12
-
73
(12) Fuse blown module
(13) I/O module verification
(14) Process control instructions
Table12.31 Special register
Number
Name
Meaning
Explanation
Set by
(When Set)
Corres-
ponding
ACPU
D9
Corresponding
CPU
SD1300
Fuse blown
module
Bit pattern in units
of 16 points,
indicating the
modules whose
fuses have blown
0 : No blown fuse
1 : Blown fuse
present
• The numbers of output modules whose fuses have blown are input as a
bit pattern (in units of 16 points).
(If the module numbers are set by parameter, the parameter-set
numbers are stored.)
• Also detects blown fuse condition at remote station output modules
• Not cleared even if the blown fuse is replaced with a new one.
This flag is cleared by error resetting operation.
S (Error)
D9100
Qn(H)
QnPH
QnPRH
QnU
SD1301
D9101
SD1302
D9102
SD1303
D9103
SD1304
D9104
SD1305
D9105
SD1306
D9106
SD1307
D9107
SD1308
New
SD1309
to
SD1330
New
SD1331
New
Table12.32 Special register
Number
Name
Meaning
Explanation
Set by
(When Set)
Corres-
ponding
ACPU
D9
Corresponding
CPU
SD1400
I/O module
verify error
Bit pattern, in units
of 16 points,
indicating the
modules with
verification errors.
0 : No I/O
verification
errors
1 : I/O verification
error present
• When the I/O modules whose I/O module information differs from that
registered at power-ON are detected, the numbers of those I/O modules
are entered in bit pattern.
(If the I/O numbers are set by parameter, the parameter-set numbers
are stored.)
• Also detects I/O module information.
• Not cleared even if the blown fuse is replaced with a new one.
This flag is cleared by error resetting operation.
S (Error)
D9116
Qn(H)
QnPH
QnPRH
QnU
SD1401
D9117
SD1402
D9118
SD1403
D9119
SD1404
D9120
SD1405
D9121
SD1406
D9122
SD1407
D9123
SD1408
New
SD1409
to
SD1430
New
SD1431
New
Table12.33 Special register
Number
Name
Meaning
Explanation
Set by
(When Set)
Corres-
ponding
ACPU
D9
Corresponding
CPU
SD1500
SD1501
Basic period
Basic period tome
• Set the basic period (1 second units) use for the process control
instruction using floating point data.
U
New
QnPH
SD1502
Process control
instruction detail
error code
Process control
instruction detail
error code
• Shows the detailed error contents for the error that occurred in the
process control instruction.
S (Error)
New
SD1503
Process control
instruction
generated error
location
Process control
instruction
generated error
location
• Shows the error process block that occurred in the process control
instruction.
S (Error)
New
SD1506
SD1507
Dummy device
Dummy device
• Used to specify dummy devices by a process control instruction.
U
New
QnPH
QnPRH
SD1508
Function
availability
selection for
process control
instruction
b0
Bumpless function
availability setting
for the S.PIDP
instrunction
0: Enabled
1: Disabled
(Default: 0)
• Selects the availability (enabled/disabled) of the function for process
control instructions.
U
New
QnPH
QnPRH
b15 b1
4
b13 b12 b11b10 b9 b8 b7 b6 b5 b
4
b3 b2 b1 b0
0
0
0
1
(
Y
C0)
0
0
0
0
0
0
0
0
0
0
0
1
(
Y
80)
SD1300
0
0
1
(
Y
1
F
0)
0
0
0
0
0
0
0
0
0
0
1
(
Y
1A0)
SD1301
0
0
0
0
1
Y
1
F
B0
0
0
0
0
0
0
0
0
SD1331
0
0
0
1
Y
1
F
30
0
I
nd
i
cates
fuse
b
l
o
w.
b15 b1
4
b13 b12 b11 b10 b9 b8 b7 b6 b5 b
4
b3 b2 b1 b0
0
0
0
0
0
0
0
0
0
0
0
0
0
SD1
4
00
0
0
0
0
0
0
0
0
0
0
0
SD1
4
01
0
0
0
0
0
0
0
0
0
0
0
SD1
4
31
0
0
0
0
I
nd
i
cates
an
I/O
modu
l
e
ver
i
fy
error
.
0
0
0
0
0
0
1
X Y
0
1
X Y
190
1
X Y
1
FE
0
SD1501
SD1500
Fl
oat
i
ng
po
i
nts
data
=
SD1501
SD1500
Fl
oat
i
ng
po
i
nt
data
=
b0
b1
b2
b15 b14
to
0
0
SD1508
0 1/0
Bumpless function
availability for the
S.PIDP instruction