FX2N-64CL-M CC-Link/LT Master Block
Specifications 2
2-3
2.3
Performance specifications
*1 When connected to an FX
1N
Series PLC, up to two FX
2N
-64CL-M can be connected to each of the
main and extension units.
*2 The FX
2N
-64CL-M draws 190mA from the 5V DC source.
The total 5V consumption of all special function blocks connected to a main unit or extension unit
must not exceed the 5V source capacity of the system.
(Refer to the Hardware manual of the applicable PLC)
Item
Specification
Applicable PLC
FX
1N
/FX
2N
/FX
2NC
Series PLC (Section 4.3)
(FX
2NC
-CNV-IF is required when FX
2NC
Series PLC is connected.)
Number of connectable master
blocks
FX
1N
Series: Up to 4
*1
FX
2N
Series: Up to 8
*2
FX
2NC
Series: Up to 3
*2
Applicable point mode
4-point mode and 16-point mode (selectable by DIP switch)
Co
ntr
o
l s
pec
ifi
c
ati
ons
4-point mode
16-point mode
Maximum number of link points
Connected to FX
1N
Series PLC: 128 points
Connected to FX
2N
/FX
2NC
Series PLC: 256 points
(including I/O points in PLC in each case)
Number of link points per station
( ) shows the number of link
points when composite I/O
module is used.
4 points (8 points)
16 points (32 points)
Li
n
k
sc
an
t
im
e
32 stations
Points
128 points
256 points
2.5Mbps
0.7ms
1.0ms
625kbps
2.2ms
3.8ms
156kbps
8.0ms
14.1ms
64 stations
Points
256 points
256 points
2.5Mbps
1.2ms
2.0ms
625kbps
4.3ms
7.4ms
156kbps
15.6ms
27.8ms
Com
m
un
ic
ati
on sp
ec
ifi
c
a
tio
ns
Communication speed
2.5 Mbps, 625 kbps and 156 kbps (selectable by DIP switch)
Protocol
BITR method (Broadcastp Interval Timed Response)
Network topology
T-branch
Error control method
CRC
Number of connected stations
64 stations maximum
Remote station numbers
1 to 64
Master station connection
position
Connected at end of trunk line
RAS function
Communication error detection, automatic return to system, slave station
disconnection and internal loop back diagnosis
Connection cable
Dedicated flat cable (0.75 mm
2
×
4)
Number of occupied I/O points
8 points (fixed) + Number of connected remote I/O points
Current consumption inside 5V DC
190 mA (Supplied by PLC via extension connector)
24V DC power
supply
Voltage
20.4V to 28.8V DC
Supplied from power adapter via
connector for flat cable dedicated to
CC-Link/LT.
Current
consumption
25 mA
Initial current
35 mA
Mass (weight)
0.15 kg (0.33 lbs)
Содержание MELSEC FX2N-64CL-M
Страница 4: ...FX2N 64CL M CC Link LT Master Block ii ...
Страница 6: ...FX2N 64CL M CC Link LT Master Block iv ...
Страница 12: ...FX2N 64CL M CC Link LT Master Block Generic Names and Abbreviations 2 MEMO ...
Страница 22: ...FX2N 64CL M CC Link LT Master Block System Startup Procedure 3 3 2 MEMO ...
Страница 26: ...FX2N 64CL M CC Link LT Master Block System Configuration 4 4 4 MEMO ...
Страница 34: ...FX2N 64CL M CC Link LT Master Block Connection of Cables Connectors and Terminating Resistors 6 6 6 MEMO ...
Страница 36: ...FX2N 64CL M CC Link LT Master Block Various Modes 7 7 2 MEMO ...