FX2N-64CL-M CC-Link/LT Master Block
System Configuration 4
4-3
4.2
PLC connection
This paragraph explains which PLC series are connectable with the FX
2N
-64CL-M and
cautions on the number of connectable FX
2N
-64CL-M.
4.2.1
Applicable PLC and number of connectable FX
2N
-64CL-M
•
Connect the FX
2N
-64CL-M to the right side of the PLC using an extension cable.
•
The number of occupied I/O points is "8 (either input or output) Number of
connected remote I/O points".
The total number of I/O points including extended points must not exceed 128 points for the
FX
1N
Series or 256 points for the FX
2N
or FX
2NC
Series.
•
The FX
2N
-64CL-M consumes 190 mA at 5V DC.
The total current consumption at 5V for special blocks connected to the PLC must not
exceed the 5 V power capacity of the main and extension units.
When connecting to the FX
1N
Series PLC, a maximum of two FX
2N
-64CL-M can be
connected to each of the main and extension units.
4.3
Power adapters installation concept
At least one power adapter is required per CC-Link/LT system.
When constructing a system using only one power adapter, the following three conditions
should be satisfied:
1) Total current consumption of remote I/O units, I/O equipment and master unit receiving
power from power adapter
≤
5 A
2) To operate the system in a stable environment, the voltage drop should be equivalent to or
less than 3.6V.
3) Because the minimum operating voltage of each remote I/O unit connected to the power
adapter is 20.4 V, therefore, Supply voltage to power adapter - Voltage drop
≥
20.4 V
If the total current consumption or voltage drop is large, the power adapter position should be
changed or additional power adapters should be installed.
For further details, refer to the "CL1PAD1 (Power Adapter) USER'S MANUAL (Detailed
Volume)" offered separately.
4.4
Power adapter installation condition
For further details on power adapter installation conditions, refer to the "CL1PAD1 (Power
Adapter) USER'S MANUAL (Detailed Volume)" offered separately.
The conditions for installing power adapters to the CC-Link/LT system depend on connected
equipment and wiring length.
Applicable PLC
FX
1N
/FX
2N
/FX
2NC
Series PLC
(FX
2NC
-CNV-IF is required when FX
2NC
Series PLC is connected.)
Number of connectable
master blocks
FX
1N
Series: Up to 4
FX
2N
Series: Up to 8
FX
2NC
Series: Up to 3
Содержание MELSEC FX2N-64CL-M
Страница 4: ...FX2N 64CL M CC Link LT Master Block ii ...
Страница 6: ...FX2N 64CL M CC Link LT Master Block iv ...
Страница 12: ...FX2N 64CL M CC Link LT Master Block Generic Names and Abbreviations 2 MEMO ...
Страница 22: ...FX2N 64CL M CC Link LT Master Block System Startup Procedure 3 3 2 MEMO ...
Страница 26: ...FX2N 64CL M CC Link LT Master Block System Configuration 4 4 4 MEMO ...
Страница 34: ...FX2N 64CL M CC Link LT Master Block Connection of Cables Connectors and Terminating Resistors 6 6 6 MEMO ...
Страница 36: ...FX2N 64CL M CC Link LT Master Block Various Modes 7 7 2 MEMO ...