5
4
WIRING
4.1
Terminal Connection Diagram
R/L1
P1
P/ +
PR N/-
S/L2
T/L3
U
V
W
STR
STF
RH
RM
RL
SD
PC
RUN
SE
A
B
C
2
10(+5V)
2
3
1
4
(+)
(-)
5
*4
*1
*8
*2
*3
*5
SINK
SOURCE
V
I
*5
AM
5
(+)
(-)
*7
*9
*6
*6
24V
L1
N
S1
S2
SC
SO
24V
Source logic
Main circuit terminal
Control circuit terminal
Jumper
*1 DC reactor
When connecting a DC reactor, remove the
jumper across P1 and P/+.
Earth
Motor
3-phase
AC power
supply
Main circuit
Control circuit
Terminal functions vary with
the input terminal
assignment.
(Pr. 178 to Pr. 182)
Forward
rotation start
Reverse
rotation start
High speed
Medium speed
Low speed
Multi-speed selection
*2 When using terminals PC-SD as a 24 V DC power supply, take
care not to short across terminals PC-SD.
Safety stop input common terminal
Frequency setting signals (analog)
Terminal 4
input
(Current input)
0–5 V DC
0–5 V DC
0–10 V DC
PU
connector
*4 It is recommended to use
a 1 k
2 W potentiometer
when the frequency setting
signal is changed frequently.
Relay output
(Alarm output)
Running
Terminal functions vary by
Pr. 192 "
ABC terminal function
selection
".
Terminal functions vary with the output
terminal assignment.
(Pr. 190)
Open collector output common
Safety monitor output common
Sink/source common
Frequency
setting
potentiometer
1 k ,1/2 W
M
3~
Earth
Brake unit
(Option)
*8 Brake resistor (FR-ABR)
Install a thermal relay to prevent an overheat
and burnout of the brake resistor.
(The brake resistor can not be connected to
the FR-D720S-008SC and 014SC.)
*5 Terminal input specifications can be changed by analog input
specifications switchover (Pr. 267) (initial settings in frame).
Set the voltage/current input switch in the "V" position to
select voltage input (0–5 V/0–10 V) and "I" (initial value) to
select current input (0/4–20 mA.)
To use terminal 4 (initial setting is current input), set "4" in any
of Pr.178 to Pr.182 (input terminal function selection) to assign
the function, and turn ON AU signal.
Voltage/current
input switch
Relay output
Open collector output
Analog signal output
(0–10 V DC)
0–10 V DC
(Analog common)
4–20 mA DC
*3 Terminal input specifications
can be changed by analog
input specifications switcho-
ver (Pr. 73) (initial settings in
frame). Terminal 10 and ter-
minal 2 are used as PTC input
terminal (Pr. 561).
Earth
1-phase
AC power
supply
*7 A brake transistor is not built-in to the
FR-D720S-008SC and 014SC.
Control input signals (no voltage input allowed)
Single-phase power input
Safety stop signal
Safety stop input (Channel 2)
Shorting wire
*6 FR-D720S-008SC to 100SC: +, –
FR-D740-012SC to 160SC: P/+, N/–
MCCB
MC
MCCB
MC
Inrush
current limit
circuit
Terminal functions vary with the output
terminal assignment. (Pr. 197)
Safety monitor output
*9 Common terminal of terminal SO is terminal SE.
Output shutoff
circuit
Safety stop input (Channel 1)
24 V DC power supply/max. 100 mA load current
Contact input common (Source*)
Contact input common (Sink*),
24 V DC power supply common
*(Common for external power supply transistor)
Содержание FR-D720S-008SC
Страница 37: ...31 APPENDIX ...