Specifications 3
3-1
3.
Specifications
3.1
General Specifications
Table 3.1: General Specifications
Item
Description
Operating Temperature
0 ~ 55°C (32 to 131°F)
Storage Temperature
-20 ~ 70°C (-4 to 158°F)
Operating Humidity
35 ~ 85% Relative Humidity, No condensation
Storage Humidity
35 ~ 90% Relative Humidity, No condensation
Vibration Resistance
- Direct Mounting
10 ~ 57Hz: 0.075mm Half Amplitude
57 ~ 150Hz: 9.8m/s
2
Acceleration
Sweep Count for X, Y, Z: 10 times (80 min in each direction)
Vibration Resistance
- DIN rail Mounting
10 ~ 57Hz: 0.035mm Half Amplitude
57 ~ 150Hz: 4.9m/s
2
Acceleration
Sweep Count for X, Y, Z: 10 times (80min in each direction)
Shock Resistance
147m/s
2
Acceleration, Action Time: 11ms
3 times in each direction X, Y, and Z
Noise Immunity
1,000Vp-p, 1microsecond, 30 ~ 100Hz, tested by noise simulator
Dielectric
Withstand Voltage
FX
2N
-32DP-IF
1,500V AC > 1 min, tested between all points, terminals and ground
FX
2N
-32DP-IF-D
500V AC > 1 min, tested between all points, terminals and ground
Insulation Resistance
5M
Ω
> at 500V DC, tested between all points, terminals and ground
Grounding
Grounding resistance is 100
Ω
or less
Complies with
UL508
FX2N-32DP-IF Profibus-DP Interface Unit
Содержание MELSEC FX2N-32DP-IF
Страница 1: ...HARDWARE MANUAL FX2N 32DP IF Profibus DP Interface Unit ...
Страница 4: ...FX2N 32DP IF Profibus DP Interface Unit ii ...
Страница 8: ...FX2N 32DP IF Profibus DP Interface Unit vi ...
Страница 20: ...FX2N 32DP IF Profibus DP Interface Unit Introduction 1 1 10 MEMO ...
Страница 22: ...FX2N 32DP IF Profibus DP Interface Unit Mounting and Wiring 2 2 2 Figure 2 2 Mounting Arrangement ...
Страница 40: ...FX2N 32DP IF Profibus DP Interface Unit Specifications 3 3 4 MEMO ...
Страница 46: ...FX2N 32DP IF Profibus DP Interface Unit Diagnostics 5 5 4 MEMO ...
Страница 53: ......