27

APPENDIX

A.1.2 Low Voltage Directive

We have self-confirmed our inverters as products compliant to the Low Voltage Directive (conforming standard EN 61800-5-1) and
placed the CE mark on the inverters. 

Outline of Instructions

If your application requires by installation standards an RCD (residual current device) as up stream protection please select according
to DIN VDE 0100-530 as following:
Single phase inverter type A or B
Three phase inverter only type B.
– Additionally, when selecting a residual current device (RCD), leakage current caused by the mains filter, the length of the shielded

motor cable and the carrier frequency must be taken into consideration.

– When connecting AC current using switches without a step function, brief asymmetrical loads may result in unwanted

triggering of the residual current device (RCD). It is recommendable here to use a Type B residual current device (RCD) Type B
with delayed actuation or to switch on all three phases simultaneously using a main contactor.

If you do not use a residual current operated protectice device, provide double or reinforced insulation between the inverter and
other equipment, or put a transformer between the main power supply and inverter.

Do not use a residual current operated protective device (RCD) as an electric shock protector without connecting the equipment
to the earth. Connect the equipment to the earth securely.

Wire the earth terminal independently. (Do not connect two or more cables to one terminal.)

Use the cable sizes on 

page 7

 under the following conditions.

– Ambient temperature: 40 °C maximum
– If conditions are different from above, select appropriate wire according to EN 60204 ANNEX C TABLE 5.

Use a tinned (plating should not include zinc) crimping terminal to connect the earth cable. When tightening the screw, be careful
not to damage the threads.

For use as a product compliant with the Low Voltage Directive, use PVC cable whose size is indicated on 

page 8

.

Use the moulded case circuit breaker and magnetic contactor which conform to the EN or IEC Standard. 

Use the inverter under the conditions of overvoltage category II (usable regardless of the earth (ground) condition of the power
supply), overvoltage category III (usable with the earthed-neutral system power supply, 400 V class only) specified in IEC664.

To use the inverter under the conditions of pollution degree 3, install it in the enclosure of IP54 or higher.

To use the inverter (IP20) outside of an enclosure in the enviroment of pollution degree 2, fix a fan cover with the fan cover
fixing srews enclosed.

On the input and output of the inverter, use cables of the type and size set forth in EN 60204 Appendix C.

The operating capacity of the relay outputs (terminal symbols A, B, C) should be 30 V DC, 0.3 A. (Relay outputs are basically
isolated from the inverter internal circuit.)

Control circuit terminals on 

page 5

 are safely isolated from the main circuit.

Fan cover 
fixing screws

Fan cover

Fan

Example for FR-D740-036SC

Example for FR-D740-160SC

Fan connector

Fan cover fixing screw

Fan cover

Fan

Fan connector

FR-D720S-070SC and 100SC, FR-D740-080SC or less

FR-D740-120SC or more

Содержание FR-D720S-008SC

Страница 1: ... a full knowledge of the equipment the safety information and the instructions Please forward this Installation Guideline and the CD ROM to the end user 1 2 3 4 5 PRODUCT DESCRIPTION 1 INSTALLATION OF THE INVERTER AND INSTRUCTIONS 2 OUTLINE DIMENSION DRAWING 4 WIRING 5 PRECAUTIONS FOR USE OF THE INVERTER 13 FAILSAFE OF THE SYSTEM WHICH USES THE INVERTER 15 PARAMETER 16 TROUBLESHOOTING 21 MAINTENAN...

Страница 2: ...ating applications please contact your nearest Mitsubishi Electric sales representative 앫 Although this product was manufactured under conditions of strict quality control you are strongly advised to install safety devices to prevent serious accidents when it is used in facilities where breakdowns of the product are likely to cause a serious accident 앫 Please do not use this product for loads othe...

Страница 3: ... inverter may only be mounted by safety persons Safety persons are defined as persons who 앫 have undergone the appropriate technical training Please note appropriate technical training is available from your local Mitsubishi Electric office Please contact your local office for locations and schedules 앫 have been instructed by the responsible machine operator in the operation of the machine and the...

Страница 4: ...lved in the wiring or inspection of this equipment should be fully competent to do the work 앫Always install the inverter before wiring Otherwise you may get an electric shock or be injured 앫If your application requires by installation standards an RCD residual current device as up stream protection please select according to DIN VDE 0100 530 as following Single phase inverter type A or B Three pha...

Страница 5: ...peration 앫When you have chosen the retry function stay away from the equipment as it will restart suddenly after an alarm stop 앫Since pressing key may not stop output depending on the function setting status provide a circuit and switch separately to make an emergency stop power off mechanical brake operation for emergency stop etc 앫Make sure that the start signal is off before resetting the inver...

Страница 6: ...brake which will prevent the machine and equipment from hazardous conditions if the inverter fails 앫When the breaker on the inverter primary side trips check for the wiring fault short circuit damage to internal parts of the inverter etc Identify the cause of the trip then remove the cause and power on the breaker 앫When the protective function is activated i e the frequency inverter switches off w...

Страница 7: ...NOTE For detailed description of the operation panel please refer to the Inverter FR D700 SC Instruction Manual LED Display 4 digit 7 segment display for operational values parameter numbers etc Unit Indication LED to indicate the current unit 앫 Hz Frequency 앫 A Current 앫 Off Voltage 앫 Flicker Set frequency Operation Status Display Lit or flicker during inverter operation 앫 RUN is lit Forward rota...

Страница 8: ... 3 for every extra 500 m up to 2500 m 91 Vibration 5 9 m s or less at 10 to 55 Hz directions of X Y Z axes CAUTION 앫 Install the inverter on a strong surface securely and vertically with bolts 앫 Leave enough clearances and take cooling measures 앫 Avoid places where the inverter is subjected to direct sunlight high temperature and high humidity 앫 Install the inverter on a non combustible surface FR...

Страница 9: ...Refer to the clearances beside Ambient temperature and humidity Clearances front Clearances side 5 cm 5 cm 5 cm Inverter Measurement position Measurement position Temperature 10 C to 50 C Humidity 90 RH maximum 10 cm or more 1 cm or more 1 10 cm or more 1 cm or more 1 1 cm or more 1 Leave enough clearances and take cooling measures 1 When using the inverters at the ambient temperature of 40 C or l...

Страница 10: ...S 014SC FR D720S 025SC 142 5 FR D720S 042SC 162 5 FR D720S 070SC 108 96 155 5 FR D720S 100SC 140 128 150 138 145 400 V class FR D740 012SC 108 96 128 118 129 5 FR D740 022SC FR D740 036SC 135 5 FR D740 050SC 155 5 FR D740 080SC 165 5 FR D740 120SC 220 208 150 138 155 FR D740 160SC W1 W H1 H D W W1 H1 H 2 ØC hole 1 ØC hole ...

Страница 11: ... the brake resistor The brake resistor can not be connected to the FR D720S 008SC and 014SC 5 Terminal input specifications can be changed by analog input specifications switchover Pr 267 initial settings in frame Set the voltage current input switch in the V position to select voltage input 0 5 V 0 10 V and I initial value to select current input 0 4 20 mA To use terminal 4 initial setting is cur...

Страница 12: ...tting may cause a fault failure or malfunction 앫 The output of the single phase power input specification is three phase 230 V FR D720S 008SC to 042SC FR D720S 070SC and 100SC FR D740 012SC to 080SC FR D740 120SC 160SC CAUTION 앫 Make sure the power cables are connected to the R L1 S L2 T L3 three phase 400 V class resp to the L1 N for single phase 200 V class Never connect the power cable to the U...

Страница 13: ... Sizes HIV mm2 1 AWG 2 PVC mm2 3 R L1 S L2 T L3 P 1 P U V W EarthCable Gauge R L1 S L T L3 P 1 P U V W R L1 S L2 T L3 P 1 P U V W EarthCable Gauge FR D740 012SC to 080SC 2 2 2 14 14 2 5 2 5 2 5 FR D740 120SC 3 5 2 3 5 12 14 4 2 5 4 FR D740 160SC 3 5 3 5 3 5 12 12 4 4 4 1 The recommended cable size is that of the HIV cable 600 V class 2 vinyl insulated cable with continuous maximum permissible temp...

Страница 14: ...ils Setting of Pr 72 PWM Frequency selection Carrier Frequency FR D720S 008SC 014SC 025SC 042SC 070SC 1 1 kHz or less 200 m 200 m 300 m 500 m 500 m 2 to 15 2 kHz to 14 5 kHz 30 m 100 m 200 m 300 m 500 m Setting of Pr 72 PWM Frequency selection Carrier Frequency FR D740 012SC 022SC 036SC 050SC 080SC 1 1 kHz or less 200 m 200 m 300 m 500 m 500 m 2 to 15 2 kHz to 14 5 kHz 30 m 100 m 200 m 300 m 500 m...

Страница 15: ... source Analog output AM Analog voltage output Frequency setting 10 Frequency setting power supply 2 Frequency setting voltage 4 Frequency setting current 5 Frequency setting common Communication Safety Stop Signal Type Terminal Name Terminal Name RS485 PU connector S1 Safety stop input Channel 1 S2 Safety stop input Channel 2 S0 Safety monitor output Open collector output SC Safety stop input ter...

Страница 16: ...crimping is inappropriate or the face is damaged 앫 Introduced products on bar terminals 1 A bar terminal with an insulation sleeve compatible with MTW wire which has a thick wire insulation 2 Applicable for terminal ABC Wire Size mm Bar Terminal Model Bar Terminal Crimping Tool With Insulation Sleeve Without Insulation Sleeve For UL Wire 1 0 3 AI 0 5 10WH CRIMPFOX 6 Phoenix Contact Co Ltd 0 5 AI 0...

Страница 17: ...coil lamp etc In no way must a voltage be short circuited by these relay contacts 앫 It is recommended to use the cables of 0 3mm to 0 75mm gauge for connection to the control circuit terminals The wiring length should be 30 m maximum 앫 The level of the control signals can be switched over between positive SOURCE and negative SINK logic The input signals are set to source logic when shipped from th...

Страница 18: ...function 앫Ensure the safety relay module and the D700 SC unit is mounted closely in enclosure meeting IP54 and all interconnection wiring is short and protected against open and short circuit faults Refer to ISO IEC13849 2 앫The approved safety relay module to ISO13849 1 EN954 1 safety category 3 or better shall be used in conjunction with FR D700 SC as shown in example In addition all other compon...

Страница 19: ...e input side of the inverter Use AC or DC reactors to reduce line propagated noise harmonics Use shielded motor power lines to reduce output noise For EMC correct installation refer to the Manual for Frequency Inverters and EMC 앫 Do not install a power factor correction capacitor varistor or arrester on the inverter output side This will cause the inverter to trip or the capacitor varistor or arre...

Страница 20: ...the inverter from the power supply to ensure safe maintenance and inspection work If using an MC for emergency stop during operation select an MC regarding the inverter input side current as JEM1038 AC 3 class rated current 앫 Handling of inverter output side magnetic contactor Switch the magnetic contactor between the inverter and motor only when both the inverter and motor are at a stop When the ...

Страница 21: ...urrent and consider the backup system such as checking up as below according to the level of importance of the system Check the motor running and motor current while the start signal is input to the inverter by comparing the start signal to the inverter and detected speed of the speed detector or detected current of the current detector Note that the motor current runs as the motor is running for ...

Страница 22: ...Electronic thermal O L relay 0 to 500 A Rated inverter current 10 DC injection brake operation frequency 0 to 120 Hz 3 Hz 11 DC injection brake operation time 0 to 10 s 0 5 s 12 DC injection brake operation voltage 0 to 30 6 4 3 13 Starting frequency 0 to 60 Hz 0 5 Hz 14 Load pattern selection 0 to 3 0 15 Jog frequency 0 to 400 Hz 5 Hz 16 Jog acceleration deceleration time 0 to 3600 s 0 5 s 17 MRS...

Страница 23: ...ied motor 0 1 3 13 23 40 43 50 53 0 72 PWM frequency selection 0 to 15 1 73 Analog input selection 0 1 10 11 1 74 Input filter time constant 0 to 8 1 75 Reset selection disconnected PU detection PU stop selection 0 to 3 14 to 17 14 77 Parameter write selection 0 1 2 0 78 Reverse rotation prevention selection 0 1 2 0 79 Operation mode selection 0 1 2 3 4 6 7 0 80 Motor capacity 0 1 to 7 5 kW 9999 9...

Страница 24: ...37 60 62 65 to 67 9999 60 Parameter Name Setting Range Initial Value 179 STR terminal function selection 0 to 5 7 8 10 12 14 16 18 24 25 37 61 62 65 to 67 9999 61 180 RL terminal function selection 0 to 5 7 8 10 12 14 16 18 24 25 37 62 65 to 67 9999 0 181 RM terminal function selection 1 182 RH terminal function selection 2 190 RUN terminal function selection 0 1 3 4 7 8 11 to 16 25 26 46 47 64 70...

Страница 25: ... time 0 1 to 1 s 1 s 556 Data output mask time 0 to 20 s 0 s 557 Current average value monitor signal output reference current 0 to 500 A Rated inverter current 561 PTC thermistor protection level 0 5 to 30 k 9999 9999 563 Energization time carrying over times 0 to 65535 0 564 Operating time carrying over times 0 to 65535 0 571 Holding time at a start 0 0 to 10 0 s 9999 9999 575 Output interruptio...

Страница 26: ...rminal 4 frequency setting bias 0 to 300 20 Parameter Name Setting Range Initial Value 126 905 1 Terminal 4 frequency setting gain frequency 0 to 400 Hz 50 Hz C7 905 1 Terminal 4 frequency setting gain 0 to 300 100 C22 922 1 Parameter for manufacturer setting Do not set C23 922 1 C24 923 1 C25 923 1 990 PU buzzer control 0 1 1 991 PU contrast adjustment 0 to 63 58 Pr CL Parameter clear 0 1 0 ALLC ...

Страница 27: ...atic restart or the execution of a reset 앫 If protective functions were activated i e the inverter switched off with an error message follow the instructions for error correction provided in the manual for the inverter Especially in the case of short circuits or earth contacts in the inverter output and mains overvoltages the cause of the fault must be determined prior to switching on again as a r...

Страница 28: ...an inverter 앫 Using the operation panel press the STOP RESET key to reset the inverter This may only be performed when a fault occurs 앫 Switch OFF the power once then switch it ON again after the indicator of the operation panel turns OFF 앫 Turn ON the reset signal RES for more than 0 1 s If the RES signal is kept ON Err appears flickers to indicate that the inverter is in a reset status OFF statu...

Страница 29: ...f during deceleration or stop E OV1 Regenerative overvoltage shut off during acceleration E OV2 Regenerative overvoltage shut off during constant speed E OV3 Regenerative overvoltage shut off during deceleration or stop E THT Inverter overload shut off electronic thermal relay function E THM Motor overload shut off electronic thermal relay function E FIN Fin overheat to to Fault E ILF Input phase ...

Страница 30: ...even for faulty demands of the safety function has to be performed in order to check the correct function of the restart prevention This test shall be carried out at system installation any software changes parameterization changes and or at least once per year For detailed checking procedure refer to the Transistorized Inverter FR D700 SC Safety stop function Instruction Manual 앫To avoid an elect...

Страница 31: ...when regenerative energy is large A brake unit FR BU2 may also be used 6 The power supply capacity varies with the value of the power supply side inverter impedance including those of the input reactor and cables 7 When operating the inverter with ambient temperature of 40 C maximum the rated output current is the value in parentheses Model FR D720S 첸첸첸SC EC 008 014 025 042 070 100 Rated motor cap...

Страница 32: ... with the dedicated EMC filter conforms with the EMC Directive in industrial environments and affix the CE marking on the inverter When using the inverter in a residential area take appropriate measures and ensure the conformity of the inverter used in the residential area NOTES 앫 First environment Environment including residential buildings Includes building directly connected without a transform...

Страница 33: ... one terminal 앫 Use the cable sizes on page 7 under the following conditions Ambient temperature 40 C maximum If conditions are different from above select appropriate wire according to EN 60204 ANNEX C TABLE 5 앫 Use a tinned plating should not include zinc crimping terminal to connect the earth cable When tightening the screw be careful not to damage the threads 앫 For use as a product compliant w...

Страница 34: ...unction dedicated to the Mitsubishi Electric constant torque motor this characteristic curve applies to operation at 6 Hz or higher During Operation In Storage During Transportation Ambient temperature 10 C to 50 C 20 C to 65 C 20 C to 65 C Ambient humidity 90 RH or less non condensing 90 RH or less non condensing 90 RH or less non condensing Maximum altitude 1000 m 1000 m 10000 m FR D720S SC EC C...

Страница 35: ...inverter or when using a multi pole motor or special motor In this case set 0A to the electronic thermal O L relay setting of the inverter For the external thermal relay determine the setting value in consideration of the current indicated on the motor s rating plate and the line to line leakage current Self cooling ability of a motor is reduced at low speed operation Use a motor with a built in t...

Страница 36: ...e rating or Listed UL 489 Molded Case Circuit Breaker MCCB must be employed Refer to page 28 A 2 4 Short Circuit Ratings 앫 200 V class Suitable for use in a circuit capable of delivering not more than 100 kA rms symmetrical amperes 264 V Maximum 앫 400 V class Suitable for use in a circuit capable of delivering not more than 100 kA rms symmetrical amperes 528 V Maximum A 2 5 Wiring For wiring the i...

Страница 37: ...31 APPENDIX ...

Страница 38: ...0 Fax 358 0 207 463 541 GREECE UTECO 5 Mavrogenous Str GR 18542 Piraeus Phone 30 211 1206 900 Fax 30 211 1206 999 HUNGARY MELTRADE Kft Fertő utca 14 HU 1107 Budapest Phone 36 0 1 431 9726 Fax 36 0 1 431 9727 LATVIA Beijer Electronics SIA Ritausmas iela 23 LV 1058 Riga Phone 371 0 784 2280 Fax 371 0 784 2281 LITHUANIA Beijer Electronics UAB Savanoriu Pr 187 LT 02300 Vilnius Phone 370 0 5 232 3101 F...

Отзывы: