Check items
Condition of trouble :
Remote controller display etc.
Frequency of trouble :
The date of starting operation and occur-
rence of trouble
Occurrence timing
With or without working drawings :
Equipment (including controllers), ca-
bles, wiring, and settings.
Applicable models
Lossnay
LGF-100GX-E
Remote controller
PZ-60DR-E
PZ-41SLB-E
PZ-52SF-E
Troubleshooting 1
The system will not start properly.
• Check the initialization checklist from
installation to operation (Table 1-1-1 to 1-1-4 ).
• Check the system checklist (Table 1-2-1 to 1-2-2).
Troubleshooting 2
• An error code displays on the remote
controller.
• The LED on the Lossnay circuit board is
blinking or lit up.
Check the checklist of error codes and
LED displays (Table 2-1 to 2-2).
Troubleshooting 3
The remote controller operation is
disabled or irregular.
The Lossnay operation is disabled or
irregular.
Troubleshooting 4
Check the checklist for the remote controllers
(Table 3-1 to 3-2).
Check the Lossnay checklist (Table 4).
Yes
No
No
This is normal.
No
No
Yes
Yes
Yes
7. Troubleshooting
Work precautions
• When removing or touching a transformer, printed circuit board or other parts, make sure to turn off the
earth leakage breaker.
• When removing the circuit board, always hold it at both ends and remove carefully so as not to apply force
to the surface mounted parts.
• When removing the circuit board, be careful of the metal edges on the board.
• When removing or inserting the connectors for the circuit board, hold the entire housing section. Never pull
on the lead wires.
• When servicing, be sure to recreate the malfunction two or three times before starting repairs.
• If it is thought that there is a printed circuit board malfunction, check for disconnected wires in the print pat-
tern, burnt parts or discoloration.
• If the printed circuit board is replaced, make sure that the switch settings on the new board are the same as
the old board.
7-1 Service
fl
owchart