7.3.6
Program used for setting
Make sure to write the program above from the 0th step as the N:N network parameter setting program.
This program is not required to be executed because it becomes effective automatically when it is programmed in this position.
Note:
Setting of the parameters for the N:N network is started at the 0th step (LD M8038), and finished when any
instruction or device other than the program above is processed.
M8038
FNC 12
MOV
K 0
D8176
FNC 12
MOV
K 2
D8177
FNC 12
MOV
K 1
D8178
FNC 12
MOV
K 3
D8179
0
Station No. setting: Required for
master station (Set range: 0 to 7)
Refry count setting:
3 (3times)
Total number of slave
stations: 2
(Setting range: 1 to 7)
Refresh range setting:
Pattern 1
(Set range: 0 to 2)
Not required for
slave station
FNC 12
MOV
K 6
D8180
Comms time-out setting:
6 (60ms)
7