7.3.3
Setting the Refresh Range (D8178)
Set a value 0 to 2 to the special data register D8178. (Default = 0)
This setting is not requires for the slave station.
The devices used in each pattern are occupied by all the stations for the N:N network.
Communication
device
Refresh range
Pattern 0 Pattern 1
Pattern 2
Bit device (M)
0 point
32 points
64 points
Word device (D) 4 points
4 points
8 points
1) In the case of pattern 0
Station No.
Device No.
Bit device (M)
Word device (D)
0 point
4 points
No. 0
———
D0 to D3
No. 1
———
D10 to D13
No. 2
———
D20 to D23
No. 3
———
D30 to D33
No. 4
———
D40 to D43
No. 5
———
D50 to D53
No. 6
———
D60 to D63
No. 7
———
D70 to D73
7
FX
2N
-485-BD COMMUNICATION BOARD
N:N NETWORK
7-5