─ 23 ─
No.
Problem
Factor
Corrective action
1 Nothing is displayed
on the remote
controller.
The ON/OFF lamp
does not blink.
The power of the Lossnay unit is
not ON.
Check the items described in (1) [1].
Faulty connection of the remote
controller transmission cable
Check the items described in (1) [2].
In one group, three or more
PZ-62DR-E controllers are
connected.
Only up to two PZ-62DR-E controllers can be
connected in one group.
In one group, 16 or more Lossnay
units are connected.
Only up to 15 Lossnay units can be connected
in one group.
The wiring length of the remote
controller exceeds 200 m.
The wiring length of the remote controller shall
be within 200 m.
In one group, two or more Lossnay
units are set as the main Lossnay
(with address number 1 or the
smallest number other than 0).
Only one Lossnay unit can be set as the main
Lossnay in one group.
2 The remote control-
ler continues to dis-
play “Please Wait”.
Error code “6831” is
displayed.
The remote controller is starting
up.
The remote controller displays “Please Wait”
during start-up for maximum three minutes.
Faulty connection of the remote
controller transmission cable
Check the items described in (1) [2].
The remote controller transmis-
sion cable is connected to the
terminal block (TB5 [A] [B]) for the
M-NET transmission cable.
Connect the remote controller transmission
cable to the terminal block (TM4 [1] [2]).
PZ-43SMF-E is used together.
PZ-62DR-E and PZ-43SMF-E cannot be used
together.
The old model remote controller
(PZ-61DR-E) is connected.
Use PZ-62DR-E remote controller.
3 It takes time for the
remote controller to
be fed with power
after turning the
Lossnay unit ON.
The Lossnay unit is starting up.
The remote controller is not fed with power dur-
ing start-up of the Lossnay unit for maximum
one minute.
(2) Failure mode 2: The remote controller does not work.
If the remote controller does not work, check the following items.
[1] PZ-62DR-E
[2] PZ-43SMF-E
No.
Problem
Factor
Corrective action
1 The power indicator
“
” is not displayed.
The power of the Lossnay unit is not
ON.
Check the items described in (1) [1].
Faulty connection of the remote con-
troller transmission cable
Check the items described in (1) [2].
In one group, three or more
PZ-43SMF-E controllers are connected.
Only up to two PZ-43SMF-E controllers can
be connected in one group.
In one group, 16 or more Lossnay
units are connected.
Only up to 15 Lossnay units can be con-
nected in one group.
The wiring length of the remote con-
troller exceeds 200 m.
The wiring length of the remote controller
shall be within 200 m.
In one group, two or more Lossnay
units are set as the main Lossnay
(with address number 1 or the small-
est number other than 0).
Only one Lossnay unit can be set as the
main Lossnay in one group.
(See the Lossnay Operating/Installation
Instructions or PZ-62DR-E Instruction Book.)