45
CHAPTER
9
Model selection and capacity calculation
STEP3-2. Calculation of Dx-coil unit heating capacity
I: Read out characteristics from the specification sheet
III : Calculate the capacity of Dx-coil unit
LGH-100RVX-E + GUG-02SL-E + PUHZ-ZRP71
0 ˚CDB, 50 %RH
13.2 kW
1000 m
3
/h
RA Temp. control
7.5 m
8.1 kW
1.0
20 ˚CDB, 50 %RH
5.1 kW
(1) Calculation conditions
(2) Characteristics read out from specifications
(A) L Dx-coil System configuration
(B) Temperature control feature
(C) Ventilation air volume
(D) Outdoor air condition
(E) Return air condition
(F) Refrigerant pipe length
(1) Air volume factor
Air volume factor C
1
is the same as Example1-1.
(2) Air condition difference factor
Characteristics for heating written in specification sheet are based on air conditions of outdoor air: 7°CDB, 6°CWB and
return air: 20°CDB, 15°CWB.
(G) Heating capacity under specification condition
- Lossnay recovery
- Heating capacity of Dx-coil unit
II: Calculate Dx-coil inlet air (Lossnay outlet air) condition
The conditions of Lossnay outlet air are already calculated in STEP1-III
as shown below.
Example 1-2 condition
Outdoor air
Return air
Dx-coil inlet air
(Lossnay outlet air)
Dry-bulb temperature [˚C]
0
20
16
Wet-bulb temperature [˚C]
–3
13.8
10
Absolute humidity [kg/kg(DA)]
0.0019
0.0073
0.0051
Relative humidity [%]
50
50
46
Enthalpy [kJ/kg(DA)]
4.7
38.3
29.1
Specification condition
Outdoor air
Return air
Dx-coil inlet air
(Lossnay outlet air)
Dry-bulb temperature [˚C]
7
20
(B)17.4
Wet-bulb temperature [˚C] (A)6
15
12.8
Absolute humidity [kg/kg(DA)]
0.0054
0.0086
0.0073
Relative humidity [%]
87
59
59
Enthalpy [kJ/kg(DA)]
20.6
41.9
36.0
Adjusted Dx-coil unit capacity (heating)
= Capacity under specification condition x Air volume factor C
1
x Air Condition difference factor C
2
x Corrected refrigerant pipe length factor C
3
Read out the air volume factor C
2-2
by outdoor air wet-bulb temperature and Lossnay outlet air dry-bulb temperature using
the performance curves on the page 62.
Calculation steps
I
:
Read out characteristics from the specification sheet
II
:
Calculate Dx-coil inlet air (Lossnay outlet air) condition
III
:
Calculate the capacity of Dx-coil unit
IV
:
Calculate supply air conditions from Dx-coil unit