9.2 Int
ernal User Device
9.2.11
Counter
(C)
9
-
27
9.2.11
Counter (C)
(1) Definition
The counter (C) is a device that counts the number of rises for input conditions in sequence programs.
When the count value matches the set value, the counting stops and its contact is turned on.
The counter is of an incremental type.
(2) Counter types
Counters are mainly classified into the following two types.
• Counter that counts the number of rises for input conditions in sequence programs
• Interrupt counter that counts the number of interrupts occurred
(3) Counting
(a) When the OUT C instruction is executed
The coil of the counter is turned on/off, the current value is updated (the count value + 1), and the contact is
turned on.
In the END processing, the current counter value is not updated and the contact is not turned on.
(b) Current value update (count value + 1)
The current value is updated (count value + 1) at the leading edge (
OFFŮON)
of the
OUT C
instruction.
The current value is not updated while the coil is off, or when it remains on or turns off from on by the OUT C
instruction.
Figure 9.29 Execution and processing of the OUT C instruction
Figure 9.30 Current value update timing
X0
C0
K10
END
OUT C0
END
[Ladder example]
Sequence
program
[Processing at OUT C0 Instruction (X0: OFF to ON)]
Coil ON/OFF
Current value update
Contact ON
Processing
X0
CO
K10
X0
OFF
OFF
ON
ON
END
END
END