FX2N-32DP-IF Profibus-DP Interface Unit
Mounting and Wiring 2
2-15
Figure 2.13:Connect to Profibus-DP Network
Table 2.1: Connect to Profibus-DP Network
Ref.
Description
①
Power source for 32DP-IF (Refer to section 3.2)
②
Grounding terminal in 32DP-IF
③
Profibus connector (Refer to Figure 3.10)
④
Grounding plate
⑤
For noise Prevention please attach at least 50mm (1.97”)
of the shielded
twisted-pair
cable along the grounding plate to which the ground terminal is connected.
⑥
Grounding resistance of 100
Ω
or less
⑦
Shielded twisted-pair cable complying with EN50170 to Profibus-DP network
L(24+)
32DP-IF
N(24
-
)
c
d
e
f
g
h
i