10
CHAPTER
3
Specifications
CHAPTER
2
System configurations /
3. The conditions when Dx-coil unit is forcibly thermo-OFF/4. Water level sensor/5. Drain pump operation
1. Operation range
2. Connectable Lossnay unit and outdoor unit for each functions
3. Refrigerant pipe size information
Note
:
Dx-coil unit is only connectable to the Lossnay unit manufactured later than June 2016. Serial number of Lossnay unit
should be 16060001 or later.
The software version written in Lossnay PCB should be 05 or later.
Lossnay
Dx-coil unit
PZ-01RC
Outdoor air
-15 ˚C to +40 ˚C *1
-
-
Return air *2
+40 ˚C, 80 %RH or less
-
-
Ambient the unit
0 ˚C to +40 ˚C, 80 %RH or less
0 ˚C to +40 ˚C, 80 %RH or less
0 ˚C to +40 ˚C
*1: -15 ˚C to -10 ˚C : Intermittent operation takes 60 min. for ON and 10 min. for OFF.
-15
˚C or lower : Intermittent operation takes 55 min. for OFF and 5 min. for ON.
*2: Air conditioned room air.
Guaranteed operation
ranges [Outdoor]
Outdoor unit
PUHZ-ZRP35 and 50
PUHZ-ZRP71, 100 and 125
Cooling *3
-15 ˚C to +46 ˚C
-15 ˚C to +46 ˚C
Heating
-11 ˚C to +21 ˚C
-20 ˚C to +21 ˚C
*3: The optional air protection guide is required where the ambient temperature is lower than -5 ˚C.
[RA (Return Air) temperature control]
Dx-coil unit
GUG-01SL-E
GUG-02SL-E
GUG-03SL-E
Connectable Lossnay
LGH-50RVX-E
LGH-65RVX-E
LGH-80RVX-E LGH-100RVX-E LGH-150RVX-E
LGH-150RVXT-E
LGH-200RVX-E
LGH-200RVXT-E LGH-250RVXT-E
Connectable outdoor unit
PUHZ-ZRP35
PUHZ-ZRP35
PUHZ-ZRP50
PUHZ-ZRP71
PUHZ-ZRP100 PUHZ-ZRP100 PUHZ-ZRP125
[SA (Supply Air) temperature control]
Dx-coil unit
GUG-02SL-E
GUG-03SL-E
Connectable Lossnay
LGH-80RVX-E LGH-100RVX-E LGH-150RVX-E
LGH-150RVXT-E
LGH-200RVX-E
LGH-200RVXT-E LGH-250RVXT-E
Connectable outdoor unit
PUHZ-ZRP50
PUHZ-ZRP50
PUHZ-ZRP71
PUHZ-ZRP71
PUHZ-ZRP71
A
B
E
F
D
C
Dx-coil unit
Outdoor unit
Dx-coil unit
-
GUG-01SL-E
GUG-02SL-E
GUG-03SL-E
Ref. pipe size of unit
A / B
6.35 / 12.7
9.52 / 15.88
9.52 / 15.88
Outdoor unit
-
PUHZ-ZRP35
PUHZ-ZRP50
PUHZ-ZRP71
PUHZ-ZRP71, 100, 125
Ref. pipe size of unit
C / D
6.35 / 12.7
6.35 / 12.7
9.52 / 15.88
9.52 / 15.88
Pipe size between Dx-coil
unit and outdoor unit
E / F
6.35 / 12.7
6.35 / 12.7 *1
9.52 / 15.88
9.52 / 15.88
*1: To change the pipe size, PAC-SH30RJ and PAC-SH50RJ are needed to be installed at Dx-coil unit side.
Note:
GUG-01SL-E cannot be used for the SA temperature control function.