WALL-MOUNTED Inverter Heat Pump
M series
TROUBLESHOOTING
W
ALL-
MOUNTED
C-166
MUZ-FD50VA
MUZ-FD50VAH
LED1(Red) LED2(Yellow)
Lightning
Twice
Outdoor power system
Lightning
3 times
Discharge temperature
thermistor
Outdoor heat exchanger
temperature thermistor
Defrost thermistor
Lightning
7 times
Nonvolatile memory data
Lightning
8 times
Current sensor
Lightning
11 times
Communication error
between P.C. boards
Lightning
12 times
Zero cross detecting
circuit
Abnormal point/Condition
A short circuit is detected in the thermistor during operation,
or an open circuit is detected in the thermistor after 5 minutes
(in cooling) and 10 minutes (in heating) of compressor start-up.
A short circuit is detected in the thermistor during operation,
or an open circuit is detected in the thermistor after 5 minutes
of compressor start-up.
Indication
Overcurrent protection stop is continuously performed
3 times within 1 minute after the compressor gets
started, or when converter protection stop or bus-bar
voltage protection stop is continuously performed 3
times within 3 minutes after start-up.
A short circuit is detected in the thermistor during
operation, or an open circuit is detected in the
thermistor after 10 minutes of compressor start-up.
Condition
The nonvolatile memory data cannot be read properly.
Lightning
6 times
Serial signal
Fin temperature
thermistor
P.C board temperature
thermistor
Lightning
4 times
Ambient temperature
thermistor
Current sensor protection stop is continuously performed twice.
The communication protection stop between boards is
continuously performed twice.
The protection stop of the zero cross detecting circuit is
continuously performed 10 times.
A short or open circuit is detected in the thermistor
during operation.
A short or open circuit is detected in the thermistor
during operation.
5 times
Lightning
Outdoor electronic control P.C. board(Parts side)
Lighting
IPM protection
Lock protection
3 times
Goes out
Discharge temperature
protection
Fin temperature
protection
P.C. board temperature
protection
High-pressure
protection
8 times
Goes out
Converter protection
Bus-bar voltage
protection (1)
Bus-bar voltage
protection (2)
13 times
Goes out
Outdoor fan motor
Lighting
8 times
Current sensor
protection
Lighting
11 times
Communication between P.C.
boards protection
Lighting
12 times
Zero cross detecting circuit
protection
Twice
Goes out
4 times
Goes out
5 times
Goes out
9 times
Goes out
Overcurrent is detected after 30 minutes of compressor start-up.
Overcurrent is detected within 30 minutes of compressor
start-up.
The bus-bar voltage exceeds 400V or falls to 200V or below
during compressor operating.
The bus-bar voltage exceeds 400V or falls to 50V or below
during compressor operating.
Discharge temperature exceeds 116
during operation and
compressor stops. Compressor can restart if discharge
temperature thermistor reads 100
or less 3 minutes later.
The fin temperature exceeds 87
during operation.
The P.C. board temperature exceeds 70
during operation.
Failure occurs continuously 3 times within 30 seconds after the
fan gets started.
A short or open circuit is detected in the current sensor during
compressor operating.
Communication error occurs between the outdoor electronic
control P.C. board and power board for more than 10 seconds.
Zero cross signal cannot be detected while the compressor is
operating.
The outdoor heat exchanger temperature exceeds 70
during
cooling or indoor gas pipe temperature exceeds 70
during
heating.
A failure is detected in the operation of the converter during
operation.
Outdoor unit
does not
operate.
LED2 LED1
The communication fails between the indoor and outdoor
unit for 3 minutes.
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
Symptom
'Outdoor unit
stops and
restarts 3
minutes
later' is
repeated.
ON
OFF
2.5-second OFF
2.5-second OFF
The flashing frequency shows the number of times the LED blinks after every 2.5-second OFF.
(Example) When the flashing frequency is “2”.
0.5-second ON
0.5-second ON
NOTE 1. The location of LED is illustrated at the right figure.
2. LED is lighted during normal operation.
Troubleshooting check table
Содержание M-SERIES
Страница 6: ...M series C WALL MOUNTED ...
Страница 38: ...WALL MOUNTED Outdoor Unit M series WIRING DIAGRAM WALL MOUNTED C 36 MUH GD80VB OUTDOOR UNIT ...
Страница 39: ...WALL MOUNTED Outdoot Unit M series WIRING DIAGRAM WALL MOUNTED C 37 MUZ FD25VA MUZ FD35VA OUTDOOR UNIT ...
Страница 40: ...WALL MOUNTED Outdoor Unit M series WIRING DIAGRAM WALL MOUNTED C 38 OUTDOOR UNIT MUZ FD50VA ...
Страница 41: ...WALL MOUNTED Outdoot Unit M series WIRING DIAGRAM WALL MOUNTED C 39 MUZ FD25VABH MUZ FD35VABH OUTDOOR UNIT ...
Страница 42: ...WALL MOUNTED Outdoor Unit M series WIRING DIAGRAM WALL MOUNTED C 40 OUTDOOR UNIT MUZ FD50VABH ...
Страница 43: ...WALL MOUNTED Outdoot Unit M series WIRING DIAGRAM WALL MOUNTED C 41 MUZ GE25VA MUZ GE35VA OUTDOOR UNIT ...
Страница 44: ...WALL MOUNTED Outdoor Unit M series WIRING DIAGRAM WALL MOUNTED C 42 OUTDOOR UNIT MUZ GE25VAH MUZ GE35VAH ...
Страница 45: ...WALL MOUNTED Outdoot Unit M series WIRING DIAGRAM WALL MOUNTED C 43 MUZ GE42VA OUTDOOR UNIT ...
Страница 46: ...WALL MOUNTED Outdoor Unit M series WIRING DIAGRAM WALL MOUNTED C 44 MUZ GE42VAH OUTDOOR UNIT ...
Страница 47: ...WALL MOUNTED Outdoot Unit M series WIRING DIAGRAM WALL MOUNTED C 45 MUZ GE50VA OUTDOOR UNIT ...
Страница 48: ...WALL MOUNTED Outdoor Unit M series WIRING DIAGRAM WALL MOUNTED C 46 MUZ GE50VAH OUTDOOR UNIT ...
Страница 49: ...WALL MOUNTED Outdoot Unit M series WIRING DIAGRAM WALL MOUNTED C 47 OUTDOOR UNIT MUZ GE60VA MUZ GE71VA ...
Страница 50: ...WALL MOUNTED Outdoor Unit M series WIRING DIAGRAM WALL MOUNTED C 48 MUZ HC25VA OUTDOOR UNIT ...
Страница 51: ...WALL MOUNTED Outdoot Unit M series WIRING DIAGRAM WALL MOUNTED C 49 OUTDOOR UNIT MUZ HC35VA MUZ HC35VAB ...
Страница 192: ...WALL MOUNTED Inverter Heat Pump M series INSTALLATION PROCEDURE WALL MOUNTED C 190 ...
Страница 199: ...WALL MOUNTED MSC MS MSH Series M series C 197 OPERATION AND ACTUATOR CONTROL WALL MOUNTED MUH MUH ...
Страница 202: ...WALL MOUNTED MSC MS MSH Series M series C 200 OPERATION AND ACTUATOR CONTROL WALL MOUNTED MSH g TIMER OPERATION ...
Страница 271: ...FLOOR STANDING MFZ KA VA Series M series OPERATION FLOOR STANDING C 269 ...
Страница 272: ...FLOOR STANDING MFZ KA VA Series M series OPERATION FLOOR STANDING C 270 f i save OPERATION ...
Страница 274: ...FLOOR STANDING MFZ KA VA Series M series OPERATION FLOOR STANDING C 272 i EMERGENCY TEST OPERATION ...
Страница 289: ...CEILING CASSETTE Inverter Heat Pump M series INSTALLATION PROCEDURE CEILING CASSETTE C 287 ...
Страница 290: ...CEILING CASSETTE Inverter Heat Pump M series INSTALLATION PROCEDURE CEILING CASSETTE C 288 ...
Страница 292: ...CEILING CASSETTE Inverter Heat Pump M series INSTALLATION PROCEDURE CEILING CASSETTE C 290 ...
Страница 293: ...CEILING CASSETTE Inverter Heat Pump M series INSTALLATION PROCEDURE CEILING CASSETTE C 291 ...
Страница 294: ...CEILING CASSETTE Inverter Heat Pump M series INSTALLATION PROCEDURE CEILING CASSETTE C 292 ...
Страница 300: ...CEILING CASSETTE M series CEILING CASSETTE C 298 ...
Страница 496: ...M series C 494 MULTI SYSTEM Inverter Heat Pump MULTI SYSTEMS WIRING DIAGRAM OUTDOOR UNIT MXZ 3B54VA ...
Страница 497: ...M series C 495 MULTI SYSTEM Inverter Heat Pump MULTI SYSTEMS WIRING DIAGRAM OUTDOOR UNIT MXZ 3B68VA ...
Страница 498: ...M series C 496 MULTI SYSTEM Inverter Heat Pump MULTI SYSTEMS WIRING DIAGRAM OUTDOOR UNIT MXZ 4B71VA ...
Страница 499: ...M series C 497 MULTI SYSTEM Inverter Heat Pump MULTI SYSTEMS WIRING DIAGRAM OUTDOOR UNIT MXZ 4B80VA ...
Страница 500: ...M series C 498 MULTI SYSTEM Inverter Heat Pump MULTI SYSTEMS WIRING DIAGRAM OUTDOOR UNIT MXZ 5B100VA ...