14 The air supply fan periodi-
cally stops operating.
• When the outdoor temperature is -10 °C or lower, the fan is periodi-
cally stopped for approximately 10 minutes to prevent freezing of
the Lossnay core. (Cold region speci
fi
cations)
• When the Lossnay unit has duct connections and interlocked with
Mr. Slim or City Multi indoor units, the fan will stop during air condi-
tioner defrosting.
13 When PZ-60DR-E is used,
“
(“Locked” indica-
tor)” is displayed, and the
remote controller cannot be
operated.
In the following circumstances “
(“Locked” indicator)” is dis-
played, and the applicable function button cannot be operated.
• The operation lock is enabled. (Buttons other than the “ON/OFF”
button, or all buttons)
• When operating with the High / Low fan speed switching input (“Fan
Speed Adjustment” button)
• When operating with the bypass ventilation switching input.
(“Function selector” button)
• During the night purge operation. (“Function selector” button)
• When two remote controllers are used, one of the remote control-
lers is set to the function selection mode or the maintenance mode.
(All buttons)
Page
27
20, 21
22
23, 24
27 - 30
15 The Lossnay unit starts by
itself at night.
When the night purge setting is set to “on”, the night purge operation
will be performed at night
time.
Page
23, 24
16 Night purge operation does
not work even though Night
purge operation is set.
The night purge operation will not be performed in the following cir-
cumstances:
• The night purge conditions have not been satis
fi
ed.
• Lossnay has been started or stopped during the display of “
(Night purge)”.
• Night purge operation will not be performed when “CENTRAL” is
displayed.
Page
23, 24
17 Damper board does not
operate.
When the ventilation mode is switched with the remote controller, a
maximum delay of 30 seconds will be generated depending on the
timing.
Page
16
18 Delay operation does not
work even though Delay
operation is set.
• Delay operation will not start until 2 hours after the Lossnay stopped.
• When the pulse input setting is set to “on”, delay operation will not
start.
• When PZ-60DR-E and PZ-41SLB-E are used, operation will be ac-
cording to the setting of the remote controller.
Page
19
Operation monitor output will
not be output until several
seconds after the fan started
operation.
When the TM4 , output setting is set to operation monitor with
delay function 1 (SW2-8 is ON), the operation monitor will be output
10 seconds after the fan started operation.
Page
20
20 After operation has been
stopped with the remote
controller, the fan continues
to run for a while.
When the TM4 , output setting is set to operation monitor with
delay function 1 (SW2-8 is ON), or when the TM3 , output set-
ting is set to operation monitor with delay function 2 (SW5-6 is ON),
the fan will stop 3 minutes after stop with the remote controller.
Page
14
Page
14
No.
Error
Cause
Reference
12 When PZ-41SLB-E is used,
the operation will not be in
accordance with the set-
ting of the function selection
switch on the Lossnay circuit
board.
The settings will be disabled for switches (SW2-6, SW5-1, SW5-4,
SW5-5, SW5-7, and SW5-8).