JEP0-IL9416
20
Operation
Step Description
Switch Press
Indication
8
Use the UP switch to let the item number “730”
(Contact X
3
) appear in the item No. box.
UP
Once
1
F
o
0
3
7
Item No.
Item data
9
Make sure that the item number “730” is
displayed in the box and press the
SELECT/SET switch. The item data box will
start blinking, instead of the item No. box, so that
data can be changed.
SELECT/SET
Once
0
3
7
Item No.
1
F
o
Item data
10 Instead of “oF” (disabled), select “on” (enabled)
for forced operation in the item data box.
Then, the figure shown in the lowest digit of the
item data box, which indicates the number of
contacts selected for forced operation, will be
added by one.
UP
Once
0
3
7
Item No.
2
n
o
Item data
11 When the SELECT/SET switch is pressed
then for programming, the item No. box will start
blinking, instead of the item data box.
In this case, the SET.END/TRIP indicator LED
still remains blinking, which means that the
specified forced operation has not been
executed.
SELECT/SET
Once
2
n
o
0
3
7
Item No.
Item data
12
-
To execute forced operation of the selected
contacts, press the SET.END/TRIP switch.
Forced operation will be performed only while
this switch is depressed.
During forced operation, the figure shown in the
lowest digit in the item data box which indicates
the number of contacts selected for forced
operation is blinking. Also, the operation
indicator LEDs that correspond to the selected
programmable contacts come on.
2
n
o
0
3
7
Item No.
Item data
I >
I
C
>
I
B
>
I
A
>
TRIP
I >>
I
C
>>
I
B
>>
I
A
>>
When
the SET.END/TRIP switch is
released, the indication of contact operation,
item No. and data will end. Also, the data
programmed for forced operation in the step
above will be all cleared. However, the
operation indicator LEDs will remain the same
status.
To extinguish the operation indicator LED
lamps, press the RESET switch.
To execute:
SET.END/
TRIP
Press and
hold
(operation)
Item No.
Item data
S E T T IN G /
C A N C E L
S E L E C T /
S E T
S E T .E N D /
T R IP
U P
D O W N
IN D ./
IN D I.E N D
R E S E T
-
To terminate the procedure without executing
forced operation, press the
SETTING/CANCEL switch to delete all the
data programmed in the step above.
To cancel:
SETTING/
CANCEL
Once
Item No.
Item data
S E T T IN G /
C A N C E L
S E L E C T /
S E T
S E T .E N D /
T R IP
U P
D O W N
IN D ./
IN D I.E N D
R E S E T