A - 5 Lapse of time-delayed timer – status indication
<< Example >> To input a current equal to or more than the setting to check the operation timer of the phase fault
time-delayed element A-phase for proper operation:
Operation
Step Description
Switch Press
Indication
1
The indication mode starts.
IND./IND.END
Once
0
0
0.
0
1
0
Item No.
Item data
A-
phase
B-
phase
C-
phase
Zero-
phase
kA
A
2
When the switch is kept depressed until
the item number “320” appears, the laps
of time-delayed of the phase fault
time-delayed A-phase will be indicated.
With “0 A” input, nothing will be displayed
in the item data box.
UP
-
0
2
3
Item No.
Item data
A-
phase
B-
phase
C-
phase
Zero-
phase
kA
A
3
When a current that is equal to or more
than the setting is input, “0” will be
displayed in the item data box.
The value with which the “0” display
appears first should be the starting value
of the phase fault time-delayed element.
At the same time, the operation indicator
LED that corresponds to the element
detected will blink.
None No
0
0
2
3
Item No.
Item data
I >
I
C
>
I
B
>
I
A
>
TRIP
I >>
I
C
>>
I
B
>>
I
A
>>
4
Furthermore, keep inputting currents.
The item data box will be counted up as in
“1”, “2”, …. to ”9”.
None No
1
0
2
3
Item No.
Item data
:
:
9
0
2
3
Item No.
Item data
5
When “10” is shown at last, the output
contact will be operated. Also, the
corresponding operation indicator LED
will come on.
None No
0
1
0
2
3
Item No.
Item data
I >
I
C
>
I
B
>
I
A
>
TRIP
I >>
I
C
>>
I
B
>>
I
A
>>
6
The indication mode ends.
IND./IND.END
Once
Item No.
Item data
A-
phase
B-
phase
C-
phase
Zero-
phase
kA
A