However, when the coil frost prevention works while the indoor fan is OFF, the indoor fan speed becomes set speed.
The set temperature is determined from the initial room temperature.
a. COOL ( ) OPERATION
b. DRY ( ) OPERATION
d. HEAT ( ) OPERATION <MUH>
1. Coil frost prevention
When the temperature of indoor heat exchanger becomes too low, the coil frost prevention mode works.
The indoor fan operates at the set speed and the compressor stops. This mode continues until the temperature of indoor
heat exchanger rises.
ON with a beep tone.
2. Discharge temperature protection <MUH-GD80>
Discharge temperature protection is as same as COOL mode.
3. Defrosting
Defrosting starts when the temperature of outdoor heat exchanger becomes too low.
The compressor stops once, the indoor/outdoor fans stop, the 4-way valve reverses, and the compressor re-starts.
This mode continues until the temperature of outdoor heat exchanger rises or the fixed time passes.
c. FAN( ) OPERATION <MU>
(1) Press OPERATE/STOP (ON/OFF) button. OPERATION INDICATOR lamp of the indoor unit turns ON with a beep tone.
(2) Select FAN mode with OPERATION SELECT button.
(3) Select the desired fan speed. When AUTO, it becomes Low.
Only indoor fan operates.
Outdoor unit does not operate.
When the compressor is not operating or is starting, and the temperature of indoor heat exchanger and/or the room
temperature is low or when defrosting is being done, the indoor fan will stop or rotate in Very Low speed.
Cold air prevention control
2. Discharge temperature protection
<MU-GD80,MUH-GD80>
The compressor is controlled by the temperature of discharge temperature thermistor RT62 for excess
compressor discharge pressure.
Mode
COOL mode of
"I FEEL CONTROL"
DRY mode of
"I FEEL CONTROL"
HEAT mode of
"I FEEL CONTROL"
Initial room temperature
<MUH>
25 or more
23 to 25
Less than 23
e."I FEEL CONTROL" ( ) OPERATION
(1) Press OPERATE/STOP (ON/OFF) button on the remote controller.
OPERATION INDICATOR lamp of the indoor unit turns ON with a beep tone.
(2) Select "I FEEL CONTROL" mode with OPERATION SELECT button.
(3) The operation mode is determined by the room temperature at start-up of the operation.
Содержание M-SERIES
Страница 6: ...M series C WALL MOUNTED ...
Страница 38: ...WALL MOUNTED Outdoor Unit M series WIRING DIAGRAM WALL MOUNTED C 36 MUH GD80VB OUTDOOR UNIT ...
Страница 39: ...WALL MOUNTED Outdoot Unit M series WIRING DIAGRAM WALL MOUNTED C 37 MUZ FD25VA MUZ FD35VA OUTDOOR UNIT ...
Страница 40: ...WALL MOUNTED Outdoor Unit M series WIRING DIAGRAM WALL MOUNTED C 38 OUTDOOR UNIT MUZ FD50VA ...
Страница 41: ...WALL MOUNTED Outdoot Unit M series WIRING DIAGRAM WALL MOUNTED C 39 MUZ FD25VABH MUZ FD35VABH OUTDOOR UNIT ...
Страница 42: ...WALL MOUNTED Outdoor Unit M series WIRING DIAGRAM WALL MOUNTED C 40 OUTDOOR UNIT MUZ FD50VABH ...
Страница 43: ...WALL MOUNTED Outdoot Unit M series WIRING DIAGRAM WALL MOUNTED C 41 MUZ GE25VA MUZ GE35VA OUTDOOR UNIT ...
Страница 44: ...WALL MOUNTED Outdoor Unit M series WIRING DIAGRAM WALL MOUNTED C 42 OUTDOOR UNIT MUZ GE25VAH MUZ GE35VAH ...
Страница 45: ...WALL MOUNTED Outdoot Unit M series WIRING DIAGRAM WALL MOUNTED C 43 MUZ GE42VA OUTDOOR UNIT ...
Страница 46: ...WALL MOUNTED Outdoor Unit M series WIRING DIAGRAM WALL MOUNTED C 44 MUZ GE42VAH OUTDOOR UNIT ...
Страница 47: ...WALL MOUNTED Outdoot Unit M series WIRING DIAGRAM WALL MOUNTED C 45 MUZ GE50VA OUTDOOR UNIT ...
Страница 48: ...WALL MOUNTED Outdoor Unit M series WIRING DIAGRAM WALL MOUNTED C 46 MUZ GE50VAH OUTDOOR UNIT ...
Страница 49: ...WALL MOUNTED Outdoot Unit M series WIRING DIAGRAM WALL MOUNTED C 47 OUTDOOR UNIT MUZ GE60VA MUZ GE71VA ...
Страница 50: ...WALL MOUNTED Outdoor Unit M series WIRING DIAGRAM WALL MOUNTED C 48 MUZ HC25VA OUTDOOR UNIT ...
Страница 51: ...WALL MOUNTED Outdoot Unit M series WIRING DIAGRAM WALL MOUNTED C 49 OUTDOOR UNIT MUZ HC35VA MUZ HC35VAB ...
Страница 192: ...WALL MOUNTED Inverter Heat Pump M series INSTALLATION PROCEDURE WALL MOUNTED C 190 ...
Страница 199: ...WALL MOUNTED MSC MS MSH Series M series C 197 OPERATION AND ACTUATOR CONTROL WALL MOUNTED MUH MUH ...
Страница 202: ...WALL MOUNTED MSC MS MSH Series M series C 200 OPERATION AND ACTUATOR CONTROL WALL MOUNTED MSH g TIMER OPERATION ...
Страница 271: ...FLOOR STANDING MFZ KA VA Series M series OPERATION FLOOR STANDING C 269 ...
Страница 272: ...FLOOR STANDING MFZ KA VA Series M series OPERATION FLOOR STANDING C 270 f i save OPERATION ...
Страница 274: ...FLOOR STANDING MFZ KA VA Series M series OPERATION FLOOR STANDING C 272 i EMERGENCY TEST OPERATION ...
Страница 289: ...CEILING CASSETTE Inverter Heat Pump M series INSTALLATION PROCEDURE CEILING CASSETTE C 287 ...
Страница 290: ...CEILING CASSETTE Inverter Heat Pump M series INSTALLATION PROCEDURE CEILING CASSETTE C 288 ...
Страница 292: ...CEILING CASSETTE Inverter Heat Pump M series INSTALLATION PROCEDURE CEILING CASSETTE C 290 ...
Страница 293: ...CEILING CASSETTE Inverter Heat Pump M series INSTALLATION PROCEDURE CEILING CASSETTE C 291 ...
Страница 294: ...CEILING CASSETTE Inverter Heat Pump M series INSTALLATION PROCEDURE CEILING CASSETTE C 292 ...
Страница 300: ...CEILING CASSETTE M series CEILING CASSETTE C 298 ...
Страница 496: ...M series C 494 MULTI SYSTEM Inverter Heat Pump MULTI SYSTEMS WIRING DIAGRAM OUTDOOR UNIT MXZ 3B54VA ...
Страница 497: ...M series C 495 MULTI SYSTEM Inverter Heat Pump MULTI SYSTEMS WIRING DIAGRAM OUTDOOR UNIT MXZ 3B68VA ...
Страница 498: ...M series C 496 MULTI SYSTEM Inverter Heat Pump MULTI SYSTEMS WIRING DIAGRAM OUTDOOR UNIT MXZ 4B71VA ...
Страница 499: ...M series C 497 MULTI SYSTEM Inverter Heat Pump MULTI SYSTEMS WIRING DIAGRAM OUTDOOR UNIT MXZ 4B80VA ...
Страница 500: ...M series C 498 MULTI SYSTEM Inverter Heat Pump MULTI SYSTEMS WIRING DIAGRAM OUTDOOR UNIT MXZ 5B100VA ...