer to the in the Reference column.
Section 7.2 in the
QCPU User's Manual
(Hardware Design,
Maintenance and
Inspection)
Содержание melsec q00ucpu
Страница 2: ......
Страница 3: ......
Страница 13: ...A 10 Memo ...
Страница 620: ......