FX2N-64CL-M CC-Link/LT Master Block
Troubleshooting 12
12-2
12.2
Confirmation of status based on status indicator LEDs and countermeasures
12.2.1
ONLINE mode
The table below shows the descriptions of errors during in the ONLINE mode (bits 6 and 7 of
the DIP switches are OFF in the FX
2N
-64CL-M), indicated by the status indicator LEDs and
their countermeasures.
Name
Description
Countermeasures
St
a
tus
indic
a
tor
L
E
Ds
POWER
Lit: Power is supplied
Extinguished: Power is not
supplied
Extinguished
• Confirm the capacity of the power for the PLC and
the supplied 5V DC power.
RUN
Lit: FX
2N
-64CL-M is operating
normally
Extinguished: FX
2N
-64CL-M is
abnormal
Power is interrupted
EEPROM read
error (sum
mismatch) occurred
Extinguished
• Confirm the capacity of the power for the PLC and
the supplied 5 VDC power.
• Set the FX
2N
-64CL-M to the CONFIG mode. If
necessary, edit the detailed remote station
information, and write it to the EEPROM.
• If the system is not restored even after confirming
the items above, contact an office of MITSUBISHI
ELECTRIC SYSTEM & SERVICE, CO., LTD.
ERR.
Lit: Communication speed setting
error occurred
EEPROM read error (sum
mismatch) occurred
Flickering: Power supplied for
communication is
abnormal
DIP switch for
operation setting was
changed during
operation
Extinguished: FX
2N
-64CL-M is
operating normally
Lit
• Confirm the DIP switch setting, reset power.
• Set the FX
2N
-64CL-M to the CONFIG mode. If
necessary, edit the detailed remote station
information, and write it to the EEPROM.
Flickering
• Return the DIP switch setting to the status at the
time of power ON.
• If the DIP switch setting should be changed,
change the DIP switch setting, then execute the
CONFIG mode again.
• Confirm connection to the power adapter and the
power supplied to the power adapter. (For the
details of power adapter, refer to the User's Manual
(Detailed Volume) of the power adapter.)
L RUN
Lit: Data link is being executed
Extinguished: Data link is stopped
Extinguished
• Take proper countermeasures according to the
status of other LEDs.
L ERR.
Lit: Use station number
discrepancy
(when BFM#32(20h) to
#95(5Fh) is edited, the station
numbers are checked.)
Outside-control-range station
error occurred
Flickering: Stations are abnormal
Extinguished: Data link is being
executed normally
Lit
• Securely connect the FX
2N
-64CL-M and remote I/O
units.
• Make sure that connected remote I/O units are
consistent with the detailed remote station
information.
Flickering
• Securely connect the FX
2N
-64CL-M and remote I/O
units.
• Make sure that connected remote I/O units are
consistent with the detailed remote station
information.
Содержание MELSEC FX2N-64CL-M
Страница 4: ...FX2N 64CL M CC Link LT Master Block ii ...
Страница 6: ...FX2N 64CL M CC Link LT Master Block iv ...
Страница 12: ...FX2N 64CL M CC Link LT Master Block Generic Names and Abbreviations 2 MEMO ...
Страница 22: ...FX2N 64CL M CC Link LT Master Block System Startup Procedure 3 3 2 MEMO ...
Страница 26: ...FX2N 64CL M CC Link LT Master Block System Configuration 4 4 4 MEMO ...
Страница 34: ...FX2N 64CL M CC Link LT Master Block Connection of Cables Connectors and Terminating Resistors 6 6 6 MEMO ...
Страница 36: ...FX2N 64CL M CC Link LT Master Block Various Modes 7 7 2 MEMO ...