WALL-MOUNTED Cooling Only/Fixed Speed Heat Pump
M series
C-170
INST
ALLA
TION PROCEDURE
W
ALL-
MOUNTED
SPECIFICATIONS
*1 Connect to the power switch which has a gap of 3 mm or
more when open to interrupt the source power phase. (When
the power switch is shut off, it must interrupt all phases.)
*2 Use wires in conformity with design 60245 IEC 57.
*3 Never use pipes with thickness less than specified. The
pressure resistance will be insufficient.
*4 Use a copper pipe or a copper-alloy seamless pipe.
*5 Be careful not to crush or bend the pipe during pipe bending.
*6 Refrigerant pipe bending radius must be 100 mm or more.
*7 If pipe length exceeds 7 m, additional refrigerant (R410A)
charge is required. (No additional charge is required for
pipe length less than 7 m.)
Additional refrigerant = A × (pipe length (m) - 7)
*8 Insulation material : Heat resisting foam plastic 0.045 spe-
cific gravity
*9 Be sure to use the insulation of
specified
thickness. Exces-
sive thickness may cause incorrect installation of the indoor
unit and insufficient thickness may cause dew drippage.
Model
Power supply *1
Wire specifications *2
Pipe size
(thickness *3, *4)
Indoor unit
Outdoor unit
Rated
Voltage Frequency
Breaker capacity
(Indoor/outdoor)
Indoor Power
supply cord
Outdoor Power
supply
Indoor/outdoor
connecting wire
Gas / Liquid
MS(H)-GE50VB MU(H)-GE50VB 230 V
50 Hz
10 / 15 A
3-core
1.0 mm
2
3-core
1.5 mm
2
(10 m or less)
2.5 mm
2
(15 m or less)
2-core
1.0 mm
2
ø12.7 / 6.35 mm
(0.8 mm)
Pipe length and height difference
Max. pipe length
25 m
Max. height difference
10 m
Max. number of bends *5, *6
10
Refrigerant adjustment A *7
20 g/m
Insulation thickness *8, *9
8 mm
When the piping is to be
attached to a wall contain-
ing metals (tin plated) or
metal netting, use a chemi-
cally treated wooden piece
20 mm or thicker between
the wall and the piping or
wrap 7 to 8 turns of insula-
tion vinyl tape around the
piping.
To use existing piping, per-
form COOL operation for
30 minutes and pump down
before removing the old air
conditioner. Remake
flare
according to the dimension
for new refrigerant.
INSTALLATION DIAGRAM
ACCESSORIES
Check the following parts before installation.
<Indoor unit>
(1) Installation plate
1
(2)
Installation plate fixing screw
4 × 25 mm
7
(3) Remote controller holder
1
(4) Fixing screw for (3)
3.5 × 16 mm (Black)
2
(5) Battery (AAA) for (6)
2
(6) Wireless remote controller
1
(7) Felt tape
(For left or left-rear piping)
1
<Outdoor unit>
(8) Drain socket <MSH type only>
1
PARTS TO BE PROVIDED
AT YOUR SITE
(A) Indoor/outdoor unit connecting wire*
1
(B) Extension pipe
1
(C) Wall hole sleeve
1
(D) Wall hole cover
1
(E)
Pipe fixing band
2 to 5
(F) Fixing screw for (E) 4 x 20 mm
2 to 5
(G) Piping tape
1
(H) Putty
1
(I)
Drain hose
(or soft PVC hose, 15 mm inner
diameter or hard PVC pipe VP16)
1 or 2
(J) Refrigeration oil
1
(K) Power supply cord*
1
Units should be installed by licensed contractor
according to local code requirements.
120 mm
or more
100 mm
or more
350 mm or more
100 mm
or more
ro
m
m
27
ro
m
m
00
1/
er
o
m
tf
el
dn
atf
el
rof
er
o
m
gni
su(
gni
pi
p
kc
ab
)r
ec
ap
s
m
m
7
er
o
mr
o
200 mm
or more
* Note:
Place indoor/outdoor unit connecting wire (A)
and power supply cord (K) at least 1 m away
from the TV antenna wire.
Appearance of the outdoor unit may differ from some models.
100 mm
or more
After the leak test, apply
insulating material tightly
so that there is no gap.
Be sure to use wall hole sleeve (C) to
prevent indoor/outdoor connecting wire
(A) from contacting metal parts in the
wall and to prevent damage by rodents
in case the wall is hollow.
Cut off
the extra
length.
Pipe fixing
band (E)
Fixing
screw (F)
Indoor
unit
Wall hole
sleeve (C)
Wall hole cover (D)
Seal the wall hole
gap with putty (H).
Fix the pipe to
wall with pipe
fixing band (E).
Space for indoor unit working
Please leave the space as shown in the
picture for maintenance usage.
Indoor unit
Installation
plate
Space
250 mm or more
100 mm or more
(8)
(I)
Drain piping for outdoor unit
<MSH type only>
• Provide drain piping before indoor and
outdoor piping connection.
• Connect drain hose (I) I.D.15 mm as
shown in the illustration.
• Make sure to provide drain piping with
a downhill grade for easy drain flow.
Note:
Install the unit horizontally.
Do not use drain socket (8) in cold regions.
Drain may freeze and make the fan stop.
The outdoor unit produces condensate
during the heating operation. Select the in-
stallation place to ensure to prevent the
outdoor unit and/or the grounds from being
wet by drain water or damaged by frozen
drain water.
200 mm or more
Air inlet
Air outlet
Outdoor unit installation
2/4-10 mm × 21mm slot
800 mm
150
mm
500 mm
344.5 mm
285 mm
304-325 mm
40 mm
MS-GE50VB MSH-GE50VB
MU-GE50VB MUH-GE50VB
Содержание M-SERIES
Страница 6: ...M series C WALL MOUNTED ...
Страница 38: ...WALL MOUNTED Outdoor Unit M series WIRING DIAGRAM WALL MOUNTED C 36 MUH GD80VB OUTDOOR UNIT ...
Страница 39: ...WALL MOUNTED Outdoot Unit M series WIRING DIAGRAM WALL MOUNTED C 37 MUZ FD25VA MUZ FD35VA OUTDOOR UNIT ...
Страница 40: ...WALL MOUNTED Outdoor Unit M series WIRING DIAGRAM WALL MOUNTED C 38 OUTDOOR UNIT MUZ FD50VA ...
Страница 41: ...WALL MOUNTED Outdoot Unit M series WIRING DIAGRAM WALL MOUNTED C 39 MUZ FD25VABH MUZ FD35VABH OUTDOOR UNIT ...
Страница 42: ...WALL MOUNTED Outdoor Unit M series WIRING DIAGRAM WALL MOUNTED C 40 OUTDOOR UNIT MUZ FD50VABH ...
Страница 43: ...WALL MOUNTED Outdoot Unit M series WIRING DIAGRAM WALL MOUNTED C 41 MUZ GE25VA MUZ GE35VA OUTDOOR UNIT ...
Страница 44: ...WALL MOUNTED Outdoor Unit M series WIRING DIAGRAM WALL MOUNTED C 42 OUTDOOR UNIT MUZ GE25VAH MUZ GE35VAH ...
Страница 45: ...WALL MOUNTED Outdoot Unit M series WIRING DIAGRAM WALL MOUNTED C 43 MUZ GE42VA OUTDOOR UNIT ...
Страница 46: ...WALL MOUNTED Outdoor Unit M series WIRING DIAGRAM WALL MOUNTED C 44 MUZ GE42VAH OUTDOOR UNIT ...
Страница 47: ...WALL MOUNTED Outdoot Unit M series WIRING DIAGRAM WALL MOUNTED C 45 MUZ GE50VA OUTDOOR UNIT ...
Страница 48: ...WALL MOUNTED Outdoor Unit M series WIRING DIAGRAM WALL MOUNTED C 46 MUZ GE50VAH OUTDOOR UNIT ...
Страница 49: ...WALL MOUNTED Outdoot Unit M series WIRING DIAGRAM WALL MOUNTED C 47 OUTDOOR UNIT MUZ GE60VA MUZ GE71VA ...
Страница 50: ...WALL MOUNTED Outdoor Unit M series WIRING DIAGRAM WALL MOUNTED C 48 MUZ HC25VA OUTDOOR UNIT ...
Страница 51: ...WALL MOUNTED Outdoot Unit M series WIRING DIAGRAM WALL MOUNTED C 49 OUTDOOR UNIT MUZ HC35VA MUZ HC35VAB ...
Страница 192: ...WALL MOUNTED Inverter Heat Pump M series INSTALLATION PROCEDURE WALL MOUNTED C 190 ...
Страница 199: ...WALL MOUNTED MSC MS MSH Series M series C 197 OPERATION AND ACTUATOR CONTROL WALL MOUNTED MUH MUH ...
Страница 202: ...WALL MOUNTED MSC MS MSH Series M series C 200 OPERATION AND ACTUATOR CONTROL WALL MOUNTED MSH g TIMER OPERATION ...
Страница 271: ...FLOOR STANDING MFZ KA VA Series M series OPERATION FLOOR STANDING C 269 ...
Страница 272: ...FLOOR STANDING MFZ KA VA Series M series OPERATION FLOOR STANDING C 270 f i save OPERATION ...
Страница 274: ...FLOOR STANDING MFZ KA VA Series M series OPERATION FLOOR STANDING C 272 i EMERGENCY TEST OPERATION ...
Страница 289: ...CEILING CASSETTE Inverter Heat Pump M series INSTALLATION PROCEDURE CEILING CASSETTE C 287 ...
Страница 290: ...CEILING CASSETTE Inverter Heat Pump M series INSTALLATION PROCEDURE CEILING CASSETTE C 288 ...
Страница 292: ...CEILING CASSETTE Inverter Heat Pump M series INSTALLATION PROCEDURE CEILING CASSETTE C 290 ...
Страница 293: ...CEILING CASSETTE Inverter Heat Pump M series INSTALLATION PROCEDURE CEILING CASSETTE C 291 ...
Страница 294: ...CEILING CASSETTE Inverter Heat Pump M series INSTALLATION PROCEDURE CEILING CASSETTE C 292 ...
Страница 300: ...CEILING CASSETTE M series CEILING CASSETTE C 298 ...
Страница 496: ...M series C 494 MULTI SYSTEM Inverter Heat Pump MULTI SYSTEMS WIRING DIAGRAM OUTDOOR UNIT MXZ 3B54VA ...
Страница 497: ...M series C 495 MULTI SYSTEM Inverter Heat Pump MULTI SYSTEMS WIRING DIAGRAM OUTDOOR UNIT MXZ 3B68VA ...
Страница 498: ...M series C 496 MULTI SYSTEM Inverter Heat Pump MULTI SYSTEMS WIRING DIAGRAM OUTDOOR UNIT MXZ 4B71VA ...
Страница 499: ...M series C 497 MULTI SYSTEM Inverter Heat Pump MULTI SYSTEMS WIRING DIAGRAM OUTDOOR UNIT MXZ 4B80VA ...
Страница 500: ...M series C 498 MULTI SYSTEM Inverter Heat Pump MULTI SYSTEMS WIRING DIAGRAM OUTDOOR UNIT MXZ 5B100VA ...