JEP0-IL9416
21
【
D
】
Option mode (Item No. : “800” to “900” range)
This mode can be used to establish contact arrangement, hold the operation indicator LEDs, set the primary current
of the combined current transformer, reset records and test the LED lamps.
D - 1 Specifying contact arrangement
Establish your desired contact arrangement according to the contact arrangement data setting table shown
in the instruction manual of the model.
<< Example >> To change the setting of the contact X
1
(item No. “810”) according to the following
specification:
Currently used specification
(factory default setting)
Target specification
Output condition Earth fault time-delayed only
Phase fault time-delayed A-, B- or
C-phase or earth fault time-delayed
Specification
Contact hold
Auto reset
Self hold
Contact arrangement data
0010
001F
To get your contact arrangement data, first give a desired value for each setting item for which a digit
number is allocated as listed in the contact arrangement data setting table shown below. This will make
up a 16-digit binary code. Then, convert the binary code into a 4-digit hexadecimal code. Note that the
arrangement shown in the table below varies by model. Please refer to the instruction manual that is
specifically prepared for your model.
Input
Digit
No.
Setting item
0 1
0
Self hold / auto reset
Reset
Hold
1
Phase fault time-delayed A-phase
Off
On
2
Phase fault time-delayed B-phase
Off
On
3
Phase fault time-delayed C-phase
Off
On
4
Earth fault time-lag
Off
On
5
Phase fault instantaneous A-phase
Off
On
6
Phase fault instantaneous B-phase
Off
On
7
Phase fault instantaneous C-phase
Off
On
8
Earth fault instantaneous
Off
On
9
Not used
×
10
Not used
×
11
Not used
×
12
Not used
×
13
Not used
×
14
Not used
×
15
OR logic ele
m
en
t com
bina
tion
Not used
×
0
0
0
0
0 0
0
0
0
0
0
1
1
1
1
1
ditto.
1
ditto.
0
Contact arrangement data
0
Conversion from binary number to hexadecimal
Binary
Æ
Hexadecimal
Binary
Æ
Hexadecimal
Binary
Æ
Hexadecimal
0 0 0 0
Æ
0
0 1 1 0
Æ
6
1 1 0 0
Æ
C
0 0 0 1
Æ
1
0 1 1 1
Æ
7
1 1 0 1
Æ
D
0 0 1 0
Æ
2
1 0 0 0
Æ
8
1 1 1 0
Æ
E
0 0 1 1
Æ
3
1 0 0 1
Æ
9
1 1 1 1
Æ
F
0 1 0 0
Æ
4
1 0 1 0
Æ
A
0 1 0 1
Æ
5
1 0 1 1
Æ
B
ditto.
F