FX2N-64CL-M CC-Link/LT Master Block
Connection of Cables, Connectors and Terminating Resistors 6
6-2
6.1
Connection of units using flat cables dedicated to CC-Link/LT
This paragraph explains the connection method using flat cables dedicated to CC-Link/LT.
1) The connection order of dedicated flat cables has no relevance to the station No.
2) Lay out the FX
2N
-64CL-M at either end of the trunk line.
Connect a terminating resistor on the FX
2N
-64CL-M side in a position that is within 20 cm
from the FX
2N
-64CL-M.
3) Make sure to connect a terminating resistor to each end of the trunk line the CC-Link/LT.
Connect T-branches and remote I/O units using the connectors for dedicated flat cable.
6.2
How to attach connectors used for dedicated flat cable
This paragraph explains how to attach connectors used for the dedicated flat cable.
1) Components
The components are as shown below.
T-branch area
Master station/remote station/power adapter connection area
Trunk line
Drop line
Connector for dedicated
flat cable
Connector for
dedicated
flat cable
Connector for dedicated
flat cable
-Master station (FX
2N
-64CL-M)
-Power adapter (CL1PAD1)
-Terminal block type remote
I/O unit
-Sensor connector type remote
I/O unit
-MIL collector type remote I/O unit
Connector for
dedicated
flat cable
Cable type
remote I/O unit
Connector for dedicated
flat cable
C o m p o n e n t 1 : C o v e r
C o m p o n e n t 2 : B o d y
C o m p o n e n t 3 : D e d i c a t e d f l a t
c a b l e
O r a n g e c o l o r
Содержание MELSEC FX2N-64CL-M
Страница 4: ...FX2N 64CL M CC Link LT Master Block ii ...
Страница 6: ...FX2N 64CL M CC Link LT Master Block iv ...
Страница 12: ...FX2N 64CL M CC Link LT Master Block Generic Names and Abbreviations 2 MEMO ...
Страница 22: ...FX2N 64CL M CC Link LT Master Block System Startup Procedure 3 3 2 MEMO ...
Страница 26: ...FX2N 64CL M CC Link LT Master Block System Configuration 4 4 4 MEMO ...
Страница 34: ...FX2N 64CL M CC Link LT Master Block Connection of Cables Connectors and Terminating Resistors 6 6 6 MEMO ...
Страница 36: ...FX2N 64CL M CC Link LT Master Block Various Modes 7 7 2 MEMO ...