JEP0-IL9416
34
Operation
Step Description
Switch Press
Indication
(Reference step 1 above, please)
If correctly, it means ZCT secondary output
is more than 4.1mA, at this time due to
outside of correction range, in order to
correct the error as possible as it can the
value 4.1mA will be remembered.
(3)When item data at “1.5” blinking
Please make sure again about the ZCT
connection and input current.
(Reference step 1 above, please)
If correctly, it means ZCT secondary output
is less than 1.5mA, at this time due to
outside of correction range, in order to
correct the error as possible as it can the
value 1.5mA will be remembered.
Example:
Here, 200:2.1mA as connected ZCT
transformation ratio is shown on the right.
Continue step 4
5
Make sure that the desired data is shown in
the item data box, and press the
SELECT/SET switch to program the data.
When it is detected that new data has been
programmed to be ready for replacing the
currently used setting, the SET.END/TRIP
indicator LED will blink.
At the same time, the item number box will
start blinking instead of the item data box.
Note that the setting being used for the
current operation is still valid even if another
value has been programmed in the item data
box.
SELECT/SET
Once
1
.
2
5
0
9
Item No.
Item data
S E T T IN G /
C A N C E L
S E L E C T /
S E T
S E T .E N D /
T R IP
U P
D O W N
IN D ./
IN D I.E N D
R E S E T
6
-
To put the new data programmed in effect,
press the SET.END/TRIP switch. The
setting currently used will be replaced by
the new data to complete the procedure.
-
To cancel the new data programmed,
press the SETTING/CANCEL switch to
delete all the data programmed,
terminating the procedure.
To put in effect:
SET.END/TRIP
To cancel:
SETTING/
CANCEL
Once
Item No.
Item data
S E T T IN G /
C A N C E L
S E L E C T /
S E T
S E T .E N D /
T R IP
U P
D O W N
IN D ./
IN D I.E N D
R E S E T
In CFP1-A02 type, since the sensitivity for input current is low value which is 1/10 of CFP1-A01 type, the input at the time of
adjustment needs to set at 2A which is 10 times the CFP1-A01 type. In adjustment, please transpose all the above-mentioned
current values to 10 times the value of them.