Cautions for using “Indoor negative pressure setting” to set exhaust fan speed bigger than supply fan speed.
When use “2 down” function, supply fan speed won’t go fan speed 3 and 4.
Therefore, Dx-coil will not be thermo ON.
Do NOT use this “2 down” function with Dx-coil unit.
The table below shows the Lossnay unit functions that cannot be used or restricted when the Dx-coil unit is connected.
3. Lossnay functions
2. Dip switch setting
The DIP-SW listed below must be set as the factory setting. If changed, please set to the factory setting.
PCB
Switch No.
Setting
PCB A of Dx-coil unit
SW1-2
SW1-3
SW1-6
Must be ON
SW1-1
SW1-4
SW1-5
SW1-8
SW2-6~2-8
SW3-1~3-3
SW3-6~3-8
SW4-1~4-8
SW6-1~6-2
Must be OFF
PCB B of Dx-coil unit
SW11-4~11-8
Must be OFF
PCB of Lossnay unit
SW7-4~7-10
Must be OFF
No.
Function
Remarks
5
Automatic recovery setting after
power interruption
Before setting this function, set function No.1 of PZ-01RC as Not
available. Refer to page 31 for more details.
6
Indoor negative pressure setting
[2 down]
Dx-coil unit can be set to thermo-ON when the supply fan is
operating at FS3 or FS4. If “2 down” is activated, Dx-coil unit will
NOT thermo-ON.
15
Interlock mode setting
“External input given priority” is prohibited to use.
“ON interlock mode” and “OFF interlock mode” are available only when
PZ-61DR-E is connected or M-NET controller is connected.
38
Calculated supply air temperature
display setting
“Calculated supply air temperature” will be different from the supply
air temperature from Dx-coil unit.
51
Automatic ventilation mode
Even when an indoor unit is interlocked with Lossnay unit,
Lossnay unit uses the conditions of setting temp. and mode
(cooling/heating/fan) of Dx-coil unit for automatic ventilation mode.
57
Prohibition of use of after-heater
By using the operation monitor output, Lossnay unit can be
connected to after-heater. However, use of after-heater in
conjunction with Dx-coil unit is prohibited.
*No. in the table shows the function setting No. in Lossnay unit installation manual and the technical manual.
Fan speed
display
Exhaust fan
Supply fan
Dx-coil unit
2down
4
4
2
Always thermo-OFF
3
3
1
2
2
1
1
1
1
Time
Mode
OFF
Temp. priority mode
Fan speed priority mode
Operation
ON
Units start
operation
8:00
10:00
When the external
signal changes the
fan speed to 2 or 1
Unit keeps operation at fan speed 3
and continue heating/cooling
OFF
CO
2
sensor etc.
Unit follows the external signal
and stop heating/cooling when fan speed 2 or 1
CO
2
sensor etc.
When the external
signal change the
fan speed depending
on CO
2
concentration
Units are OFF for more than 2 hours.
Settable from 1 to 4 hours with the step of 30 minutes increments.
Usage example
Following example shows using Fan priority mode after temp. priority mode for 2 hours; in the case of setting SW7-2 and SW7-3 both are ON.