WALL-MOUNTED Inverter Heat Pump
M series
INST
ALLA
TION PROCEDURE
W
ALL-
MOUNTED
C-185
SPECIFICATIONS
*1 Connect to the power switch which has a gap of 3 mm or
more when open to interrupt the source power phase. (When
the power switch is shut off, it must interrupt all phases.)
*2 Use wires in conformity with design 60245 IEC 57.
*3 Never use pipes with thickness less than specified. The
pressure resistance will be
insufficient.
*4 Use a copper pipe or a copper-alloy seamless pipe.
*5 Be careful not to crush or bend the pipe during pipe bending.
*6 Refrigerant pipe bending radius must be 100 mm or more.
*7 If pipe length exceeds 7 m, additional refrigerant (R410A)
charge is required. (No additional charge is required for
pipe length less than 7 m.)
Additional refrigerant = A × (pipe length (m) - 7)
*8 Insulation material : Heat resisting foam plastic 0.045
specific
gravity
*9 Be sure to use the insulation of
specified
thickness. Exces-
sive thickness may cause incorrect installation of the indoor
unit and
insufficient
thickness may cause dew drippage.
Model
Power supply *1
Wire
specifications
*2
Pipe size
(thickness *3, *4)
Indoor unit
Outdoor unit
Rated
Voltage Frequency
Breaker
capacity
Power supply Indoor/outdoor
connecting wire
Gas / Liquid
MSZ-GE22VA
MSZ-GE25VA
MSZ-GE35VA
MSZ-GE42VA
MUZ-GE25VA(H)
MUZ-GE35VA(H)
MUZ-GE42VA(H)
230 V
50 Hz
10 A
3-core
1.0 mm
2
4-core
1.0 mm
2
ø9.52 / 6.35 mm
(0.8 mm)
MSZ-GE50VA
MUZ-GE50VA(H)
16 A
3-core
2.0 mm
2
ø12.7 / 6.35 mm
(0.8 mm)
(GE25, 35, 42/GE50)
Pipe length and height difference
Max. pipe length
20/30 m
Max. height difference
12/15 m
Max. number of bends *5, *6
10
Refrigerant adjustment A *7
30/20 g/m
Insulation thickness *8, *9
8 mm
ACCESSORIES
Check the following parts before installation.
<Indoor unit>
(1) Installation plate
1
(2) Installation plate
fixing
screw
4 × 25 mm
5
(3) Remote controller holder
1
(4) Fixing screw for (3) 3.5 × 16 mm
(Black)
2
(5) Battery (AAA) for (6)
2
(6) Wireless remote controller
1
(7) Felt tape
(For left or left-rear piping)
1
<Outdoor unit>
(8) Drain socket (VA type only)
1
(9) Drain cap ø 33 (GE50VA only)
2
PARTS TO BE PROVIDED
AT YOUR SITE
(A) Indoor/outdoor unit connecting wire*
1
(B) Extension pipe
1
(C) Wall hole sleeve
1
(D) Wall hole cover
1
(E) Pipe
fixing
band
2 to 5
(F) Fixing screw for (E) 4 × 20 mm
2 to 5
(G) Piping tape
1
(H) Putty
1
(I)
Drain hose
(or soft PVC hose, 15 mm inner
diameter or hard PVC pipe VP16)
1 or 2
(J) Refrigeration oil
1
(K) Power supply cord*
1
* Note:
Place indoor/outdoor unit connecting wire (A)
and power supply cord (K) at least 1 m away
from the TV antenna wire.
110 mm
or more
100 mm
or more
100
mm
or more
350
mm
or more
100
mm
or more
45
mm
ro
/er
o
m
03
1
mm
ro
ero
m
rof
tfel
dn
a
tfel
kca
b
gni
pip
gni
su(
)re
ca
ps
01
mm
ro
ero
m
INSTALLATION DIAGRAM
Units should be installed by licensed contractor
according to local code requirements.
Indoor unit
Wall hole
sleeve (C)
Cut off the
extra length.
Pipe
fixing
band
(E)
Be sure to use wall hole
sleeve (C) to prevent
indoor/outdoor connecting
wire (A) from contacting
metal parts in the wall and
to prevent damage by
rodents in case the wall is
hollow.
Wall hole cover (D)
Seal the wall hole
gap with putty (H).
Fix the pipe to wall
with pipe
fixing
band (E).
Fixing screw
(F)
After the leak test, apply
insulating material tightly
so that there is no gap.
When the piping is to be at-
tached to a wall containing
metals (tin plated) or metal
netting, use a chemically
treated wooden piece 20
mm or thicker between the
wall and the piping or wrap
7 to 8 turns of insulation vi-
nyl tape around the piping.
To use existing piping, per-
form COOL operation for
30 minutes and pump down
before removing the old air
conditioner. Remake
flar
e
according to the dimension
for new refrigerant.
Appearance of the outdoor unit may differ from some
models.
(GE25, 35, 42/GE50)
200/500 mm or more
(GE25, 35, 42/GE50)
100/500 mm or more
(8)
(I)
(9)
(I)
Drain piping for outdoor unit
<VA type only>
• Provide drain piping before indoor and
outdoor piping connection.
• Connect drain hose (I) I.D.15 mm as
shown in the illustration.
• Choose one hole for draining, and
install drain socket (8). Close the re-
maining two holes with drain cap (9)
(GE50VA only).
• Make sure to provide drain piping with
a downhill grade for easy drain
flow.
Note:
Install the unit horizontally.
Do not use drain socket (8) in cold
regions. Drain may freeze and make the
fan stop. The outdoor unit produces
condensate during the heating operation.
Select the installation place to ensure to
prevent the outdoor unit and/or the
grounds from being wet by drain water or
damaged by frozen drain water.
Air inlet
Air outlet
Outdoor unit installation
(GE25, 35, 42/GE50)
2/4-10 mm × 21mm slot
800/840 mm
150/169
mm
500 mm
344.5/392
mm
28
5/
33
0
m
m
304-325/360
mm
40 mm
GE25, 35, 42VA
(8)
GE50VA
MSZ-GE22VA
MSZ-GE25VA
MSZ-GE35VA
MSZ-GE42VA
MSZ-GE50VA
MUZ-GE25VA
MUZ-GE35VA
MUZ-GE42VA
MUZ-GE50VA
MUZ-GE25VAH MUZ-GE35VAH MUZ-GE42VAH MUZ-GE50VAH
Содержание M-SERIES
Страница 6: ...M series C WALL MOUNTED ...
Страница 38: ...WALL MOUNTED Outdoor Unit M series WIRING DIAGRAM WALL MOUNTED C 36 MUH GD80VB OUTDOOR UNIT ...
Страница 39: ...WALL MOUNTED Outdoot Unit M series WIRING DIAGRAM WALL MOUNTED C 37 MUZ FD25VA MUZ FD35VA OUTDOOR UNIT ...
Страница 40: ...WALL MOUNTED Outdoor Unit M series WIRING DIAGRAM WALL MOUNTED C 38 OUTDOOR UNIT MUZ FD50VA ...
Страница 41: ...WALL MOUNTED Outdoot Unit M series WIRING DIAGRAM WALL MOUNTED C 39 MUZ FD25VABH MUZ FD35VABH OUTDOOR UNIT ...
Страница 42: ...WALL MOUNTED Outdoor Unit M series WIRING DIAGRAM WALL MOUNTED C 40 OUTDOOR UNIT MUZ FD50VABH ...
Страница 43: ...WALL MOUNTED Outdoot Unit M series WIRING DIAGRAM WALL MOUNTED C 41 MUZ GE25VA MUZ GE35VA OUTDOOR UNIT ...
Страница 44: ...WALL MOUNTED Outdoor Unit M series WIRING DIAGRAM WALL MOUNTED C 42 OUTDOOR UNIT MUZ GE25VAH MUZ GE35VAH ...
Страница 45: ...WALL MOUNTED Outdoot Unit M series WIRING DIAGRAM WALL MOUNTED C 43 MUZ GE42VA OUTDOOR UNIT ...
Страница 46: ...WALL MOUNTED Outdoor Unit M series WIRING DIAGRAM WALL MOUNTED C 44 MUZ GE42VAH OUTDOOR UNIT ...
Страница 47: ...WALL MOUNTED Outdoot Unit M series WIRING DIAGRAM WALL MOUNTED C 45 MUZ GE50VA OUTDOOR UNIT ...
Страница 48: ...WALL MOUNTED Outdoor Unit M series WIRING DIAGRAM WALL MOUNTED C 46 MUZ GE50VAH OUTDOOR UNIT ...
Страница 49: ...WALL MOUNTED Outdoot Unit M series WIRING DIAGRAM WALL MOUNTED C 47 OUTDOOR UNIT MUZ GE60VA MUZ GE71VA ...
Страница 50: ...WALL MOUNTED Outdoor Unit M series WIRING DIAGRAM WALL MOUNTED C 48 MUZ HC25VA OUTDOOR UNIT ...
Страница 51: ...WALL MOUNTED Outdoot Unit M series WIRING DIAGRAM WALL MOUNTED C 49 OUTDOOR UNIT MUZ HC35VA MUZ HC35VAB ...
Страница 192: ...WALL MOUNTED Inverter Heat Pump M series INSTALLATION PROCEDURE WALL MOUNTED C 190 ...
Страница 199: ...WALL MOUNTED MSC MS MSH Series M series C 197 OPERATION AND ACTUATOR CONTROL WALL MOUNTED MUH MUH ...
Страница 202: ...WALL MOUNTED MSC MS MSH Series M series C 200 OPERATION AND ACTUATOR CONTROL WALL MOUNTED MSH g TIMER OPERATION ...
Страница 271: ...FLOOR STANDING MFZ KA VA Series M series OPERATION FLOOR STANDING C 269 ...
Страница 272: ...FLOOR STANDING MFZ KA VA Series M series OPERATION FLOOR STANDING C 270 f i save OPERATION ...
Страница 274: ...FLOOR STANDING MFZ KA VA Series M series OPERATION FLOOR STANDING C 272 i EMERGENCY TEST OPERATION ...
Страница 289: ...CEILING CASSETTE Inverter Heat Pump M series INSTALLATION PROCEDURE CEILING CASSETTE C 287 ...
Страница 290: ...CEILING CASSETTE Inverter Heat Pump M series INSTALLATION PROCEDURE CEILING CASSETTE C 288 ...
Страница 292: ...CEILING CASSETTE Inverter Heat Pump M series INSTALLATION PROCEDURE CEILING CASSETTE C 290 ...
Страница 293: ...CEILING CASSETTE Inverter Heat Pump M series INSTALLATION PROCEDURE CEILING CASSETTE C 291 ...
Страница 294: ...CEILING CASSETTE Inverter Heat Pump M series INSTALLATION PROCEDURE CEILING CASSETTE C 292 ...
Страница 300: ...CEILING CASSETTE M series CEILING CASSETTE C 298 ...
Страница 496: ...M series C 494 MULTI SYSTEM Inverter Heat Pump MULTI SYSTEMS WIRING DIAGRAM OUTDOOR UNIT MXZ 3B54VA ...
Страница 497: ...M series C 495 MULTI SYSTEM Inverter Heat Pump MULTI SYSTEMS WIRING DIAGRAM OUTDOOR UNIT MXZ 3B68VA ...
Страница 498: ...M series C 496 MULTI SYSTEM Inverter Heat Pump MULTI SYSTEMS WIRING DIAGRAM OUTDOOR UNIT MXZ 4B71VA ...
Страница 499: ...M series C 497 MULTI SYSTEM Inverter Heat Pump MULTI SYSTEMS WIRING DIAGRAM OUTDOOR UNIT MXZ 4B80VA ...
Страница 500: ...M series C 498 MULTI SYSTEM Inverter Heat Pump MULTI SYSTEMS WIRING DIAGRAM OUTDOOR UNIT MXZ 5B100VA ...