a. COOL ( ) OPERATION
(1) Press OPERATE/STOP (ON/OFF) button.
POWER lamp of the indoor unit turns on with a beep tone.
(2) Select COOL mode with OPERATION SELECT button.
(3) Press TEMPERATURE buttons (TOO WARM or TOO COOL button) to select the desired temperature.
The setting range is 16 ~ 31°C.
1. Coil frost prevention
The compressor operational frequency is controlled by the temperature of the indoor heat exchanger to prevent the coil from
frosting.
When the temperature of indoor heat exchanger becomes too low, the coil frost prevention mode works.
The indoor fan operates at the set speed and the compressor stops. This mode continues until the temperature of indoor
heat exchanger rises.
2. Low outside temperature operation
When the outside temperature is lower, low outside temperature operation starts, and the outdoor fan slows or stops.
b. DRY ( ) OPERATION
(1) Press OPERATE/STOP (ON/OFF) button.
POWER lamp of the indoor unit turns on with a beep tone.
(2) Select DRY mode with OPERATION SELECT button.
(3) The set temperature is determined from the initial room temperature.
1. Coil frost prevention
Coil frost prevention is as same as COOL mode. (a.1)
2. Low outside temperature operation
Low outside temperature operation is as same as COOL mode. (a.2)
c. HEAT ( ) OPERATION
(1) Press OPERATE/STOP (ON/OFF) button.
POWER lamp of the indoor unit turns on with a beep tone.
(2) Select HEAT mode with OPERATION SELECT button.
(3) Press TEMPERATURE buttons (TOO WARM or TOO COOL button) to select the desired temperature.
The setting range is 16 ~ 31°C.
1. Cold air prevention control
When the compressor is not operating or is starting, and the temperature of indoor heat exchanger and/or the room
temperature is low or when defrosting is being done, the indoor fan will stop or rotate in Very Low speed.
2. High pressure protection
The compressor operational frequency is controlled by the temperature of the indoor heat exchanger to prevent the
condensing pressure from increasing excessively.
When the temperature of indoor heat exchanger becomes too high, the high pressure protection works.
The indoor fan operates following the cold air prevention control. This mode continues until the temperature of indoor heat
exchanger falls.
3. Defrosting
Defrosting starts when the temperature of outdoor heat exchanger becomes too low.
The compressor stops once, the indoor/outdoor fans stop, the 4-way valve reverses, and the compressor re-starts.
This mode continues until the temperature of outdoor heat exchanger rises or the fixed time passes.
d. AUTO CHANGE OVER ∙∙∙ AUTO MODE OPERATION
Once desired temperature is set, unit operation is switched automatically between COOL and HEAT operation.
Mode selection
(1) Initial mode
When unit starts the operation with AUTO operation from OFF:
• If the room temperature is higher than the set temperature, operation starts in COOL mode.
• If the room temperature is equal to or lower than the set temperature, operation starts in HEAT mode.
(2) Mode change
COOL mode changes to HEAT mode when about 15 minutes have passed with the room temperature 1°C below the set
temperature.
HEAT mode changes to COOL mode when about 15 minutes have passed with the room temperature 1°C above the set
temperature.
NOTE 1
If two or more indoor units are operating in multi system, there might be a case that the indoor unit, which is operating in
(AUTO), cannot change over to the other operating mode (COOL
HEAT) and becomes a state of standby.
Refer to
NOTE 2 “FOR MULTI SYSTEM AIR CONDITIONER”
.
Содержание M-SERIES
Страница 6: ...M series C WALL MOUNTED ...
Страница 38: ...WALL MOUNTED Outdoor Unit M series WIRING DIAGRAM WALL MOUNTED C 36 MUH GD80VB OUTDOOR UNIT ...
Страница 39: ...WALL MOUNTED Outdoot Unit M series WIRING DIAGRAM WALL MOUNTED C 37 MUZ FD25VA MUZ FD35VA OUTDOOR UNIT ...
Страница 40: ...WALL MOUNTED Outdoor Unit M series WIRING DIAGRAM WALL MOUNTED C 38 OUTDOOR UNIT MUZ FD50VA ...
Страница 41: ...WALL MOUNTED Outdoot Unit M series WIRING DIAGRAM WALL MOUNTED C 39 MUZ FD25VABH MUZ FD35VABH OUTDOOR UNIT ...
Страница 42: ...WALL MOUNTED Outdoor Unit M series WIRING DIAGRAM WALL MOUNTED C 40 OUTDOOR UNIT MUZ FD50VABH ...
Страница 43: ...WALL MOUNTED Outdoot Unit M series WIRING DIAGRAM WALL MOUNTED C 41 MUZ GE25VA MUZ GE35VA OUTDOOR UNIT ...
Страница 44: ...WALL MOUNTED Outdoor Unit M series WIRING DIAGRAM WALL MOUNTED C 42 OUTDOOR UNIT MUZ GE25VAH MUZ GE35VAH ...
Страница 45: ...WALL MOUNTED Outdoot Unit M series WIRING DIAGRAM WALL MOUNTED C 43 MUZ GE42VA OUTDOOR UNIT ...
Страница 46: ...WALL MOUNTED Outdoor Unit M series WIRING DIAGRAM WALL MOUNTED C 44 MUZ GE42VAH OUTDOOR UNIT ...
Страница 47: ...WALL MOUNTED Outdoot Unit M series WIRING DIAGRAM WALL MOUNTED C 45 MUZ GE50VA OUTDOOR UNIT ...
Страница 48: ...WALL MOUNTED Outdoor Unit M series WIRING DIAGRAM WALL MOUNTED C 46 MUZ GE50VAH OUTDOOR UNIT ...
Страница 49: ...WALL MOUNTED Outdoot Unit M series WIRING DIAGRAM WALL MOUNTED C 47 OUTDOOR UNIT MUZ GE60VA MUZ GE71VA ...
Страница 50: ...WALL MOUNTED Outdoor Unit M series WIRING DIAGRAM WALL MOUNTED C 48 MUZ HC25VA OUTDOOR UNIT ...
Страница 51: ...WALL MOUNTED Outdoot Unit M series WIRING DIAGRAM WALL MOUNTED C 49 OUTDOOR UNIT MUZ HC35VA MUZ HC35VAB ...
Страница 192: ...WALL MOUNTED Inverter Heat Pump M series INSTALLATION PROCEDURE WALL MOUNTED C 190 ...
Страница 199: ...WALL MOUNTED MSC MS MSH Series M series C 197 OPERATION AND ACTUATOR CONTROL WALL MOUNTED MUH MUH ...
Страница 202: ...WALL MOUNTED MSC MS MSH Series M series C 200 OPERATION AND ACTUATOR CONTROL WALL MOUNTED MSH g TIMER OPERATION ...
Страница 271: ...FLOOR STANDING MFZ KA VA Series M series OPERATION FLOOR STANDING C 269 ...
Страница 272: ...FLOOR STANDING MFZ KA VA Series M series OPERATION FLOOR STANDING C 270 f i save OPERATION ...
Страница 274: ...FLOOR STANDING MFZ KA VA Series M series OPERATION FLOOR STANDING C 272 i EMERGENCY TEST OPERATION ...
Страница 289: ...CEILING CASSETTE Inverter Heat Pump M series INSTALLATION PROCEDURE CEILING CASSETTE C 287 ...
Страница 290: ...CEILING CASSETTE Inverter Heat Pump M series INSTALLATION PROCEDURE CEILING CASSETTE C 288 ...
Страница 292: ...CEILING CASSETTE Inverter Heat Pump M series INSTALLATION PROCEDURE CEILING CASSETTE C 290 ...
Страница 293: ...CEILING CASSETTE Inverter Heat Pump M series INSTALLATION PROCEDURE CEILING CASSETTE C 291 ...
Страница 294: ...CEILING CASSETTE Inverter Heat Pump M series INSTALLATION PROCEDURE CEILING CASSETTE C 292 ...
Страница 300: ...CEILING CASSETTE M series CEILING CASSETTE C 298 ...
Страница 496: ...M series C 494 MULTI SYSTEM Inverter Heat Pump MULTI SYSTEMS WIRING DIAGRAM OUTDOOR UNIT MXZ 3B54VA ...
Страница 497: ...M series C 495 MULTI SYSTEM Inverter Heat Pump MULTI SYSTEMS WIRING DIAGRAM OUTDOOR UNIT MXZ 3B68VA ...
Страница 498: ...M series C 496 MULTI SYSTEM Inverter Heat Pump MULTI SYSTEMS WIRING DIAGRAM OUTDOOR UNIT MXZ 4B71VA ...
Страница 499: ...M series C 497 MULTI SYSTEM Inverter Heat Pump MULTI SYSTEMS WIRING DIAGRAM OUTDOOR UNIT MXZ 4B80VA ...
Страница 500: ...M series C 498 MULTI SYSTEM Inverter Heat Pump MULTI SYSTEMS WIRING DIAGRAM OUTDOOR UNIT MXZ 5B100VA ...