INSTALLATION OF THE INVERTER AND INSTRUCTIONS
Unpack the inverter and check the capacity plate on the front cover and the rating plate on the inverter side face to ensure that
the product agrees with your order and the inverter is intact.
2.2
General Precaution
2.3
Environment
Before installation, check that the environment meets following specifications:
The bus capacitor discharge time is 10 minutes. Before starting wiring or inspection, switch power off, wait for more than 10 minutes,
and check for residual voltage between terminal P/+ and N/– with a meter etc., to avoid a hazard of electrical shock.
Ambient temperature
–10 °C to +50 °C (non-freezing)
Ambient humidity
90 % RH or less (non-condensing)
Atmosphere
Indoors (free from corrosive gas, flammable gas, oil mist, dust and dirt)
Altitude
Maximum 1000 m above sea level for standard operation. After that derate by 3 % for every extra 500 m up to 2500 m (91 %)
Vibration
5.9 m/s² or less at 10 to 55 Hz (directions of X, Y, Z axes)
CAUTION
앫
Install the inverter on a strong surface securely and vertically with bolts.
앫
Leave enough clearances and take cooling measures.
앫
Avoid places where the inverter is subjected to direct sunlight, high temperature and high humidity.
앫
Install the inverter on a non-combustible surface.
FR - D740 - 036 SC - EC
FR-D740-036SC-EC
FR-D740-036SC-EC
2.1
Inverter Type
Symbol
Voltage Class
D720S
Single-phase 200 V class
D740
Three-phase 400 V class
Symbol
Type Number
008
to
160
3-digit display
Capacity plate example
Rating plate example
Capacity plate
Rating plate
Serial number
Inverter type
Input rating
Output rating
Serial number
Inverter type
Symbol Control Circuit Terminal Specification
SC
Source-logic safety stop function model
Serial number description
A 0 X 123456
Product ID and Lot
Month of construction: 1 to 9 for Jan. to Sep., X to Z for Oct. to Dec.
Last digit of year of construction: 0 for 2010 for example
Alphabetical code of revision
DANGER