FX2N-64CL-M CC-Link/LT Master Block
System Configuration 4
4-2
4.1
Total configuration
This paragraph describes the system configuration and cautions for CC-Link/LT.
•
Connect the master station, power adapter and remote stations using the flat cables
dedicated to CC-Link/LT and the connectors for dedicated flat cables.
•
The connection order of remote stations has no relevance to the station No.
Even if the station No. of remote stations is not consecutive, no error will occur in the data
link.
•
In the CC-Link/LT system, terminating resistors should be connected to both ends of the
trunk line.
Connect the terminating resistor on the FX
2N
-64CL-M side to a position within 200 mm
(7.87") from the FX
2N
-64CL-M.
•
Make sure to lay out the master block on one side of the trunk line.
•
Up to 64 remote stations can be connected to one FX
2N
-64CL-M as far as the condition
shown in the table below are satisfied.
•
Equipment for CC-Link cannot be connected to the CC-Link/LT system.
On the contrary, equipment for CC-Link/LT cannot be connected to the CC-Link system.
•
Refer to the respective instruction manuals when installing the power adapter or remote I/O
units.
•
Refer to the homepage of the CC-Link Partner Association (CLPA) "http://www.cc-link.org/"
for details concerning flat cabling, terminating resistors and connector for CC-Link/LT.
Item
Specification
Remarks
Communication speed
2.5Mbps
625kbps
156kbps
--
Distance between
stations
No restriction
--
Maximum number of
modules connected in 1
drop line
8 units
Maximum number of
remote I/O units connected
per branch in a drop line
Maximum trunk length
35m (114' 9") 100m (328' 1") 500m (1640' 5")
Cable length between
terminating resistors
(excluding drop line length)
T-branch interval
No restriction
--
Maximum drop length
4m (13' 1")
16m (52' 5")
60m (196' 10")
Cable length per branch
Cumulative drop line
length
15m (49' 2")
50m (164' 0")
200m (656' 2")
Sum of all drop lines
PLC main unit
Terminating
resistor
T branch
connection
T-branch interval
Power
adapter
Remote
I/O station
Remote
I/O station
Drop length
(including branch)
Remote
I/O station
Remote
I/O station
Remote
I/O station
Remote
I/O station
Distance between
stations
Terminating
resistor
Trunk length (branch line length not included)
Trunk line
Drop line
Содержание MELSEC FX2N-64CL-M
Страница 4: ...FX2N 64CL M CC Link LT Master Block ii ...
Страница 6: ...FX2N 64CL M CC Link LT Master Block iv ...
Страница 12: ...FX2N 64CL M CC Link LT Master Block Generic Names and Abbreviations 2 MEMO ...
Страница 22: ...FX2N 64CL M CC Link LT Master Block System Startup Procedure 3 3 2 MEMO ...
Страница 26: ...FX2N 64CL M CC Link LT Master Block System Configuration 4 4 4 MEMO ...
Страница 34: ...FX2N 64CL M CC Link LT Master Block Connection of Cables Connectors and Terminating Resistors 6 6 6 MEMO ...
Страница 36: ...FX2N 64CL M CC Link LT Master Block Various Modes 7 7 2 MEMO ...