─ 33 ─
Error
Code
LED1
(green)
LED2
(red)
Symptom
Cause
Corrective action
6801
9
blinks
PZ-43SMF-E
communica-
tion error
Multiple PZ-43SMF-E transmission
cables are wired using multicore
cables.
Using the applicable cable, wire
the transmission cable away from
one another.
The power supply cable is too close
to the PZ-43SMF-E transmission
cable.
Wire the power supply cable at
least 5 cm away from the transmis-
sion cable.
Faulty connection of the
PZ-43SMF-E transmission cable
Check the transmission cable
connections.
The wiring length of the PZ-43SMF-E
transmission cable is longer than
specified (200 m or more).
Check the wiring length of the
transmission cable.
PZ-43SMF-E is connected to the ter-
minals (TB5 [A] [B]).
Connect PZ-43SMF-E to the termi-
nals (TM4 [1] [2]). (See the Lossnay
Operating/Installation Instructions or
PZ-62DR-E Instruction Book.)
6831
9
blinks
PZ-62DR-E
communica-
tion error (no
reception)
Faulty connection of the PZ-62DR-E
transmission cable
Check the items described in (1) [2].
If the error re-occurs, check for
noise on the transmission cable.
If the above does not correct the
problem, replace the Lossnay
control circuit board or PZ-62DR-E
remote controller.
PZ-62DR-E is connected to the ter-
minals (TB5 [A] [B]).
Connect PZ-62DR-E to the termi-
nals (TM4 [1] [2]). (See the Lossnay
Operating/Installation Instructions or
PZ-62DR-E Instruction Book.)
6832
9
blinks
PZ-62DR-E
communica-
tion error (syn-
chronization
recovery error)
Faulty connection of the PZ-62DR-E
transmission cable
Check the items described in (1) [2].
If the error re-occurs, check for
noise on the transmission cable.
If the above does not correct the
problem, replace the Lossnay
control circuit board or PZ-62DR-E
remote controller.
6833
9
blinks
PZ-62DR-E
communica-
tion error
(hardware
error)
Faulty connection of the PZ-62DR-E
transmission cable
Check the items described in (1) [2].
If the error re-occurs, check for
noise on the transmission cable.
If the above does not correct the
problem, replace the Lossnay
control circuit board or PZ-62DR-E
remote controller.
6834
9
blinks
PZ-62DR-E
communica-
tion error (start
bit detection
error)
Faulty connection of the PZ-62DR-E
transmission cable
Check the items described in (1) [2].
If the error re-occurs, check for
noise on the transmission cable.
If the above does not correct the
problem, replace the Lossnay
control circuit board or PZ-62DR-E
remote controller.
7113 10
blinks
Function set-
ting error
The group contains two or more Loss-
nay units with the same address.
Set unique addresses to these
units.
The model selection switch (SW6) is
not set correctly.
Make the SW6 setting appropriate
for the model. (See Chapter 7. (9)
Setting status record (page 47).)