4.4 Indoor noise
(1) Principle of indoor noise
1)
Power levels
The Power level (PWL) of the sound source must be
understood when considering noise effects.
The following formula is used to obtain PWL from the
measured sound pressure data (values noted in catalog) in
an anechoic chamber.
PWL = SPLo + 20 logro + 11 [dB]. . . . . . . . . . . . . . . . . . . . . (I)
PWL : Sound source power level (dB)
SPLo : Measured sound pressure in anechoic
chamber (dB)
ro
: Measurement distance (m)
2) Principal model
Consider the room shown in Figs. 1 and 2.
●
Fig. 1 shows an example of the integrated main unit and
supply air diffuser (and return grille). This is equivalent to
the cassette-type Lossnay.
Fig. 2 shows an example of a separated main unit and
supply air diffuser (and return grille). This is equivalent to
the ceiling embedded-type Lossnay.
●
is the direct sound from the supply air diffuser (return
grille) and is the echo sound. ( to ) is the direct
sound that is emitted from the main unit and duct and
passes through the finished ceiling and leaks. is the
echo sound of .
3) Setting of noise
●
The following formula is used to obtain the noise value at a
position in the room.
SPL [dB] = PWL + 10 log + ........................(II)
(i)
(ii)
SPL : Sound pressure level at reception point [dB]
PWL : Sound source power level [dB]
Q
: Directivity factor (Refer to Fig. 3)
r
: Distance from sound source [m]
R
: Room constant [R =
α
S/(1 –
α
)]
α
: Average sound absorption ratio in room
(Normally, 0.1 to 0.2)
S
: Total surface area in room [m
2
]
48
CHAPTER 4
●
Characteristics
Sound source position
Centre of room
Centre of ceiling
Edge
Corner
a
b
c
d
Q
1
2
4
8
Fig. 1
Fig. 2
Fig. 3 (Sound source position and directivity factor Q)
3
1
Q
4
π
r
2
4
R
{
}
Main unit
r
o
Supply air diffuser
(return grille)
Supply air diffuser
(return grille)
c
b
a
d
Main unit
Содержание Lossnay PZ-41SLB-E
Страница 4: ...CHAPTER 1 Ventilation for Healthy Living Lossnay Unit ...
Страница 17: ......
Страница 18: ...CHAPTER 2 Lossnay Construction and Principle ...
Страница 24: ...CHAPTER 3 General Technical Considerations ...
Страница 41: ......
Страница 42: ...CHAPTER 4 Characteristics ...
Страница 56: ...53 CHAPTER 4 Characteristics ...
Страница 57: ...54 CHAPTER 4 Characteristics ...
Страница 59: ......
Страница 60: ...CHAPTER 5 System Design Recommendations ...
Страница 68: ...CHAPTER 6 Examples of Lossnay Applications ...
Страница 83: ......
Страница 84: ...CHAPTER 7 Installation Considerations ...
Страница 88: ...CHAPTER 8 Filtering for Freshness ...
Страница 96: ...CHAPTER 9 Service Life and Maintenance ...
Страница 98: ...CHAPTER 10 Ventilation Standards in Each Country ...
Страница 101: ......
Страница 102: ...CHAPTER 11 Lossnay Q and A ...
Страница 108: ...Lossnay Remote Controller ...
Страница 109: ......
Страница 197: ...MEMO ...
Страница 198: ...Y04 002 Jul 2004 MEE ...